IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
33
9.1.9
IO-Link Ports: Set fails-safe values
34329
For the configuration mode "Independent" the user can set fail-safe values for the outputs of IO-Link
ports X01...X04. The fail-safe values will be activated in case of an interuption of the EtherNet/IP
conection.
To set the fail-safe values:
►
Select [Port x] menu (x = 1...4).
>
The menu page shows the current settings.
►
Set the following parameters as required:
Name
Description
Possible values
[Fail-safe digital out]*
Fail-safe value of the output for operating mode
"Digital Output (DO)"
[Reset]
OFF
[Old]
old value
[Set]
ON
[Fail-safe IO-Link]*
Fail-safe value of the output for operating mode
"IO-Link"
[Off]
no Fail-safe
[Reset]
Fail-safe: OFF
[Old
Fail-safe: old value
[Pattern]
Fail-safe: byte pattern
* ... Parameter only changeable, if the connection to the EtherNet/IP controller is closed
► Save changed values on the device.
>
9.1.10
Info: Show device information
34065
To read the general information of the ifm IO-Link master:
►
Select [Info] menu.
>
The menu page shows the current settings.
Name
Description
Possible values
[Product code]
Article number of the IO-Link master
AL1120
[Device family]
Device family of the IO-Link master
IO-Link master
[Vendor]
Vendor
ifm electronic gmbh
[SW-Revision]
Firmware of the IO-Link master
[HW revision]
Hardware version of the IO-Link master
[Bootloader revision]
Bootloader version of the IO-Link master
[Serial number]
Serial number