IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
85
Command response
34361
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
4
Port No. (LSB)
5
Port No. (MSB)
6
reserved
7
reserved
8
reserved
9
reserved
10
Handshake
0x30
11
Result
12
Fail-safe mode
13...45
reserved
Legend:
[Port No.]
Number of the IO-Link port
Port No. = 0x1234
Port No. (MSB) = 0x12
Port No. (LSB) = 0x34
16 Bit
0x01
Port X01
0x02
Port X02
...
0x04
Port X04
[Handshake]
Status of the execution of the command
1 Bit
0x0
command is executed
0x1
execution of the command was
successful
[Result]
Error indication
1 Bit
0x0
no error
0x1
error occured
[Fail-safe Mode]
Behaviour of the outputs when the
EtherNet/IP connection is interrupted
8 Bit
0x00
No Fail-safe
0x01
Fail-safe Reset Value
0x02
Fail-safe Old Value
0x03