DP2122
Speed monitor
14
6 Electrical connection
The device must be connected by a qualified electrician.
Observe the national and international regulations for the installation of electrical equipment.
Voltage supply according to EN 50178, SELV, PELV.
CAUTION
Input current is not limited.
w
No fire protection.
u
Protect circuits.
Touchable surfaces of the unit are insulated to the circuits with basic insulation according to IEC
61010-1.
u
Protect circuits.
Potential
M12 connector
①
Fuse
L+ / supply voltage
Pin 1
≤ 2 A
Required tripping characteristic of the fuses:
T
fuse
≤ 120 s at max. 6.25 A (fire protection)
Alternatively supply the unit via a limited energy circuit according to IEC 61010-1 or class 2 according
to UL1310.
Output reaction to overload or short circuit:
For self-protection of the output in case of excessive thermal load (due to short circuit or
overload), the output driver starts clocking. If a short circuit / overload continues for several
hours, the driver may be damaged!
u
Disconnect power.
u
Connect the unit as follows:
2
1
4
3
2
1
3
1
2
4
5
Fig. 12: Electrical connection
1:
4-pole M12 connector
(Output side)
• Pin 1: L+ / supply voltage
• Pin 2: OUT2 / digital output 2
• Pin 3: L- / supply voltage
• Pin 4: OUT1 / IO-Link (C/Q)
2:
5-pole M12 female connector
(Input side)
• Pin 1: L+
• Pin 2: ENABLE for start-up bridging in SIO mode
• Pin 3: L-
• Pin 4: IN1 / digital input 1
• Pin 5: not used
The unit must not be externally supplied via the 5-pole M12 input socket
②
.
Always use the provided connection cables to connect other devices.
See also application examples (
Ò
Intended use)