background image

IMP54 08

1

54 Series

Pressure Switches 

Types: 

Enclosed: J54, J54A, H54

Skeleton: J54S, J54AS, H54S

DUAL SEAL

CERTIFIED

Installation and Operation Instructions

Please read all instructional literature carefully and thoroughly before starting. 

Refer to the final page for the Warranty.

GENERAL

MISUSE OF THIS PRODUCT MAY CAUSE DAMAGE TO 

EQUIPMENT OR PERSONAL INJURY. THESE INSTRUCTIONS 

MUST BE THOROUGHLY READ AND UNDERSTOOD BEFORE 

DEVICE IS INSTALLED.

PRIOR TO INSTALLATION, CHECK THE WETTED PARTS 

MATERIAL FOR COMPATIBILITY TO THE PROCESS MEDIA. 

54 Series pressure switches are activated when a 

bellows, diaphragm or piston sensor responds to a 

pressure change. This response, at a predetermined 

set point, actuates one or two snap-acting switch(es), 

converting the pressure signal into an electrical 

signal. Control set point may be varied by turning the 

adjustment hex on “J” types or a reference adjustment 

dial on “H” types. (See Adjustment -PART II).

PROOF PRESSURE * LIMITS LISTED ON NAMEPLATE 

MUST NEVER BE EXCEEDED, EVEN BY SURGES IN THE 

SYSTEM. OCCASIONAL OPERATION OF UNIT UP TO PROOF 

PRESSURE IS ACCEPTABLE, E.G., START-UP AND TESTING. 

EXCESSIVE CYCLING AT MAXIMUM PRESSURE LIMIT COULD 

REDUCE SENSOR LIFE. CONTINUOUS OPERATION SHOULD 

NOT EXCEED THE DESIGNATED OVER RANGE **. 

* Proof Pressure - the maximum pressure to which a pressure 

sensor may be occasionally subjected, which causes no permanent 

damage (e.g., start-up, testing). The unit may require re-gapping 

(consult factory for re-gapping procedure).

** Over Range Pressure - the maximum pressure to which a pressure 

sensor may be continuously subjected without causing damage and 

maintaining set point repeatability.

THIS PRODUCT DOES NOT HAVE ANY FIELD REPLACEABLE 

PARTS. ANY SUBSTITUTION OF COMPONENTS SHALL 

INVALIDATE AGENCY CERTIFICATION(S).

DEVICE MUST NOT BE ALTERED OR MODIFIED AFTER 

SHIPMENT. CONSULT UE IF MODIFICATION IS NECESSARY. 

Please refer to product datasheet at www.ueonline.com 

for product specifi cations. 

Part I - Installation

Mounting

• 

Adjustable Wrench

• 

Screwdriver

INSTALL DEVICE WHERE SHOCK, VIBRATION AND 

TEMPERATURE FLUCTUATIONS ARE MINIMAL. DO NOT 

INSTALL DEVICE IN AMBIENT TEMPERATURES THAT EXCEED 

PUBLISHED LIMITS ON THE NAMEPLATE. 

DEVICE SHOULD BE MOUNTED TO PREVENT MOISTURE 

FROM ENTERING THE ENCLOSURE. VERTICAL MOUNTING IS 

RECOMMENDED.

CONSIDER THE USE OF A PRESSURE SNUBBER IF SEVERE 

PRESSURE SURGES ARE EXPECTED. 

FOR PRESSURE MODELS, MOUNT VIA PRESSURE CONNECTION. 

ALWAYS USE A WRENCH ON PRESSURE CONNECTION HEX (SEE 

FIGURE 1). DO NOT TIGHTEN BY TURNING THE ENCLOSURE AS 

THIS WILL DAMAGE THE SENSOR AND WEAKEN WELDED JOINTS. 

Pipe Mounting: 

Mount the switch directly to the line via 

the NPT pressure connection.

Vertical Surface Mount: 

Two holes for #10 screws are 

provided in the bracket plate (see Figure 1 for J54, J54AS 

& H54S. See Dimensions page for J54, J54A & H54).

Wiring

DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING DEVICE. 

WIRE DEVICE IN ACCORDANCE WITH LOCAL AND NATIONAL  

ELECTRICAL CODES. MAXIMUM RECOMMENDED WIRE SIZE 

IS 14 AWG AND RECOMMENDED TIGHTENING TORQUE FOR 

FIELD WIRING TERMINALS IS 7 TO 17 IN-LBS. 

DO NOT EXCEED ELECTRICAL RATINGS LISTED ON 

NAMEPLATE. OVERLOAD ON A SWITCH CAN CAUSE 

FAILURE EVEN ON THE FIRST CYCLE.

Reviews: