Operating instructions

Speed monitor

DP2122

80287374 / 00   05 / 2021

GB

Summary of Contents for DP2122

Page 1: ...Operating instructions Speed monitor DP2122 80287374 00 05 2021 GB ...

Page 2: ...splay elements 16 7 1 Push rings pushbuttons 16 7 2 LEDs 16 7 3 Display 17 8 Menu 18 8 1 General 18 8 2 Menu structure 19 8 2 1 Operating mode 1 19 8 2 2 Operating mode 2 20 8 3 Parameters of the main menu 20 8 3 1 SSC1 speed monitor OUT1 20 8 3 2 SSC2 speed monitor OUT2 21 8 3 3 EF extended functions 21 8 4 Parameters for OUT1 SSC1 21 8 4 1 ModE switch point mode 21 8 4 2 LoGc switch point logic ...

Page 3: ... 8 7 3 FLASH_OFF deactivate flashing of the display 25 8 7 4 SSC counter switching counter 25 8 7 5 internal_temperature operating temperature microcontroller 25 8 7 6 operation_hours operating hours 25 8 7 7 Application specific tag 26 8 7 8 Location tag 26 8 7 9 Function tag 26 9 Parameter setting 27 9 1 Parameter setting in general 27 9 1 1 Example ModE switch point mode for OUT2 27 9 2 Notes o...

Page 4: ...unit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or interference Information Supplementary note 1 2 Warnings used CAUTION Warning of personal injury w Slight reversible injuries may result ...

Page 5: ...roduct and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Ò Intended use If the operating instructions or the technical data are not adhered to personal injury and or damage to property may occur The manufacturer assumes no liability or warrant...

Page 6: ... with the set parameters 2 3 4 5 6 6 1 Fig 1 Example speed monitoring of a drive shaft on a conveyor belt 1 Conveyor belt 2 Pulse pick up on the drive shaft 3 DP2122 4 Transistor output e g to control a light indicator horn or relay 5 Transistor output IO Link 6 Signals depending on the selected switching function The unit is not suited for environments with particular requirements on mechanical s...

Page 7: ...1167 d 00 04 8f h IO Link parameter CMPT HZ_M default Operating mode 2 rpnM Description Displays the frequency in revolutions per minute RPM Application Converted values in RPM IODD designation DP2122 Status_B CMPT rpnM IO Link device ID 1294 d 00 05 0e h IO Link parameter CMPT rpnM In operating mode 2 the display of the unit always shows kRPM Manual selection of the operating mode CMPT indication...

Page 8: ...ic information and parameter addresses at www ifm com 4 3 Standard IO wiring Switch points standard IO mode can also be used in combination with the standard inputs of a PLC OUT1 and OUT2 can be switched to digital inputs e g standard input modules OUT1 and OUT2 can be evaluated via two digital inputs and implement a window function Voltage supply pin 1 and 3 can be done via the input modules With...

Page 9: ...ameter LoGc nc low active SP1 Overspeed Reset point underspeed Switch point SP1 H Overspeed Switch point underspeed Reset point If a set rotational speed is not reached this is signalled by the switching signal as closed 1 Power on delay time 2 Start up delay 3 normally open 4 normally closed 4 4 2 Window mode SP2 SP2 SP2 H H OFF SSC SP1 SP1 H SP1 H ON OFF Fig 6 NO IO Link parameter LoGc no high a...

Page 10: ...me 2 Start up delay 3 Normally open 4 Normally closed 4 4 3 Two point mode SP2 SP1 SP2 H OFF ON SSC SP1 Fig 8 NO IO Link parameter LoGc no high active SP1 Overspeed Switch point underspeed Reset point SP2 Overspeed Reset point underspeed Switch point If a set rotational speed is not reached this is signalled by the switching signal as open SP2 SP1 SP2 H ON SSC SP1 OFF Fig 9 NC IO Link parameter Lo...

Page 11: ...ed SP1 and during start up delay Open off Rotational speed SP2 Switching function NC transistor output LED yellow Description Closed on Rotational speed SP2 Open off Rotational speed SP1 and during start up delay 4 4 6 Switching delays The switching delay enables filtering of input signals The switching delay is activated or restarted by a positive switching edge of the input signal Only if the in...

Page 12: ... enables the suppression of error signals when a plant is started It is effective after the power supply is applied and is dependent on a low speed If the drive is frequently switched on and off it is advisable to couple the voltage supplies of the drive and the speed monitor By doing so the start up delay is active every time the motor is turned on If a coupled connection of the voltage supplies ...

Page 13: ... are protected from mechanical stress such as shock and vibration u If necessary fix the unit with a clamp use M4 screw or cable tie Fig 10 Mounting clip Fig 11 Mounting clip with attached unit The mounting clip is not supplied with the unit More information about available accessories at www ifm com GB ...

Page 14: ... IEC 61010 1 or class 2 according to UL1310 Output reaction to overload or short circuit For self protection of the output in case of excessive thermal load due to short circuit or overload the output driver starts clocking If a short circuit overload continues for several hours the driver may be damaged u Disconnect power u Connect the unit as follows 2 1 4 3 2 1 3 1 2 4 5 Fig 12 Electrical conne...

Page 15: ...Carry out the fitting according to the indications of the cable manufacturer Maximum tightening torque on the connector side 1 8 Nm Maximum tightening torque o the socket side 1 3 0 1 Nm 6 2 Removing the connector u Press the connector against the unit and simultaneously loosen the coupling nut 6 3 Cable length Without IO Link communication 30 m on each side With IO Link communication 20 m on the ...

Page 16: ...ion of the parameter and acknowledgement of a parameter value Down Selection of a parameter Setting a parameter value scrolling by holding down incremen tally by pressing repeatedly Up To ensure correct operation of the push rings buttons do not install or place the unit directly on a metal surface For the installation use the mounting clip Ò Installation 7 2 LEDs LED Colour Status Designation I O...

Page 17: ...of measurement depends on the parameter C uni In the operating mode the input frequency is displayed The display value is scaled automatically in the basic setting Operating mode 1 Manual scaling via parameter C FEP is activated by parameter ScAL Manual scaling Display constraint to a step increment of 1 Hz Operating mode 2 Process or parameter values with more than 4 digits cannot be fully displa...

Page 18: ...rs of the unit directly on the unit via the menu Parameter setting Ò 27 or via an IO Link tool Access via an IO Link tool has a higher priority than parameter setting via the menu Parameter cloning and parameter setting backup is possible with an IO Link tool Some parameters can only be set via the IO Link interface Parameters adjustable via IO Link Ò 25 If the unit was locked via IO link it can a...

Page 19: ... 2000 SP2 0 1 1999 HYS 0 5 100 dS 0 99 99 dr 0 99 99 rES dSt 0 999 9 ScAL OFF cccc ccc c cc cc c ccc C FEP 500 4000 C uni coLr rEd GrEn r1ou G1ou r cF G cF cFH 0 2 2000 cFL 0 1 1999 diS b On OFF diS U d1 d2 d3 CMPT HZ_M rpn_M Lo Hi Lo Hi 3 EF P n 1 Operating mode Ò Operating modes 2 Main menu Ò Parameters of the main menu 3 Eextended functions Ò Parameters of the extended functions EF Ò Parameter ...

Page 20: ...dr 0 99 99 rES dSt 0 999 9 1 99 PrSC Lo Hi Lo Hi coLr rEd GrEn r1ou G1ou r cF G cF cFH 0 002 120 0 cFL 0 001 119 9 diS b On OFF diS U d1 d2 d3 CMPT HZ_M rpn_M 1 Operating mode Ò Operating modes 2 Main menu Ò Parameters of the main menu 3 Eextended functions Ò Parameters of the extended functions EF Ò Parameter list and factory settings 8 3 Parameters of the main menu 8 3 1 SSC1 speed monitor OUT1 ...

Page 21: ... the upper switch point In Single point mode SP1 is adjustable over its entire value range In Two point mode and Window mode the lower limit is restricted by SP2 It always applies SP1 SP2 8 4 4 SP2 switch point 2 Threshold for the lower switch point Only active in the switch point modes Two point mode and Window mode In Single point mode the existing setting of SP2 is ignored When changing to Two ...

Page 22: ...n see Parameters for OUT1 SSC1 Ò 21 8 6 Parameters of the extended functions EF 8 6 1 rES restore factory setting Resets all parameters to the Factory settings Ò 32 u Select rES u Press u Press and hold or until is displayed u Briefly press 8 6 2 Lo Hi min max measured input values Lo lowest measured value Hi highest measured value Delete memory u Select Hi or Lo u Press and hold or until is displ...

Page 23: ...4 Hz C FEP 500 8 6 5 C FEP custom user endpoint for frequency Settings for scaled display values The parameters are only displayed in operating mode 1 and when ScAL is set to cccc ccc c cc cc or c ccc All displayed frequency speed values are interpolated based on a 2 point approximation IO Link process data and parameters are not influenced by scaling 2 3 1 f Hz C FEP 2000 2000 200 4000 C FEP U f ...

Page 24: ... w printouts gn green rd red r cF red when the measured value is between the values cFL and cFH G cF green when the measured value is between the values cFL and cFH 8 6 8 cFH cFL upper lower value for colour change If coLr is set to r cF or G cF u Select cFH and set the upper limit Setting range corresponds to the measured values The lowest setting value is cFL u Select cFL and set the lower limit...

Page 25: ...reset to the factory settings with the exception of CMPT 8 7 Parameters adjustable via IO Link The following functions or parameters are only available via IO Link tools 8 7 1 C uni customer specific unit Customer specific unit with max 4 characters 8 7 2 FLASH_ON activate flashing of the display Used to identify a unit Display flashes and shows dEVC 8 7 3 FLASH_OFF deactivate flashing of the disp...

Page 26: ...fault value can be freely defined by the customer 8 7 8 Location tag Customer specific location tag of the unit max 32 characters long Default value can be freely defined by the customer 8 7 9 Function tag Customer specific function tag of the unit max 32 characters long Default value can be freely defined by the customer ...

Page 27: ...ss until SSC2 is displayed u Press to get to the extended functions menu w The first parameter of the extended functions is displayed 3 Change to the programming mode of the parameter u Press to change to the programming mode w The currently set parameter value is displayed 4 Select or change the parameter value here e g und u Press or for at least 2 s w The currently set parameter value flashes h...

Page 28: ...the unit is not locked Customer locking If C Loc is displayed when an attempt is made to modify a parameter value an IO Link communication is active temporary locking Software locking If S Loc is displayed the sensor is permanently locked via software This locking can only be removed using an IO Link parameter setting software 9 2 2 Timeout If no button is pressed for 30 s during parameter setting...

Page 29: ...monitor DP2122 29 10 Operation After power on the unit is in the operating mode SIO It carries out its measurement and evaluation functions and provides output signals according to the set parameters Menu GB ...

Page 30: ...g via pushbuttons locked due to active IO Link trans mission Wait until parameter setting via IO Link is finished S Loc any any any Parameter setting via pushbuttons disabled by software Unlocking only possible via IO Link interface IO Link parameter setting software Loc any any any Parameter setting via pushbuttons disabled Unlock pushbuttons OL any on any Process value too high measured frequenc...

Page 31: ...supply u Clean the unit from dirt using a soft chemically untreated and dry micro fibre cloth The operation of the unit is maintenance free Only the manufacturer is allowed to repair the unit u After use dispose of the device in an environmentally friendly way in accordance with the applicable national regulations GB ...

Page 32: ...t logic OUT2 no no nc SSC2 SP1 Switch point 1 OUT2 22 SSC2 SP2 Switch point 2 OUT2 20 SSC2 HyS Switch point hysteresis OUT2 10 SSC2 dS Switching delay OUT2 0 s SSC2 dr Switch off delay OUT2 0 s rES Factory setting Lo Lowest measured input value Hi Highest measured input value dSt Startup delay time 0 s PrSC only operating mode 2 Prescaler 1 ScAL only operating mode 1 Set decimal point OFF OFF cccc...

Page 33: ...2 33 Parameters Factory settings User settings diS b Display power on On On OFF diS U Refresh rate of the displayed value d2 200 ms OFF d1 50 ms d2 200 ms d3 600 ms CMPT Indication of the operating mode HZ_M HZ_M rpnM GB ...