Technical data
IDEC SmartRelay Manual
300
Derating
none; across the en-
tire temperature
range
none; across the en-
tire temperature
range
Short circuit–proof cos 1
Short–circuit proof cos 0.5 to
0.7
Parallel output circuit for power
increase
Not permitted
Not permitted
Protection of output relay
(if desired)
Switching rate
(5)
Mechanical
Electrical
10 Hz
10 Hz
Ohmic load/lamp load
10 Hz
10 Hz
Inductive load
0.5 Hz
0.5 Hz
(1): 8 V DC (Version 1 to 4 specifications)
(2): 1.0 mA (Version 1 to 4 specifications)
(3): 1.5 mA (Version 1 to 4 specifications)
For identifying the version, see page 4.
(4): When FL1D-H12SND or FL1B-M08B1S2 are switched on, signal 1 is sent to the
digital outputs for about 50 microseconds. Take this into account, especially
when using devices that react to short pulses.
(5): The maximum switching rate of the FL1D-H12SND is only dependent on the
switching program’s cycle time.
FL1D-H12SND
FL1B-M08B1S2
Note: When connecting a fluorescent lamp to the output, take the inrush current into
consideration. When the inrush current exceeds the rated value, connect an ap-
propirate relay between the output and the fluorescent lamp.
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com