(C) IDM ENERGIESYSTEME GMBH

6. Connection of the refrigerant circuit

Installation instructions AERO SLM

34

connection of the refrigerant circuit

SL-Modul

6.3. Connection of the indoor unit on refri-

gerant side

The refrigerant pipes will be soldered to the indoor 
unit. The soldered connections must be made accor-
ding to the requirements of the cooling technology 
by a trained refrigeration engineer licensed by iDM 
Energiesysteme GmbH.
The connections for the refrigerant pipes are on the 
backside of the AERO SLM indoor unit.
To connect the refrigerant pipes, the protecting caps 
must be cut.
The refrigerant pipes must be cut with a pipe cutter to 
the required length. The burrs must be removed with 
a deburring tool.
Soldering must be carried out under inert gas (Nitro-
gen N2)!

In the scope of delivery of the AERO SLM are two pcs. 
pipe bending springs. With these bending springs, 
the heating installer has the option of bending the 
refrigerant pipes on the backside of the heat pump in 
the appropriate direction, depending on the desired 
routing of the refrigerant connection pipes (see the 
red and green dashed lines in the 

fi

 gure above).

When installing the AERO SLM, make sure that the 
distance to the wall on the backside is large enough 
to solder the refrigerant connection lines properly.

The connection of the refrigerant pipes and 
the refrigerant may only be handled by 
trained experts authorised by iDM Energie-
systeme GmbH! 

The refrigerant fl ow through the indoor unit 
can lead to fl ow noises!

In accordance with Regulation (EU) 
No. 517/2014 of 01/01/2015 on certain 

fl

 uorinated greenhouse gases and in 

accordance with Regulation (EU) No. 
1516/2007, the operator of a heat pump 
system is obligated to carry out regular 
leak tests by a certi

fi

 ed professional. The 

interval may vary depending upon the 
CO2 equivalent capacity. The inspection 
intervals are indicated in the Check- and 
Servicebook.

Pipe bending spring

The refrigerant pipes are ex-factory sol-
dered. The pipes must not be unsoldered 
during commissioning, but must be cut o

 !   

Summary of Contents for AERO SLM 3-11

Page 1: ...T HGL with NAVIGATOR 2 0 control WI with NAVIGATOR 2 DIE ENERGIEFAMILIE TECHNICAL DOCUMENTATION INSTALLATION INSTRUCTIONS HEAT PUMPS FROM AUSTRIA www idm energie at 812579 Rev 8 1 Translation of origi...

Page 2: ...nnections outdoor unit AERO SLM 3 11 10 3 7 Dimensions outdoor unit AERO SLM 6 17 11 3 8 Connections outdoor unit AERO SLM 6 17 11 3 9 Technical data 12 3 10 Performance data AERO SLM 3 11 acc to EN 1...

Page 3: ...opening 35 6 5 Installation of refrigerant connection pipes 35 6 6 Important information about installation of refrigerant pipes 35 7 ELECTRICAL ASSEMBLY 36 7 1 Electrical power supply 36 7 2 Electro...

Page 4: ...o and secured against unintentional restart In addition all safety instructions in the relevant do cumentation stickers on the heat pump itself and all other applicable safety regulations must be obse...

Page 5: ...y the customer if required 1 9 Cleaning If necessary the indoor and the outdoor unit of the AERO SLM can be cleaned with a damp cloth The use of cleaning agents is not recommended 1 10 Ser vicing and...

Page 6: ...umans the legislation defines limit values that must not be exceeded Sound propagation outdoor With increasing distance from a point noise source the sound power is distributed on an increasing area d...

Page 7: ...incorporation 3 or 6 dB A Impulsiveness 0 3 or 6 dB A Daytimes with increased sensitivity 6 dB A The rating level Lr shall be obtained by summing the calculated immission level and the applied correc...

Page 8: ...of single and multiple dwellings with the heat source air In this case the building should be equipped with a low tem perature heating systems e g underfloor heating wall heating or low temperature r...

Page 9: ...LHZ 6LGH YLHZ OHIW RWWRP YLHZ 3 3 Dimensions indoor unit AERO SLM 3 11 and AERO SLM 6 17 1 HGL flow 2 Heatpump flow 3 Heat pump return 4 Cable inlet main current 5 Refrigerant pipes 6 LAN Connection 7...

Page 10: ...10 description Montage Heizungsseitig Front view Side view left Inlet side Outlet side 3 5 Dimensions outdoor unit AERO SLM 3 11 Refrigerant pipe connections 12 mm und 16 mm Condensation drain 1 Outle...

Page 11: ...scription Montage Heizungsseitig 3 7 Dimensions outdoor unit AERO SLM 6 17 3 8 Connections outdoor unit AERO SLM 6 17 Front view Side view left Inlet side Outlet side RQGHQVDWH UXQ RII VRFNHW 5HIULJHU...

