Operating Instructions

 

IDEM Safety Switches

 

UGB-NET-CS

 

 

102620 2210 UGB-NET-CS Operating Instructions 

 

12

 

9.

 

Technical 

Device Characteristics 

Actuator coding level 

Type 4 (RFID), High (acc. to ISO 14119) 

Assured sensing distance on (Sao) 

10 mm 

Assured sensing distance off (Sar) 

20 mm 

Assured locking distance 

5 mm 

Response time (E Stop) 

36 ms max. (E-stop -> transmission to field bus) 

Response time (Guard Interlock) 

36 ms max. (Guard/Lock -> transmission to field bus) 

Electrical Data 

Operating voltage  

24 V DC +10%/-15% (SELV/PELV)  

Power Supply UL Requirements 

Class 2 power supply must be used. 

Current consumption, max.  

600 mA (Lock solenoid enabled) 

Allowed through current (daisy-chain) 

5 A 

Mechanical Data 

Maximum holding force (F1) 

3000 N 

Rated holding force (Fzh) 

2307 N 

Body material 

Die cast Aluminium 

Head material 

Stainless steel 316 

Environmental Data 

Operating temperature 

-5 °C to 40 °C 

Enclosure Protection  

IP 65 

Maximum operating altitude  

2000 m 

Shock and Vibration  

Tested in accordance with: 
IEC 60068-2-6 and IEC 60068-2-27 

Pollution Degree (Storage and Operation) 

Degree 2 (EN 60664) 

Reliability / Safety Data (EN ISO 13849-1) 

Category 

Performance Level 

MTTFd 

High 

DC 

99% 

Reliability / Safety Data (EN 62061 / IEC 61508) 

Mission Time 

20 years 

SIL CL 

SIL 3 

PFHd (Guard Interlocking / Lock Monitoring) 

7.3E-10

 

PFHd (Emergency Stop Function) 

2.3E-9 

 

 

 

Summary of Contents for UGB-NET-CS

Page 1: ...nstructions To request this document in other languages please contact info idemsafety com IDEM Safety Switches UGB NET CS RFID Guard Interlock with Integrated EtherNet IP with CIP Safety Operating In...

Page 2: ...andle 3 UGB NET with Sliding Handle 3 5 Electrical Connection 4 6 Protocol Setup 5 Network Address Setup Initial Setting 6 Setting via DIP Switch 6 Setting via DHCP 6 Studio 5000 Ethernet IP Configura...

Page 3: ...es are not in a position to guarantee all of the characteristics of a given system or product not design by IDEM All relevant safety regulations and standards are to be observed The UGB NET CS complie...

Page 4: ...to IDEM immediately Replace a malfunctioning UGB NET immediately IMPORTANT Ensure that the static forces applied during normal operation do not exceed the holding force Fzh Ensure that dynamic forces...

Page 5: ...erating Instructions IDEM Safety Switches UGB NET CS 102620 2210 UGB NET CS Operating Instructions 3 UGB NET with Rotary Handle Guard Front Guard Rear UGB NET with Sliding Handle Guard Front Guard Rea...

Page 6: ...ments for UL a class 2 power supply must be used INFORMATION When multiple devices are used in a daisy chain arrangement the power bus may be forwarded via the UGB NET device Please see technical spec...

Page 7: ...e shall assume an ASYNC parameter value of 1 Configuring an originator with connection data and or target configuration data must be downloaded to the target so it can be tested and verified Only then...

Page 8: ...ccess to the DIP switches 2 Using a small tool push the required switches to the ON position to set the corresponding bit 3 Cycle power to the UGB NET or press and hold the reset button until the LEDs...

Page 9: ...ick OK 5 Open an internet browser and type in the IP address of the UGB NET 6 Navigate to Configuration under the NETWORK menu 7 Set DHCP to Disabled and click Save settings 8 Cycle power to the UGB N...

Page 10: ...onfiguration 1 Download the EDS file for the UGB NET and import to application control software 2 Open or create a project with the PLC CPU Partner and Ethernet IP modules added 3 Right click the Ethe...

Page 11: ...customisable UGB_NET_CIP used as example only and set the previously configured IP address 6 Change the Safety Network Number SNN to match that of the controller PLC 7 On the Safety tab uncheck the Co...

Page 12: ...assistance please contact technical idemsafety com Functional Tests Once the device has been installed and setup within the EtherNet IP CIP Safety application control software the following checks are...

Page 13: ...d open reset required Red Green alternate Reset in progress DS Green Device running Red Internal fault detected MS Green Connection to PLC Run state Green Flash Connection to PLC Idle state Red Major...

Page 14: ...must be used Current consumption max 600 mA Lock solenoid enabled Allowed through current daisy chain 5 A Mechanical Data Maximum holding force F1 3000 N Rated holding force Fzh 2307 N Body material D...

Page 15: ...Operating Instructions IDEM Safety Switches UGB NET CS 102620 2210 UGB NET CS Operating Instructions 13 NOTES...

Page 16: ...NET THE LISTED DEVICES CONFORM TO THE ESSENTIAL HEALTH AND SAFETY REQUIREMENTS OF THE FOLLOWING EUROPEAN DIRECTIVES AND STANDARDS DIRECTIVES Machinery Directive 2006 42 EC EMC Directive 2014 30 EU ST...

Reviews: