IO-Link Master with EtherCAT Interface DataLine 8 Ports IP 65 / IP 66 / IP 67
97
Index
Sub-
index
Description
Possible values
Datentyp /
Zugriff
0
default if device does not support
Emergency sending
1
new diagnosis messages shall be sent
as Emergency message
Bit 1:
Disable info messages
0
Info messages are stored in the
diagnosis message queue (default)
1
Info messages will not be stored in the
diagnosis message queue
Bit 2:
Disable warning messages
0
Warning messages are stored in the
diagnosis message queue (default)
1
Warning messages will not be stored
in the diagnosis message queue
Bit 3:
Disable error messages
0
Error messages are stored in the
message queue (default)
1
Error messages will not be stored in
the diagnosis message queue
Bit 4:
Mode selection for diagnosis history
handling
0
Overwrite Mode
1
Acknowledge Mode
Bit 5:
Overwrite/Discard Information
Overwrite Mode:
1
unacknowledged messages have been
overwritten (=buffer overrun)
(Subindex 0x03 is set to 0)
Acknowledge Mode:
1
message buffer is full with
unacknowledged messages and a new
massage is discarded.
Bit 6...15
reserved
0x06
Diagnosis Message 01
→
Mapping: Diagnosis Message
(
→ S.
OCTET
STRING / r
...
0x00x46 Diagnosis Message 64
r ... read only
r/w ... read and write