Page 12: ...mption at A35 C W18 C kW 1 81 2 70 EER at A35 C W18 C 4 32 4 43 Sound emission acc to EN 121021 Sound power level nominal indoor unit dB A 45 45 Sound power level maximum indoor unit dB A 48 55 Sound...

Page 13: ...outdoor unit m 20 m max height di erence 10 m2 Electrical data Electrical power supply compressor V Hz 3 400 50 1 230 50 3 400 50 Electrical power supply heating unit V Hz 3 400 50 1 230 50 3 400 50...

Page 14: ...7 7 85 8 40 W k Power intake 1 56 1 56 1 60 1 61 1 64 1 63 1 60 1 60 1 59 1 55 W k COP Heizleistung 2 80 2 80 2 80 2 80 2 80 2 80 2 80 3 21 3 80 4 42 W k Power intake 2 24 1 93 1 56 1 39 1 08 0 76 0 6...

Page 15: ...4 2 2 6 2 0 8 2 4 0 3 8 3 3 W k 2 7 4 5 2 4 8 7 3 0 3 3 3 8 2 5 3 2 R E E Cooling capacity 3 9 6 5 5 6 7 1 6 8 7 5 0 4 5 2 0 5 W k Power intake 9 3 1 5 4 1 2 5 1 1 6 1 4 7 1 1 9 1 W k 0 0 5 3 5 4 6 0...

Page 16: ...sseitig Heat output AERO SLM 3 11 at flow temperature 35 C Heat output AERO SLM 3 11 at flow temperature 45 C 0 2 4 6 8 10 12 14 20 15 10 5 0 5 10 15 20 Heat output kW Air inlet temperature C MAX NOMI...

Page 17: ...g Heat output AERO SLM 3 11 at flow temperature 55 C Heat output AERO SLM 3 11 at nominal speed 0 2 4 6 8 10 12 14 20 15 10 5 0 5 10 15 20 Heat output kW Air inlet temperature C MAX NOMINAL MIN 2 3 4...

Page 18: ...AERO SLM 18 description Montage Heizungsseitig 3 12 Performance data AERO SLM 6 17 acc to EN 14511 heating t W t KW t W t KW t W t KW t W t KW t W t KW t W t KW t W t KW t W t KW t W t KW t W t KW t W...

Page 19: ...2 19 1 80 PPMJOH DBQBDJUZ kW 1PXFS JOUBLF kW EER 13 35 12 57 11 77 10 91 10 01 9 18 2 87 2 60 2 35 2 11 1 89 1 70 7 85 6 64 5 57 4 64 3 85 3 20 PPMJOH DBQBDJUZ kW 1PXFS JOUBLF kW EER 6 29 6 14 6 13 6...

Page 20: ...structions AERO SLM 20 description Montage Heizungsseitig Heat output AERO SLM 6 17 at flow temperature 35 C Heat output AERO SLM 6 17 at flow temperature 45 C HDW SRXWSXW kW LU LQOHW WHPSHUDWXUH C D...

Page 21: ...ructions AERO SLM 21 description Montage Heizungsseitig Heat output AERO SLM 6 17 at flow temperature 55 C Heat output AERO SLM 6 17 at nominal speed HDW RXWSXW kW LU LQOHW WHPSHUDWXUH C D EKD D E HDW...

Page 22: ...ant Up to a distance of 6 m between indoor and outdoor unit no additional refrigerant needs to be refilled For pipe length more than 6 m the following refrigerant quantities must be refilled 0 0 1 0 2...

Page 23: ...ng water quality see page 44 Heat pumps are by nature subjects to limits of use regarding of pressure and temperature see diagram It is not permissible to operate the AERO SLM 3 11 and AERO SLM 6 17 o...

Page 24: ...is the lowest temperature that the heat pump can produce depending on the heat source temperature and is then switched off at this value Due to the hydraulic spread across the heat pump the control re...

Page 25: ...uring the transport shall be present If the heat pump must be transported without the wooden pallet and the protective wooden crate it is important that there will be no damage on the housing Transpor...

Page 26: ...tructure borne sound transmissi ons the heat pump must be installed on a horizontal level and weight bearing surface concrete plate or similar In the case of floating screed the screed and the impact...

Page 27: ...anel will be released The front panel can be unhinged out by gently lift up After the front panel is removed the fixing screws of the side parts will be loosed The fixing screws are located on the fro...

Page 28: ...is recommended to put powder in to insulation Then the insulation can be pushed more easily over the connecting hoses Before connecting the hoses the supplied rubber grommets must be pushed over the...

