Protocol Setup
IMPORTANT
•
The minimum time between the change of a single safe digital input and the
transmission to the CIP Safety is 32ms for the Interlock/Lock and Estop. In the case
of an input level change at both safe inputs at the same time the maximum safe
application reaction time is 42ms for Interlock/Lock and Estop.
•
Clear any pre-existing configuration from any safety device before installing it onto a
safety network.
•
Commission all safety devices with IP address prior to installing it onto a safety
network.
•
When a SIL3 device is configured directly from a workstation, the user should
compare the transferred SCID and configuration data with the SCID and
configuration data originally viewed in the workstation.
•
The configuration software shall assume an ASYNC parameter value of 1.
•
Configuring an originator with connection data and/or target configuration data
must be downloaded to the target so it can be tested and verified. Only then can
SCIDs from the target be confirmed.
•
Status-Bits reported by the device via CIP Safety messages shall not be used to
trigger the safety function of a device or system.
•
The safety-related parts of the EDS (Electronic Data Sheet) of the UGB-NET-CIP
device shall not be altered.
•
Each safety device shall have a single physical address that is unique on the devices
segment.
•
The maximum operation time (proof-test interval) of the UGB-NET shall not exceed
20 years. When reaching the proof test interval, the UGB-NET shall be replaced and
put permanently out of order.
•
After the detection of a safety critical error, the UGB-NET shall not be kept in fail-
safe state for more than 1 hour.
INFORMATION
•
The device EDS file can be found via the UGB-NET product page of the IDEM
website www.idemsafety.com/products or alternatively please contact