Technical data
303
IDEC SmartRelay Manual
Short–circuit current limitation
Derating
none; across the en-
tire temperature
range
none; across the en-
tire temperature
range
Short circuit–proof cos 1
Power protection
B16,
600A
Power protection
B16,
600A
Short–circuit proof cos 0.5 to
0.7
Power protection
B16,
900A
Power protection
B16,
900A
Parallel output circuits
for power increase
Not permitted
Not permitted
Protection of output relay
(if desired)
max. 16 A,
characteristic B16
max. 16 A,
characteristic B16
Minimum Switching Load
10 mA, 12 V DC
10 mA, 12 V DC
Initial Contact Resistance
100 m
Ω
maximum
(at 1A, 24V DC)
100 m
Ω
maximum
(at 1A, 24V DC)
Mechanical Life
10,000,000
operations minimum
(no load, 10 Hz)
10,000,000
operations minimum
(no load, 10 Hz)
Electrical Life
100,000 operations
minimum (rated re-
sistive load, 1800 op-
erations / hour)
100,000 operations
minimum (rated re-
sistive load, 1800 op-
erations / hour)
Switching rate
Mechanical
10 Hz
10 Hz
Electrical
Ohmic load/lamp load
2 Hz
2 Hz
Inductive load
0.5 Hz
0.5 Hz
FL1D-H12RCA
FL1D-B12RCA
FL1B-M08D2R2
Note: When connecting a fluorescent lamp to the output, take the inrush current into
consideration. When the inrush current exceeds the rated value, connect an ap-
propirate relay between the output and the fluorescent lamp.