Page 29: ...lected such that no noise interference can occur do not install close to bedrooms keep distance from neighbours hedges and bushes can absorb noise A frost proof connection of the condensation run o is...

Page 30: ...capacity of the wall bracket must be given Air heat pumps are producing condensation water during operation This could be 6 liters per defrost cycle within 2 minutes The condensate run o must be frost...

Page 31: ...the threaded bars After this the outdoor unit will be placed and brought into the correct position At the end the outdoor unit will be countered and secured with the washers and the hexagon nuts Moun...

Page 32: ...dapter The heating band 2 m will be placed in the drain hose The condensation bin and the run o have to be checked for soiling regularly Outdoor device Well Pipe 300mm Canalisation Condensate flow com...

Page 33: ...delivery They are available as an accessory and can be ordered by the iDM dealer 6 2 Connection of the outdoor unit on refri gerant side The refrigerant pipes are factory fitted with protective caps B...

Page 34: ...n of bending the refrigerant pipes on the backside of the heat pump in the appropriate direction depending on the desired routing of the refrigerant connection pipes see the red and green dashed lines...

Page 35: ...refrigerant itself may only be handled by trained experts autho rised by iDM Energiesysteme GmbH The refrigerant flow through the indoor unit can lead to flow noises The refrigerant pipes must be unco...

Page 36: ...conditions me chanical load current load potential drop environ mental temperature UV resistance electromagnetic compatibility Before commissioning the system check all terminals and tighten if neces...

Page 37: ...1x230V F B Z13A Indoor unit Refrigerant connection pipes Wall opening Outdoor unit Network cable Main current 3 400V 1 230V F C K13A C K16A C K25A Electrical heating element 3 400V 1 230V F B Z13A B...

Page 38: ...nnection cable between the control panel and the motherboard is disconnected The cover is fixed with two screws After removing the screws the cover can be pulled forward Now the cover can be lifted up...

Page 39: ...33 31 N 30 29 28 N 26 27 25 N 24 23 N N 22 N N 21 20 EEV1 X2 EEV2 X4 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52...

Page 40: ...re operating conditions etc to be exchanged and processed between the devices Add on module for Solar The NAVIGATOR 2 0 enables a temperature di eren tial controlled solar charging A layered solar inj...

Page 41: ...and the set shut o temperature changed if necessary If the heat pump is to be drained on the heating side the connection hose on the heat pump return must be disconnected At air source heat pumps a he...

Page 42: ...alve AERO SLM 3 11 HGL Hygienik Direct circuit for heating and cooling The heating system must be designed for cooling mode The cool demand of the building and the power output capacity of the distrib...

Page 43: ...HC A FS Refrigerant pipes Note This is only a tentative suggestion for installing an IDM heat pump in the heating system This suggestion replaces no professional planning of an executing companie On...

Page 44: ...he heat pump or high pressure faults For this reason open heating systems or steel pipe installations in combination with plastic pipe under floor heating which is not di usion tight should be avoided...

Page 45: ...FKQLFDO DWD RX FDQ ILQG RQ WKH QDPHSODWH FKDQJH WR WKH GHYLFH V QRW DXWKRUL HG E XV ZLOO UHQGHU WKLV GHFODUDWLRQ LQYDOLG 8 LUHFWLYHV RZ 9ROWDJH LUHFWLYH 8 0 LUHFWLYH 8 FRGHVLJQ LUHFWLYH 8 3UHVVXUH TXL...

Page 46: ...y efficiency s cold 150 120 average 176 135 warm 217 175 seasonal Coefficient of Performance SCOP kalt 3 82 3 07 mittel 4 47 3 44 warm 5 54 4 45 rated heat output Prated kW cold 10 9 average 9 8 warm...

Page 47: ...74 131 average 206 153 warm 252 195 seasonal Coefficient of Performance SCOP cold 4 41 3 35 average 5 22 3 83 warm 6 38 4 95 rated heat output Prated kW cold 15 12 average 14 11 warm 17 16 annual ener...

Page 48: ...d 1 95 2 02 2 36 indoor temperature 20 C indoor temperature 20 C T j Operation limit temperature TOL P dh 6 9 8 5 9 9 kW T j Operation limit temperature TOL COP d 1 82 2 02 2 36 Bivalenz temperature T...

Page 49: ...06 2 34 T j Operation limit temperature TOL P dh 8 9 10 9 15 9 kW T j Operation limit temperature TOL COP d 1 87 2 06 2 34 Bivalenz temperature Tbiv T biv 15 0 10 0 2 0 C Operation limit temperature...

Page 50: ...SITE SERVICE Our service technicians are happy to help on site Contact details for your regional customer service centre can be found on our website iDM Akademy PRACTICAL KNOWLEDGE FOR SALES AND TECH...

Reviews: