IDEC SmartRelay FL1D Series User Manual Download Page 241

Configuring IDEC SmartRelay

231

IDEC SmartRelay Manual

 

Description of the four menu items of the parameter assignment 

menu

• Stop

You select this command to stop your circuit program and 

thus change to the main menu of programming mode. To do 

so:

1. To move the ‘>’ cursor to ‘

Stop

’:

Press 

 or 

2. To confirm ‘Stop’:

Press 

OK

3. To move the ‘>’ cursor to ‘

Yes

’:

Press 

 or 

4. To confirm ‘Yes’:

Press 

OK

IDEC SmartRelay shows the main menu of the programming 

mode:

>Program..
 Card..
 Setup..
 Start

Set Param

For information on the various parameters, refer to the 

Chapters 5.1.1 to 5.1.3.

• Set..

For information on the various settings, refer to Chapter 5.2.

Prg Name

This menu command only allows you to 

read

 the name of 

your circuit program. It is not possible to modify this name in 

parameter assignment mode. (see Chapter 3.6.4.)

 Stop Prg
>No
 Yes

Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com

Summary of Contents for SmartRelay FL1D Series

Page 1: ...Courtesy of Steven Engineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www stevenengineering com...

Page 2: ...C SmartRelay s place in information technology The wiring information in your IDEC SmartRelay manual is also found in the IDEC SmartRelay Product Info included with all devices For further information...

Page 3: ...log output values for RUN STOP transition may be selected Analog inputs and analog outputs have been added to the RUN mode display New features of the current devices FL1D The Analog Ramp Control spec...

Page 4: ...d systems in accordance with safety regula tions and standards Danger Warns that death serious harm to health or damage to assets will result if the respective precautionary measures are not taken War...

Page 5: ...be ruled out Any liability and warranty for the accuracy of this information is excluded The data in this manual are reviewed at regular intervals Any corrections required are included in the subseque...

Page 6: ...cting the AS interface bus 44 2 4 Putting into operation 46 2 4 1 Switching on the IDEC SmartRelay Power On 46 2 4 2 Operating states 50 3 Programming IDEC SmartRelay 52 3 1 Connectors 54 3 2 Blocks a...

Page 7: ...2 AND with Edge Detection 115 4 2 3 NAND not AND 116 4 2 4 NAND with Edge Detection 117 4 2 5 OR 118 4 2 6 NOR not OR 119 4 2 7 XOR exclusive OR 120 4 2 8 NOT Negation Inverter 120 4 3 Basics on spec...

Page 8: ...3 Message texts 199 4 4 24 Softkey 206 4 4 25 Shift register 210 4 4 26 Analog multiplexer 213 4 4 27 Analog Ramp Control 217 4 4 28 PI controller 222 5 Configuring IDEC SmartRelay 229 5 1 Selecting p...

Page 9: ...ol system with IDEC SmartRelay 264 8 2 4 Special features and expansion options 267 8 2 5 Extended solution with FL1D H12RCC 267 8 3 Air conditioning system 270 8 3 1 Requirements for an air condition...

Page 10: ...08C2R2 295 A 3 Technical data FL1D H12SND and FL1B M08B1S2 298 A 4 Technical data FL1D H12RCA FL1D B12RCA and FL1B M08D2R2 301 A 5 Technical data FL1D H12RCE FL1D B12RCE and FL1B M08B2R2 304 A 6 Switc...

Page 11: ...nd apparatus engineer ing e g for gate control systems air conditioning systems or rainwater pumps etc IDEC SmartRelay can also be implemented for special con trol systems in conservatories or greenho...

Page 12: ...DC and are equipped with two analog inputs or two analog outputs The digital analog modules are integrated in two subunits Each one is equipped with two expansion interfaces for con necting additional...

Page 13: ...he housing prevent you from connecting devices of a different voltage class Exception The left hand interface of an analog module or commu nication module is galvanically isolated This type of expansi...

Page 14: ...Module slot with cap 8 Expansion interface 12 Version number example represents Version 1 1 2 3 I7 I8 Q1 Q2 Q3 Q4 4 35 72 L1 N 4 90 55 I5 I6 I2 I3 I4 I1 Q4 Q1 Q2 35 L1 N I2 I3 I4 I1 36 RUN STOP 90 53...

Page 15: ...expansion module e g FL1B M08B2R2 Getting started with IDEC SmartRelay 5 IDEC SmartRelay Manual 1 Power supply 5 Control panel not with FL1D B12 9 Mechanical coding pins 2 Inputs 6 LCD not with FL1D B...

Page 16: ...TOP indicator 11 Slide 13 Version number 8 Expansion interface 1 Power supply 9 Mechanical coding pins 12 PE terminal for con necting earth 2 Outputs 10 Mechanical coding sockets 7 RUN STOP indicator...

Page 17: ...of Inputs and Outputs d B1 24V DC B2 12 24V DC C2 100 240V AC DC D2 24V AC DC e S Tr source output R Relay output f Terminal type 2 non removable terminal Analog input module FL1B Jcde c Number of In...

Page 18: ...ith 8 inputs and 4 outputs The digital module is equipped with 4 digital inputs and 4 digital outputs The analog module is equipped with 2 analog inputs or two analog outputs The communications module...

Page 19: ...L1D B12RCA 2 24 V AC 24 V DC 8 digital 4 relays 10A no display unit no keyboard FL1D B12RCC 3 100 240V AC DC 8 digital 4 relays 10A no display unit no keyboard Symbol Description Supply Voltage Inputs...

Page 20: ...digital 4 relays 5A FL1B M08C2R2 100 240 V AC DC 4 digital 2 4 relays 5A FL1B J2B2 12 24 V DC 2 analog 0 10 V or 0 20 mA 3 none FL1D K2B2 24 V DC none 2 analog 0 10 V DC Symbol Description Supply Volt...

Page 21: ...dous Location CSA 213 Hazardous Location APPROVED for use in Class I Division 2 Group A B C D Tx Class I Zone 2 Group IIC Tx FM Approval Factory Mutual Research FM to Approval Standard Class Number 36...

Page 22: ...their low pollutant equipment Contact a certified electronic waste disposal center for environmentally acceptable recycling and disposal of your old devices Warning Risk of personal injury and materia...

Page 23: ...e the IDEC SmartRelay with cable conductor cross sections from 1 5 mm2 to 2 5 mm2 see Chapter 2 3 Do not exceed the screw torque of the terminals The maximum torque is 0 5Nm see Chapter 2 3 Keep the c...

Page 24: ...is designed for fixed and enclosed instal lation in the housing or the control cabinet Safety of electronic control equipment Introduction The notes below apply regardless of the type or manufactur e...

Page 25: ...ambient tempera ture over a period of several days Careful computer controlled final testing Statistical evaluation of all returned systems and compo nents to enable the immediate initiation of suita...

Page 26: ...ctronic control equipment with a safety function the measures that have to be taken to prevent or rectify faults are based on the risks involved in the installation As of a cer tain degree of hazard t...

Page 27: ...digital inputs I7 I8 Maximum setup of a IDEC SmartRelay without analog inputs FL1D H12RCA FL1D B12RCA and FL1D H12RCC FL1D B12RCC IDEC SmartRelay Base 4 digital modules and 4 analog modules example I1...

Page 28: ...lasses When setting up expansion modules of different power volt ages take the following restrictions into consideration Note To power the CPU module and expansion I O modules use one power supply to...

Page 29: ...cor responds with 4 subunits IDEC SmartRelay expansion modules have a width of 36 mm which corresponds with 2 subunits Note The figure below shows you an example of the installation and removal of a F...

Page 30: ...p it on The mount ing interlock at the rear must engage IDEC SmartRelay digital module 3 On the right side of the IDEC SmartRelay Base IDEC SmartRelay expansion module remove the connector cap 4 Place...

Page 31: ...eft In its end position the slide interlock engages in the IDEC SmartRelay Base Repeat steps 3 through 6 to mount further expansion mod ules Note The expansion interface on the last expansion module m...

Page 32: ...nstalled only one IDEC SmartRelay Base Part A 1 Insert a screwdriver into the eyelet at the bottom of the slide interlock and move the latch downward 2 Swing the IDEC SmartRelay Base off the DIN rail...

Page 33: ...let at the bottom of the slide interlock and lever it downward 4 Swing the expansion module off the profile rail Repeat steps 1 to 4 for all other expansion modules Note If you have connected more tha...

Page 34: ...e the mounting slides on the rear side of the devices towards the outside You can now wall mount the IDEC SmartRelay by means of two mounting slides and two M4 screws tightening torque 0 8 to 1 2Nm Mo...

Page 35: ...Relay you need to drill holes using the template shown below 53 5 0 2 35 5 0 2 n x 35 5 0 2 98 0 3 1 2 2 2 All dimensions in mm Bore hole for M4 screw Tightening torque 0 8 to 1 2 Nm 1 IDEC SmartRelay...

Page 36: ...adequately from impermissible contact to live parts local standards must be complied with Cross section mm2 AWG Phoenix Contact Ferrule type No NIC HIFU Blade Terminals type No NIC HIFU Insulated Pin...

Page 37: ...artRelays FL1D 12RCE FL1B M08B2R2 are suitable for a supply voltage of 12 V AC DC or 24 V AC DC Note the information on connection in the product informa tion document shipped with your device and the...

Page 38: ...least 20 above the rated voltage IDEC SmartRelay with DC power supply IDEC SmartRelay with AC power supply Note IDEC SmartRelay is a double insulated switchgear You do not need to connect an equipment...

Page 39: ...1 to 4 specifications For identifying the version see page 4 I1 I6 I7 I8 I1 I6 I7 I8 Signal status 0 5 VDC 5 VDC 5 VDC 5 VDC Input current 0 85 mA 1 0 05 mA 0 85 mA 3 0 05 mA Signal status 1 8 5 V DC...

Page 40: ...ou connect a switch with a glow lamp to IDEC SmartRelay The current that flows through the glow lamp allows IDEC SmartRelay to detect a 1 signal even though the switch contact is not closed If however...

Page 41: ...disconnects You must choose the voltage level for which the capacitor is rated such that it is not destroyed in the case of overvoltage At 230 V AC the voltage between N and an input I n must not be g...

Page 42: ...not apply to these high speed in puts Note The high speed inputs I5 and I6 are the same as in the previous versions FL1A to FL1C i e a circuit program that is written in these versions can be transfe...

Page 43: ...potentiometer and 10 V input voltage as the maximum value you must ensure that with a connected in put voltage of 24 V 14 V must release via the series resistor so that a maximum of 10 V are supplied...

Page 44: ...digital module L M M L I1 I2 I3 I4 I5 I8 The inputs of these devices are not isolated and therefore require a common reference potential chassis ground With FL1D H12RCE FL1D B12RCE and FL1D H12SND mo...

Page 45: ...20 mA cur rent measurement of the FL1B J2B2 module 2 Connect the plus connector on the sensor to the 24 V supply voltage L Connect the ground connection on the sensor to the corre sponding M input M1...

Page 46: ...FL1D H12RCC FL1D B12RCC FL1B M08C2R2 I1 I8 N 100nF 390k 390k 62k AC 2 wire Sensor I1 to I8 R4 100 to 240 V AC N L1 Internal Circuit Digital AC DC Input When using the AC two wire sensor ngineering In...

Page 47: ...D B12RCA FL1B M08D2R2 I1 I8 4 3k 5V 510 100nF P2 AC 2 wire Sensor I1 to I8 R3 240 V AC P1 P2 Internal Circuit Internal Circuit Digital AC DC Input When using the AC two wire sensor ngineering Inc 230...

Page 48: ...FL1D B12RCE FL1D H12SND FL1B J2B2 FL1B J2B2 I1 I8 3 6k 2 2k 100nF M Internal Circuit Digital DC Input I7 I8 U1 U2 M M1 M2 39k 5V 39k 10nF Internal Circuit Analog Input 0 10V Max 125 125 10nF I1 I2 M1...

Page 49: ...ctuating analog values when using these expansion modules proceed as follows Use only shielded encoder wires Shorten the encoder wire as much as possible The encoder wire must not be more than 10 mete...

Page 50: ...tputs You can connect various loads to the outputs e g lamps flu orescent lamps motors contactor relays etc For informa tion on the properties required for the loads connected to the these units refer...

Page 51: ...iary load voltage supply is not necessary because IDEC SmartRelay supplies the load voltage Requirements for transistor outputs The load connected to IDEC SmartRelay must have the fol lowing character...

Page 52: ...artRelay Manual 42 FL1D K2B2 V1 V2 RUN STOP M2 M1 L M L M L M OUTPUT 2x 0 10V PE 0 10V 0 10V 2 1 R R 1 Earth 2 DIN rail V1 V2 0 10 V DC R min 5 k ngineering Inc 230 Ryan Way South San Francisco CA 940...

Page 53: ...FL1B M08D2R2 Relay Output FL1D H12SND FL1B M08B1S2 Transister Output Source FL1D K2B2 Analog Output 0 10V 27k 47k 24V 2 1 Q1 Q4 Internal Circuit Internal Circuit 24V 10k 10nF 10nF M Q1 Q4 Internal Ci...

Page 54: ...ected beforehand This is necessary for safety reasons ADDR RUN STOP AS I AS I Networking on the AS interface bus To make the connection to the AS interface bus you need a communications capable IDEC S...

Page 55: ...ess space If you are al ready using more than 12 physical outputs or more than 20 physical inputs it is no longer possible to operate the FL1B CAS2 Warning The AS Interface and IDEC SmartRelay systems...

Page 56: ...erly Is the power supply connected to the expansion module In addition always ensure that you switch on the power supply to the expansion module first before activating the power supply to the IDEC Sm...

Page 57: ...ion 1 to 3 FL1B J2B2 Version 1 to 4 FL1D K2B2 Version 1 For identifying the version see page 4 10sec Power Input signals at base and expansion I O modules Base module input and output signals Run Expa...

Page 58: ...After power on No program in memory or empty with program IDEC SmartRelay in RUN mode or empty with program or empty with program Program in memory With stored program from IDEC SmartRelay IDEC Smart...

Page 59: ...ard IDEC SmartRelay adopts the operational state it had prior to POWER OFF Versions without display unit FL1D B12 automatically change from STOP to RUN LED changes from red to green 4 If you have enab...

Page 60: ...de not FL1D B12 LED is red only FL1D B12 Display Screen mask for monitoring I Os and messag es after START in the main menu not FL1D B12 Switching IDEC SmartRelay to parameter assignment mode not FL1D...

Page 61: ...n modules which are arranged to the right of the FL1B CAS2 expansion module is interrupted Recommendation Position FL1B CAS2 on the far right hand side If communication is interrupted the switching ou...

Page 62: ...n this manual relate only to the creation of circuit programs on the actual IDEC SmartRelay because the programming software WindLGC already con tains an extensive Online Help See also Chapter 7 Note...

Page 63: ...next step we shall create a circuit program based on a simple conventional circuit which you can enter directly in IDEC SmartRelay in the third step It will take you only a few pages of this manual st...

Page 64: ...s FL1B J2B2 has the inputs at the bottom Each output is identified by the letter Q plus a number FL1D K2B2 AQ plus number In the figure you can see the output terminals at the bottom L M I13I14I15I16...

Page 65: ...nal is digital signals at AI1 or AI2 are analog IDEC SmartRelay s connectors The term connector refers to all connections and states in IDEC SmartRelay The digital I O status can be 0 or 1 Status 0 me...

Page 66: ...ts FL1D H12RCC FL1D B12RCC FL1D H12RCA FL1D B12RCA Two groups I1 I4 and I5 I8 I9 I24 AI1 AI8 none FL1D H12RCE FL1D B12RCE FL1D H12SND I1 I6 I7 I8 AI1 AI2 I9 I24 AI3 AI8 Outputs Q1 Q4 Q5 Q16 none AQ1 A...

Page 67: ...al box When you create the circuit program you interconnect the blocks To do so simply select the connection you require from the Co menu The menu name Co is an abbreviation of the term Connector Logi...

Page 68: ...ut This connector is not required Block Output Block number as signed by IDEC SmartRelay Assigning a block number IDEC SmartRelay assigns each new block a circuit program a block number IDEC SmartRela...

Page 69: ...circuit layout To do so however you need to know how IDEC SmartRelay has named the blocks Note We advise you to create an organizational program chart You will find this a valuable aid when you creat...

Page 70: ...on and off by means of the switches S1 OR S2 AND S3 Relay K1 picks up when the condition S1 OR S2 AND S3 is met K1 S1 K1 S2 E1 S3 Creating this circuit with IDEC SmartRelay In IDEC SmartRelay you cre...

Page 71: ...pen contact S3 is interconnected in series to output Q1 and to a further circuit element A series connection corresponds with the AND block I3 x Q1 Step 2 S1 and S2 are connected in parallel A paralle...

Page 72: ...elay S3 to connector I3 of IDEC SmartRelay The output of the AND block controls the relay at output Q1 The load E1 is connected to output Q1 Wiring example The following figure shows you the wiring ba...

Page 73: ...art command on the main menu to set RUN mode When the system is in RUN you can return to parameter assignment mode by pressing the ESC key When parameter assignment mode is open and you want to return...

Page 74: ...exit programming mode You select a connector block when the cursor appears as solid square Press or to select a connector or a block Confirm with OK Press ESC to return to the previous step Rule 4 Pl...

Page 75: ...se menus refer to Appendix D Program Card Setup Start Edit Clear Prg Password Card Card CopyProtect IDEC SmartRelay Clock Contrast OK OK OK ESC ESC ESC Main menu Programming menu Transfer menu Setup m...

Page 76: ...nd switched it on The display now shows you the message Switch IDEC SmartRelay to programming mode by pressing ESC This will take you to the main menu of IDEC SmartRelay IDEC SmartRelay s main menu Th...

Page 77: ...You are now in programming mode Press and to select the other outputs Now start to edit your circuit program Note Because we have not yet saved a password for the circuit program in IDEC SmartRelay y...

Page 78: ...ay interprets this parallel circuit as an OR logic because S1 OR S2 switches on the output Translated into a IDEC SmartRelay circuit program this means Relay K1 is at output Q1 is controlled by means...

Page 79: ...witches input I1 while S2 switches input I2 The load is connected to the relay Q1 3 6 3 Circuit program input Let us now write the circuit program starting at the output and working towards the input...

Page 80: ...ting mode Q1 Co The cursor is displayed as a solid square You can now select a con nector or a block The cursor no longer appears in the form of an underscore but instead as a flashing solid square ID...

Page 81: ...display now shows Block number Your complete circuit program layout You have now entered the first block Each new block is au tomatically assigned a block number The only thing left to do is intercon...

Page 82: ...jumps to the next input of the OR block 1 B1 Q1 1 Q1 I1 I1 B1 Your complete circuit program in IDEC SmartRelay up to now The display now shows Now you connect input I2 to the input of the OR block Yo...

Page 83: ...of the OR block for this circuit program You can mark the unused inputs with an x Enter the x character twice 1 Switch to editing mode Press OK 2 To select the Co list Press or 3 To accept the Co lis...

Page 84: ...r to the relevant position e g Confirm with OK Now press or to invert this input Next press ESC You can review your first circuit program by pressing or to move the cursor through the circuit program...

Page 85: ...of up to 16 uppercase lowercase letters numbers and special characters In the programming menu 1 To move the cursor to Edit Press or 2 To accept Edit Press OK 3 Move the cursor to Edit Name Press or 4...

Page 86: ...assignment mode 3 6 5 Password You can protect a circuit program from unauthorized access by assigning it a password To assign a password A password may have a maximum length of 10 characters and con...

Page 87: ...same as for entering the name of the circuit program Select New and enter 3 Select A Press 4 To move to the next letter Press 5 Select A Press The display now shows Old No Password New AA 6 To confirm...

Page 88: ...ted memory cartridge card you first need to assign a password to this new program see Chapter 6 1 Changing the Password You need to know the current password in order to change it In the programming m...

Page 89: ...You must know your current password in our example ZZ same as if you were chang ing it In the programming menu 1 Move the cursor to Password Press or 2 To confirm the Password Press OK Select Old and...

Page 90: ...to accelerate progress in our further exercises and examples Password Wrong Password When the user inputs the wrong password and confirms the input with OK IDEC SmartRelay does not open editing mode b...

Page 91: ...6789 1 0123456789 2 01234 Q 0 123456789 1 0123456 AI 1 00000 2 01000 3 00253 AI 4 00010 5 00000 6 00005 Display field of the IDEC SmartRelay in RUN mode Start screen Date and current time of day only...

Page 92: ...AQ 1 00000 2 01000 Analog inputs AI7 to AI8 Markers M1 to M9 Markers M10 to M19 Markers M20 to M24 4 cursor keys for manual intervention in the circuit program ESC key Press Press Press Analog output...

Page 93: ...2 01234 Input output status is 1 inverted Input output status is 0 not inverted In this example only the inputs I1 I15 Q8 and Q12 are set high Status indication on the display I 0 123456789 1 01234567...

Page 94: ...the first circuit program as a basis for the sec ond with some slight modifications First of all take a look at the circuit diagram for the second circuit program L1 N S1 S2 K1 K1 E1 You already know...

Page 95: ...n menu select Program 3 On the Programming menu select Edit confirm with OK Next select Edit Prg and confirm with OK If required enter your password at the prompt and con firm with OK You can now modi...

Page 96: ...ock is assigned the block number B2 The cursor is positioned at the top input of the added block The B1 block previously connected to Q1 is automatically connected to the uppermost input of the new bl...

Page 97: ...itch to editing mode Press OK IDEC SmartRelay shows the parameters in the parameter assignment window B2 R T 00 00s T The block pa rameter B2 is a time function means The parameter is shown and can be...

Page 98: ...er assignment mode 1 Move the cursor to the protection mode Press or 2 Select the protection mode Press or The display should now show T 12 00m B2 R T 12 00m B2 R or Protection mode The value of the t...

Page 99: ...in programming mode i e this is not possible in parameter assign ment mode In this manual the protection mode or and retentivity R or settings are only shown in the displays where these can ac tually...

Page 100: ...s a reminder 1 To return to the programming menu Press ESC 2 To return to the main menu Press ESC 3 To move the cursor to Start Press or 4 To confirm Start Press OK IDEC SmartRelay is back in RUN mode...

Page 101: ...ired enter your password and confirm with OK 4 Select Edit Prg Press or 5 Confirm Edit Prg Press OK 6 To move the cursor to the input of Q1 i e to B2 press 7 Confirm with OK 8 Now replace block B2 wit...

Page 102: ...ess OK if required enter your password and confirm with OK 4 To select Edit Prg Press or 5 To confirm Edit Prg Press OK 6 To move the cursor to the input of Q1 i e to B2 press 7 Confirm with OK 8 Now...

Page 103: ...output values for RUN STOP transition You can select the analog values that are output at the two analog outputs when IDEC SmartRelay changes from RUN mode to STOP mode In the programming menu 1 Move...

Page 104: ...ng a specific analog output value You want to output a specific analog value at the two analog outputs 1 Move the cursor to Defined Press or 2 Confirm Defined Press OK The display shows AQ1 00 00 AQ2...

Page 105: ...Program Press OK 3 Move the cursor to Clear Prg Press or 4 Confirm Clear Prg Press OK To cancel deletion of the circuit program leave the cursor at No and press OK Program Card Setup Start IDEC Smart...

Page 106: ...assignment mode by calling the Set menu command in programming mode by calling the Setup menu com mand To enable disable automatic S W Time conversion in program ming mode 1 Switch IDEC SmartRelay to...

Page 107: ...Set then menus Clock and S W Time You can now enable disable automatic S W Time conversion Enabling summertime wintertime conversion You now want to enable this conversion and define or set its parame...

Page 108: ...2 00 01 00 60 Min AUS Last Sunday in October 02 00 03 00 Last Sunday in March 03 00 02 00 60 Min AUS TAS First Sunday in October 02 00 03 00 Last Sunday in March 03 00 02 00 60 Min NZ First Sunday in...

Page 109: ...3 Confirm the menu item PressOK The display shows MM DD 01 01 01 01 000min 0 Cursor solid square Month MM and Day DD Start of summertime End of summertime The desired time zone difference in min Let...

Page 110: ...SmartRelay indicates that summertime wintertime conversion is enabled and that user defined parameters have been set Note To disable summertime wintertime conversion in this menu you merely confirm Of...

Page 111: ...g of the automatic synchronization function is displayed in the bottom row The default setting is Off disabled Enabling synchronization You want to enable synchronization 1 Move the cursor to On Press...

Page 112: ...is based on the maximum number of bytes a circuit program may contain The total number of bytes used can be determined by adding up the num ber of bytes used for the relevant function blocks Retentiv...

Page 113: ...and on the timer current value of the On delay FB is sometimes reset as shown in Fig 2 Other FBs are shown below Function blocks whose timer current value is sometimes reset Off delay On delay On Off...

Page 114: ...Blocks REM 2000 130 60 Function Program memory Rem memory 1 Basic functions AND 12 AND with Edge Detection 12 NAND not AND 12 NAND with Edge Detection 12 OR 12 NOR not OR 12 XOR exclusive OR 8 NOT Ne...

Page 115: ...ry space is fully occupied optimize your circuit pro gram or install a second IDEC SmartRelay Counter Up down counter 24 5 Operating hours counter 24 9 Frequency trigger 16 Analog Analog trigger 16 An...

Page 116: ...Function Memory area Bytes Blocks REM B1 OR 12 1 B2 AND 12 1 B3 Seven day time switch 20 1 B4 On delay 1 1 Configured with retentivity 8 1 3 B5 Stairwell Light Switch 12 1 0 B6 AND 12 1 Resources used...

Page 117: ...ceed as follows 1 Switch the IDEC SmartRelay to programming mode as a reminder refer to page 63 2 Select Edit Press or 3 Accept Edit Press OK 4 Select Memory Press or 5 Accept Memory Press OK The disp...

Page 118: ...s show the elements available in IDEC SmartRelay Usually this includes all connectors basic functions and special functions the IDEC SmartRelay knows This includes all the blocks you have created in I...

Page 119: ...ND FL1D H12RCE and FL1D B12RCE are equipped with the inputs I7 and I8 which can also be programmed for use as AI1 and AI2 inputs Signals at the I7 and I8 inputs are interpreted as digital values and t...

Page 120: ...icance to a circuit program 2 Analog outputs Analog outputs are identified by the letters AQ Two analog outputs are available namely AQ1 and AQ2 An analog out put can only be connected with the analog...

Page 121: ...circuit pro gram The content of shift register bits can only be modified by means of the Shift register special function see Chapter 4 4 25 Cursor keys Up to four cursor keys are available to you nam...

Page 122: ...example is found in Chapter 3 6 3 The GF list contains the basic function blocks you can use for your circuit program The following basic functions are available View in the circuit diagram View in I...

Page 123: ...lly closed con tact NOR not OR see page 119 Double changeover contact XOR exclusive OR see page 120 Normally closed contact NOT negation inverter see page 120 View in the circuit diagram View in IDEC...

Page 124: ...is only 1 if all inputs are 1 i e all con tacts are closed At an unused block input x x 1 Table of the AND logic 1 2 3 4 Q 0 0 0 0 0 0 0 0 1 0 0 0 1 0 0 0 0 1 1 0 0 1 0 0 0 0 1 0 1 0 0 1 1 0 0 0 1 1 1...

Page 125: ...an edge triggered AND is only 1 if all inputs are 1 and if at least one input was low in the previous cycle At an unused block input x x 1 Timing diagram for the AND with Edge Detection 1 3 Q 2 1 2 3...

Page 126: ...D is only 0 if the status at all inputs is 1 i e the contacts are closed At an unused block input x x 1 Table of the NAND logic 1 2 3 4 Q 0 0 0 0 1 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 1 0 1 0 1 1 0...

Page 127: ...the NAND with Edge Detection is only 1 if at least one input is 0 and if all inputs were 1 in the previ ous cycle At an unused block input x x 1 Timing diagram for the NAND with Edge Detection 1 3 Q 2...

Page 128: ...only 1 if at least one input is 1 i e at least one of the contacts is closed At an unused block input x x 0 Table of the OR logic 1 2 3 4 Q 0 0 0 0 0 0 0 0 1 1 0 0 1 0 1 0 0 1 1 1 0 1 0 0 1 0 1 0 1 1...

Page 129: ...i e if switched off The NOR output is set to 0 when one of the inputs is switched on logical 1 status At an unused block input x x 0 Table of the NOR logic 1 2 3 4 Q 0 0 0 0 1 0 0 0 1 0 0 0 1 0 0 0 0...

Page 130: ...er Symbol in IDEC SmartRelay A normally closed contact in the circuit diagram The output status is 1 if the input is 0 The NOT block inverts the input status Advantage of the NOT block for example The...

Page 131: ...ntain timer functions retentive functions and various parameter assignment op tions which allow you to adapt the circuit program to suit your own requirements This section provides you with a brief ov...

Page 132: ...s input enables a block function When this input is 0 other signal to the block will be ignored Inv Invert A signal at this input inverts the output signal of the block Ral Reset all All internal valu...

Page 133: ...tRelay has a maximum tolerance of 0 02 When 0 02 of the time T is smaller than 0 02 seconds the maximum deviation is 0 02 seconds Example The maximum tolerance per hour 3600 seconds is 0 02 which is p...

Page 134: ...ent data are retained after a power failure and that the block resumes operation at the break point The timer is not reset but resumes operation until the time to go has expired for example To enable...

Page 135: ...nto range of values from 0 to 1000 An input voltage exceeding 10V is shown as internal value 1000 Because you can not always process the range of values from 0 to 1000 as predetermined by IDEC SmartRe...

Page 136: ...hnical data 30 to 70 C 0 to 10 V DC i e 0 to 1000 in IDEC SmartRelay Actual value internal value gain offset thus 30 0 A B i e offset B 30 70 1000 A 30 i e gain A 0 1 Example 2 A pressure sensor conve...

Page 137: ...000 mbar 3700 mbar 5000 mbar 0 6 75 10 0 675 1000 4 4 4 1000 1000 1000 1000 3700 5000 0 5 10 0 500 1000 0 01 0 01 0 01 0 0 0 0 5 10 0 5 10 0 500 1000 1 1 1 0 0 0 0 500 1000 0 5 10 0 500 1000 10 10 10...

Page 138: ...verts into a logical 1 An example of the program code found in Chapter 3 6 3 The table also specifies whether the relevant function can be set retentivity Rem The following SFs are available View in I...

Page 139: ...147 REM Random generator see page 149 Stairwell Light Switch see page 151 REM Dual function switch see page 154 REM Seven day time switch see page 157 Twelve month time switch see page 162 View in ID...

Page 140: ...r see page 174 Analog Analog trigger see page 177 Analog differential trigger see page 180 Analog comparator see page 184 Analog value monitoring see page 189 Analog amplifier see page 192 View in IDE...

Page 141: ...scellaneous Latching relay see page 195 REM Current impulse relay see page 196 REM Message texts see page 199 Softkey see page 206 REM Shift register see page 210 REM View in IDEC SmartRelay Name of t...

Page 142: ...e AQ see Chapter 4 4 26 Analog Ramp Control actual value AQ see Chapter 4 4 27 PI controller actual value AQ see Chapter 4 4 28 and Counter actual value Cnt see Chapter 4 4 13 Select the required func...

Page 143: ...If the referenced block B6 in the example returns a value that lies out of the valid range the value is rounded up or down to the next valid value Timebase max value min resolution Accuracy s seconds...

Page 144: ...its timebase is shown 3 Press to move the cursor to the B of the shown block and then press to select the required block number 4 Press to move the cursor to the block s timebase and press to select t...

Page 145: ...expiration of this time the output follows the input with on delay The time is reset when the status at input Trg returns to 0 be fore the time T has expired The output is reset to 0 when the signal a...

Page 146: ...Chapter 4 4 20 Analog multiplexer actual value AQ see Chapter 4 4 26 Analog Ramp Control actual value AQ see Chapter 4 4 27 PI controller actual value AQ see Chapter 4 4 28 and Symbol in IDEC SmartRe...

Page 147: ...EC SmartRelay is retriggered at the 1 to 0 transition of Trg The output remains set Output Q is reset to 0 with off delay when Ta reaches the value config ured at T Ta T The time Ta is retriggered wit...

Page 148: ...egative edge 1 to 0 tran sition at input Trg Trigger triggers the off delay time TL Parameter TH is the time after which the output is set hi output signal transition 0 to 1 TL is the time after which...

Page 149: ...be fore the time TH has expired A 1 to 0 transition at input Trg triggers the time TL If the status at input Trg is 0 at least for the duration of the signal TL the output is set to 0 on expiration o...

Page 150: ...e AQ see Chapter 4 4 26 Analog Ramp Control actual value AQ see Chapter 4 4 27 PI controller actual value AQ see Chapter 4 4 28 and Counter actual value Cnt see Chapter 4 4 13 Select the required func...

Page 151: ...Trg does not influence the time Ta The output and the time Ta are reset with the next 1 signal at input R If retentivity is not set output Q and the expired time are re set after a power failure Trg...

Page 152: ...gger triggers the time for the Inter val time delay relay function Parameter The output is switched off af ter the time T has expired output signal transition 1 to 0 Retentivity No retentivity R The s...

Page 153: ...Output Q is reset to lo pulse output when Ta reaches the value preset at T Ta T The output is immediately reset if there is a 1 to 0 transition at input Trg before the specified time has expired If re...

Page 154: ...e times for the edge triggered interval time delay relay Input R A signal at input R resets the current time Ta and the out put Parameter The interpulse width TL and the pulse width TH are con figurab...

Page 155: ...TL TH has expired Ta is reset and the pulse pause cycle is restarted If retentivity is not set output Q and the time are reset after a power failure Preset of the Par parameter View in programming mod...

Page 156: ...C SmartRelay Manual 146 View in parameter assignment mode example B25 TL 02 00s TH 03 00s Ta 01 15s Current pulse width TL or TH ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General I...

Page 157: ...reset the asynchronous pulse generator Input INV Input INV can be used to in vert the output signal of the active asynchronous pulse generator Parameter You can configure the pulse width TH and the in...

Page 158: ...ime High and TL Time Low parameters Input Inv can be used to invert the output signal provided the block is enabled with a signal at input EN If retentivity is not set output Q and the expired time ar...

Page 159: ...En Enable triggers the on delay time of the random generator A negative edge 1 to 0 tran sition at input En Enable triggers the off delay time of the random generator Parameter The on delay is set at...

Page 160: ...expired A 1 to 0 transition at input EN triggers a random on delay time between 0s and TL The output is reset after the off delay time has expired pro vided input En remains lo at least for the durati...

Page 161: ...g A signal at input Trg Trigger triggers the off delay time for the Stairwell Light Switch Parameter T represents the off delay time of the output output sig nal transition 1 to 0 T determines the tri...

Page 162: ...period T L A further one shot at input Trg during Ta retriggers the time Ta If retentivity is not set output Q and the expired time are re set after a power failure Preset of the Par parameter Note t...

Page 163: ...ctions 153 IDEC SmartRelay Manual View in parameter assignment mode example B9 1 T 60 00s Ta 06 00s Current value of T ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 8...

Page 164: ...rameter T represents the time after which f the output is reset output signal transition 1 to 0 TL represents the time during which the output must be set to enable the permanent lighting function T r...

Page 165: ...prior to the expiration of the off delay time to reset Q for the duration of the off warning signal T L A further signal at Trg always resets T and the output Q If retentivity is not set output Q and...

Page 166: ...L 20 00s Start of the off warning period T T Off warning time View in parameter assignment mode example B5 1 T 60 00s TL 10 00s Ta 06 00s Current value of the time TL or T ngineering Inc 230 Ryan Way...

Page 167: ...iming diagram three examples Cam No1 Daily 06 30 h to 08 00h Cam No2 Tuesday 03 10 h to 04 15h Cam No3 Saturday and Sunday 16 30 h to 23 10h Symbol in IDEC SmartRelay Wiring Description Cam parameters...

Page 168: ...cam3 takes priority over cam2 whereas cam2 takes priority over cam1 The switching state of the Seven day time switch is deter mined by the status of all three cams Parameter assignment screen form Vi...

Page 169: ...position of the on time 5 Set the on time Modify the value at the respective position using the keys and Move to the cursor to the various posi tions using the keys and At the first position you can o...

Page 170: ...res three cams Here are the parameter assignment screen forms of the cams No 1 2 and 3 based on the timing diagram shown ear lier Cam1 Cam No1 must set the output of the Seven day time switch daily fr...

Page 171: ...en day time switch switch every Saturday and Sunday from 16 30 h to 23 10 h B1 3 D SS On 16 30 Off 23 10 Result Q 1 1 2 3 1 1 1 1 1 3 Cam Monday Tuesday Wednesday Thursday Friday Saturday Sunday ngine...

Page 172: ...time The off date iden tifies the day on which the output is reset again The first val ue identifies the month the second the day For MM you can select a placeholder so that the on and off time is set...

Page 173: ...th time switches with corresponding on times The outputs are then logically linked by means of an OR block B1 MM DD On 03 01 Off 04 04 On time March 1 Off time April 4 B2 MM DD On 07 07 Off 11 19 In a...

Page 174: ...time is the first and off time the second day each month B12 DD On 10 Off 20 Each month from the 10th through to the 20th B13 DD On 25 Off 05 In the next month from the 25th through the 5th ngineerin...

Page 175: ...ing Description Input R A signal at input R resets the internal count value to zero Input Cnt The function counts the 0 to 1 transitions at input Cnt 1 to 0 transitions are not counted Use inputs I5 I...

Page 176: ...are re set after a power failure Q is set or reset depending on the current value at Cnt and the set thresholds See the calculation rule below Parameter On On threshold Range of values 0 999999 Off Of...

Page 177: ...trol actual value AQ see Chapter 4 4 27 PI controller actual value AQ see Chapter 4 4 28 and Counter actual value Cnt see Chapter 4 4 13 Select the required function by means of the block number For i...

Page 178: ...block B6 in the example returns a value that lies out of the valid range the value is rounded to the next valid value The view in parameter assignment mode example B3 On 001234 Off 000000 Cnt 000120...

Page 179: ...d value MI at the counter for the duration of the time to go MN Input En En is the monitoring input IDEC SmartRelay scans the on time of this input Input Ral A positive edge at input Ral Re set all re...

Page 180: ...ange of values 0000 9999 h OT The accumulated total operating time you can specify an offset Range of values 00000 99999 h Q 0 When R is selected Q 1 if MN 0 Q 0 if R 1 or Ral 1 When R En is selected...

Page 181: ...ating hours counter OT continues the count With a signal at the reset input Ral you reset output Q and set the preset value of MI at the counter for the duration of MN The Operating hours counter OT...

Page 182: ...T continues the count as long as En 1 irrespective of the status at the reset input R The counter limit of OT is 99999 h The Operating hours counter stops when it reaches this val ue In programming mo...

Page 183: ...C SmartRelay Manual View in parameter assignment mode B16 MI 0100h MN 0017h OT 00083h Time interval Time to go Total operating hours ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 Gener...

Page 184: ...I5 I6 for high speed counting only FL1D H12RCE FL1D B12RCE and FL1D H12SND max 2 kHz any other input or circuit com ponent for counting low fre quency signals typ 4 Hz Parameter On On threshold Range...

Page 185: ...ulation rule If the On threshold Off threshold then Q 1 if fa On Q 0 if fa Off If the On threshold Off threshold then Q 1 if On fa Off Preset of the Par parameter Note The system scans the counter lim...

Page 186: ...preset a time G_T of 1 s the IDEC SmartRelay returns the current frequency in parameter fa in Hz View in parameter assignment mode example B15 On 0009 Off 0005 fa 0010 On threshold Off threshold Q 1...

Page 187: ...o be analyzed at input Ax Use the analog inputs AI1 AI8 the Analog Memory Markers AM1 AM6 the block num ber of a function with analog output Parameter A Gain Range of values 10 00 B Offset Range of va...

Page 188: ...n The function fetches the analog signal at input Ax Ax is multiplied by the value of the A gain parameter and the value at parameter B offset is added to product i e Ax gain offset actual value of Ax...

Page 189: ...4000 Off 02000 Parameter protection mode On threshold Off threshold Press B3 2 A 01 00 B 00000 p 2 Gain Offset Decimals in the message text View in parameter assignment mode example B3 On 04000 Off 02...

Page 190: ...zed at input Ax Use the analog inputs AI1 AI8 the Analog Memory Markers AM1 AM6 the block num ber of a function with analog output Parameter A Gain Range of values 10 00 B Offset Range of values 10 00...

Page 191: ...nctional description The function fetches the analog signal at input Ax Ax is multiplied by the value of the A gain parameter and the value at parameter B offset is added to product i e Ax gain offset...

Page 192: ...B Preset of the Par parameter The gain and offset parameters are used to adapt the sen sors to the relevant application View in programming mode example B3 1 On 04000 02000 Parameter protection mode O...

Page 193: ...IDEC SmartRelay functions 183 IDEC SmartRelay Manual Press B3 Off 02000 Off threshold ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4183 www ste...

Page 194: ...ference you want to analyze at the inputs Ax and Ay Use the analog inputs AI1 AI8 the Analog Memory Markers AM1 AM6 the block num ber of a function with analog output Parameter A Gain Range of values...

Page 195: ...the analog values from the inputs Ax and Ay Ax and Ay are each multiplied by the value of the A gain pa rameter and the value at parameter B offset is then added to the relevant product i e Ax gain of...

Page 196: ...ter protection mode On threshold Off threshold Press B3 2 A 00 00 B 00000 p 0 Gain Offset Decimals in the message text Example In a heating control system the supply Tv and return line temperatures Tr...

Page 197: ...A 00 10 B 00030 p 0 Gain Offset Decimals in the message text if used View in parameter assignment mode example B3 1 On 00015 Off 00005 On threshold Off threshold Application Internal mapping 30 to 70...

Page 198: ...y means of the On delay and Off delay special func tions With on delay output Q is only set if the pulse width of the triggering signal at input Trg analog comparator out put is longer than the on del...

Page 199: ...ut En saves the analog val ue at input Ax Aen to memory and starts monitoring of the ana log range Aen Input Ax You apply the analog signal to be monitored at input Ax Use the analog inputs AI1 AI8 th...

Page 200: ...ed to as Aen Both the analog actual values Ax and Aen are multiplied by the value at parameter A gain and parameter B offset is then added to the product i e Ax gain offset Actual value Aen when input...

Page 201: ...w in programming mode B3 1 00000 Parameter protection mode Differential value for the on off threshold Press B3 2 A 00 00 B 00000 p 0 Gain Offset Decimals in the message text View in parameter assignm...

Page 202: ...ymbol in IDEC SmartRelay Wiring Description Input Ax You apply the analog signal to be amplified at input Ax Use the analog inputs AI1 AI8 the Analog Memory Markers AM1 AM6 the block number of a funct...

Page 203: ...on to a value range of 0 to 1000 Scaling an analog input value You can influence the analog input value of a potentiometer by interconnecting an analog input with an analog amplifier and an analog mem...

Page 204: ...lay functions IDEC SmartRelay Manual 194 View in parameter assignment mode example B3 A 02 50 B 00300 AQ 00250 ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 4...

Page 205: ...urrent status of the output signal is retained after a power failure Symbol in IDEC SmartRelay Wiring Description Input S You set output Q with a sig nal at input S Input R You reset output Q with a s...

Page 206: ...put Q with a sig nal at input S Input R You reset output Q with a signal at input R Parameter Selection RS R input priority or SR S input priority Retentivity No retentivity R The status is retentive...

Page 207: ...the output is set hi You reset the current impulse relay with a signal at input R i e the output is set lo Status diagram RS or SR Triggering signal is effective because S and R 0 Par Qn 1 S R Trg Qn...

Page 208: ...rent impulse relay and output Q are reset if you have not enabled retentivity View in programming mode B29 R Par RS B29 R Par SR Press or This special function is not available in parameter assign men...

Page 209: ...rameter Text Input of the message text Par Parameter or actual value of another al ready programmed function see Visible parameters or process variables Time Display of the continu ously updated time...

Page 210: ...es from 1 to 0 the message text is output until it is acknowledged with OK When En 1 you can not acknowledge the message text When multiple message text functions are triggered with En 1 the message t...

Page 211: ...with priority 10 Date and current time of day only for versions with real time clock Input P configuration To configure the priority and the acknowledgment program ming mode B33 Priority 00 Quit Off...

Page 212: ...tive on delay T Ta Interval time delay relay Pulse output T Ta Edge triggered interval time de lay relay Ta TH TL Asynchronous pulse generator Ta TH TL Random generator TH TL Stairwell Light Switch Ta...

Page 213: ...nges with OK You can now edit further pa rameters in the message text if any exist Press ESC to exit editing mode Key input simulation in the active message text You can enable the four cursor keys C...

Page 214: ...ct ed Press or to select the letter to be displayed in the text To move the cursor from one position to the other press or The list of available characters is here the same as for the circuit program...

Page 215: ...s to be displayed and the corresponding parameters Press or to select the block or parameter you want to view Select the parameter by pressing OK Press ESC to exit the parameter assignment mode and to...

Page 216: ...confirmed in parameter assignment mode Parameter Programming mode Selecting the function for pushbutton action for the du ration of one cycle or for switching action Start On or off state initial ized...

Page 217: ...ition Off was selected at the Switch pa rameter and confirmed with OK in parameter assignment mode If retentivity is not set output Q is initialized after a power fail ure according to your configurat...

Page 218: ...lay shows the following display B33 Switch Off The momentary pushbutton switch is here switched off Let us assume you want to set Switch On 1 Change to the editing mode Confirm with OK the cursor is n...

Page 219: ...Relay functions 209 IDEC SmartRelay Manual B33 Switch On The momentary pushbutton switch is here switched on ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inquiries 800 670 418...

Page 220: ...rt of the function Input Trg A positive edge 0 to 1 transi tion at input Trg Trigger starts the special function 1 to 0 transitions are irrelevant Input Dir The signal at input Dir deter mines the shi...

Page 221: ...is shifted to S7 the previous value at S7 is shifted to S6 etc Output Q returns the value of the configured shift register bit If retentivity is disabled the shift function restarts at S1 or S8 after...

Page 222: ...ter View in programming mode B3 R Q S8 Retentivity enabled Preset Press B3 R Q S7 etc You can select S8 S1 This special function is not available in parameter assign ment mode ngineering Inc 230 Ryan...

Page 223: ...hange in status from 0 to 1 at input En Enable switches a parameterized analog value to the output AQ depending on the value of S1 and S2 Inputs S1 and S2 S1 and S2 selectors for selecting the analog...

Page 224: ...ntroller actual value AQ see Chapter 4 4 28 and Counter actual value Cnt see Chapter 4 4 13 Select the required function by means of the block number For information on parameter defaults refer to Cha...

Page 225: ...sues the analog value 0 at output AQ Analog output If you interconnect this special function with a real analog output note that the analog output can only process values between 0 and 1000 To do this...

Page 226: ...View in programming mode example B3 1 V1 04000 V2 02000 B3 2 V3 B020 V4 B021 p 0 Press View in parameter assignment mode B3 1 V1 04000 V2 02000 B3 2 V3 B020 V4 B021 AQ 4000 Press ngineering Inc 230 R...

Page 227: ...o the selected level A change in the status from 1 to 0 immediately sets the output AQ to 0 Input Sel SeI 0 Level1 is selected SeI 1 Level2 is selected A change instatus of Sel caus es the output AQ t...

Page 228: ...that is added to Offset B to create the start stop lev el If the Start Stop offset is 0 then the start stop level is Offset B Range of values 10 000 to 20 000 Rate Acceleration with which level 1 leve...

Page 229: ...I controller actual value AQ see Chapter 4 4 28 and Counter actual value Cnt see Chapter 4 4 13 Select the required function by means of the block number For information on parameter defaults refer to...

Page 230: ...Offset B is issued at output AQ The scaled value is 0 If the input St isset the function can only be restarted once the inputs St and En have been reset If input Sel has been changed depending on the...

Page 231: ...L 7000 StSp 00222 Rate 00500 B3 3 A 02 50 B 00300 p 0 Gain Offset Decimals in the message text Press Press View in parameter assignment mode B3 1 L1 04000 L2 B020 AQ 00250 B3 2 StSp 00222 Rate 00500 B...

Page 232: ...l in IDEC SmartRelay Wiring Description Input A M Set the mode of the controller 1 automatic mode 0 manual mode Input R Use the input R to reset the output AQ As long as this input is set the input A...

Page 233: ...9 59 m Dir Action direction of the controller Range of values or Mq Value from AQ with manual mode Range of values 0 to 1000 Min Minimum value for PV Range of values 10 000 to 20 000 Max Maximum value...

Page 234: ...unter actual value Cnt see Chapter 4 4 13 Select the required function by means of the block number For information on parameter defaults refer to Chapter 4 4 1 Parameters KC TI Please note If paramet...

Page 235: ...Min Max PV SP Q 1 A disturbance causes the PV to drop as Dir is positioned upwards AQ increases until PV corresponds again to SP 2 A disturbance causes the PV to drop as Dir is positioned downwards A...

Page 236: ...then the special function reduces the value of AQ If the updated value PV SP then the special function increases the value of AQ Dir downwards timing diagram number 2 If the updated value PV SP then t...

Page 237: ...ication related parameter sets for KC TI and Dir refer to the online help for WindLGC Preset of the Par parameter View in programming mode example B3 1 SP B020 B3 2 KC 10 00 TI 01 00 Dir B3 4 A 02 50...

Page 238: ...w in parameter assignment mode B3 1 SP B020 PV 0 AQ 0250 B3 2 KC 10 00 TI 01 00 Dir B3 4 A 02 50 B 00300 B3 3 Mq B021 Min 05000 Max 05000 Press Press Press ngineering Inc 230 Ryan Way South San Franci...

Page 239: ...ode In programming mode the author of the circuit program also sets the parameters We have added the parameter assignment mode to allow the editing of parameters without having to modify the circuit p...

Page 240: ...7 Mo 09 00 ESC Press Note The following applies to earlier device versions up to 0BA2 You open parameter assignment mode by pressing ESC OK IDEC SmartRelay changes to parameter assignment mode and ope...

Page 241: ...o confirm Yes Press OK IDEC SmartRelay shows the main menu of the programming mode Program Card Setup Start Set Param For information on the various parameters refer to the Chapters 5 1 1 to 5 1 3 Set...

Page 242: ...ameters are for example The delay times of a time relay The switching times cams of time switch Counter thresholds The monitoring time for hour counters The trigger thresholds Each one of the paramete...

Page 243: ...assignment menu 3 Now select the desired parameter Press or 4 Select the parameter you want to edit and press OK Stop Set Param Set Prg Name B9 1 Press ESC No Param T 60 00s Ta 06 00s Block number Dis...

Page 244: ...you can also change the timebase s seconds m minutes h hours This does not apply if the time parameter represents the re sult of another function for an example see Chapter 4 4 1 In this case you can...

Page 245: ...f B021 Cnt 000120 or Current count value You can change the On Off threshold This does not apply if the on or off threshold represents the result of another func tion in the example this is B21 see Ch...

Page 246: ...ger View of the parameter of a frequency trigger in parameter as signment mode B15 On 0009 Off 0005 fa 0010 On threshold Off threshold Process variable You can change the On Off threshold ngineering I...

Page 247: ...Chapter 3 6 14 Contrast settings You can set the default value for the display contrast in parameter assignment mode by means of the set menu Contrast menu item in programming mode by means of the se...

Page 248: ...rtRelay is equipped with a real time clock You set the real time clock of IDEC SmartRelay by means of the Set Clock command IDEC SmartRelay shows the following display Set Clock Mo 15 30 YYYY MM DD 20...

Page 249: ...enu item To set the display contrast in parameter assignment mode 1 Select parameter assignment mode see Chapter 5 1 2 On the parameter assignment menu select Set Press or 3 Confirm Set Press OK 4 Mov...

Page 250: ...Set Press or 3 Confirm Set Press OK 4 Move the cursor to StartScreen Press or 5 Confirm StartScreen Press OK IDEC SmartRelay shows the following display Clock Input DI StartScreen Clock The current se...

Page 251: ...hiving circuit programs Reproducing circuit programs Write and test your circuit program at the office and then transfer it to a IDEC SmartRelay in the switching cabinet IDEC SmartRelay is supplied wi...

Page 252: ...ersions FL1A or FL1B devices can not be used in IDEC SmartRelay devices of the FL1C or FL1D generation When the IDEC SmartRelay system detects such an old memory cartridge card the message Unknown Car...

Page 253: ...execute this circuit program in IDEC SmartRelay the pro tected memory cartridge card must remain inserted during RUN i e the circuit program stored on the memory cartridge card can not be copied to ot...

Page 254: ...SC Stop 2 The main menu opens To select the Card command Press or 3 To apply Card Press OK 4 Move the cursor to CopyProtect Press or 5 To apply CopyProtect Press OK IDEC SmartRelay shows the following...

Page 255: ...ry cartridge card the circuit program itself must be copied separately from the IDEC SmartRelay to the memory cartridge card can also be done initially You can always change the No status security fun...

Page 256: ...tridge card IDEC SmartRelay outputs the message No Program A removal of the memory cartridge card during RUN will lead to imper missible operating states Always heed the following warning Warning Do n...

Page 257: ...ry cartridge removal tool MT 101 and pull the memo ry cartridge straight out Inserting a memory cartridge card The entry of the memory cartridge card slot is chamfered on its bottom right The edge of...

Page 258: ...select the Card command Press or 4 Press OK The transfer menu opens 5 Move the cursor to IDEC SmartRelay Card if re quired Press or 6 Press OK IDEC SmartRelay now copies the circuit program to the me...

Page 259: ...orget to replace the cap If power fails while IDEC SmartRelay is copying the circuit program repeat the process after Power On Note The password X of a protected circuit program in IDEC SmartRelay als...

Page 260: ...the copied program in the IDEC SmartRelay is also protected with the same password Automatic copying during the startup of IDEC SmartRelay Proceed as follows 1 Switch off the power supply to IDEC Sma...

Page 261: ...rom the memory cartridge card to IDEC SmartRelay 1 Insert the memory cartridge card 2 Switch IDEC SmartRelay to programming mode ESC Stop 3 Move the cursor to Card Press or 4 Press OK The transfer men...

Page 262: ...rcuit programs Easy configuration of blocks Transferring the circuit program from IDEC SmartRelay to the PC and from the PC to IDEC SmartRelay Reading the values of the hour counter Setting the TOD Su...

Page 263: ...o the file system on your PC to make it directly available for any modifi cations 5 It takes only a few key actions to download the circuit program to IDEC SmartRelay WindLGC WindLGC runs under Window...

Page 264: ...processed first and then the outputs Thus the output results are not reflected on the inputs within the same scan time but rather they are reflected at the following scan ex Interlock is not activated...

Page 265: ...the instructions on the screen when you install the driver for the converter Make sure you specify the correct Windows OS version when you select the driver Switching IDEC SmartRelay to PC IDEC SmartR...

Page 266: ...with WindLGC is password protected both the circuit program and the password are downloaded to IDEC SmartRelay The password prompt is enabled at the end of the data transfer The upload of a password...

Page 267: ...t diagram and com pared it with the IDEC SmartRelay solutions You can find solutions for the following tasks Page Stairway or corridor lighting system page 259 Automatic door page 263 Ventilation syst...

Page 268: ...ponsibility We refer to the relevant national standards and system related installation reg ulations Although you have four inputs available for logic operations basic functions see Chapter 4 2 the fo...

Page 269: ...ff in order to save energy 8 1 2 Previous solution The two conventional options for switching the lights With a pulse relay With an automatic stairway lighting switch The wiring of both these lighting...

Page 270: ...aning the stairway The switch for permanent lighting is usually located on the auto matic stairway lighting switch and may be difficult or impos sible to access 8 1 3 Lighting system with IDEC SmartRe...

Page 271: ...ry functions are entered directly in IDEC SmartRelay Current impulse relay with IDEC SmartRelay Output Q1 is toggled with a pulse signal at input I1 Automatic stairway lighting switch with IDEC SmartR...

Page 272: ...flashing function that indicates that the light is about to be switched off automatically You can integrate various central functions Central off Central on panic button Control of all lamps or indivi...

Page 273: ...red When the doorway is cleared the door must close auto matically with a short delay B1 B2 Q1 S1 S2 Outside inside Motion detector Limit switch closed Limit switch open Motion detector Master switch...

Page 274: ...g motion is initiated by setting K3 After the detection range of the two motion sensors has been cleared at least for a minimum time K4 enables the closing motion 8 2 3 Door control system with IDEC S...

Page 275: ...ontact limit switch close S2 normally closed contact limit switch open B1 normally open contact infrared motion sensor outside B2 normally open contact infrared motion sensor inside L1 N I4 I5 I6 I7 I...

Page 276: ...elay functions You can use the off delay function to replace the latching relay and the on delay The block dia gram below illustrates this simplification 1 1 1 I4 I3 I1 I2 x Q2 Q1 x 10 s Q1 Q2 Open Cl...

Page 277: ...C Smar tRelay to warn of the closing of the door You can enable opening of the door time and direc tion dependent i e opening only during business hours and opening only from the inside after closing...

Page 278: ...0 Cam1 Day Mo Fr On 09 00 Off 19 00 Cam2 Day Sa On 08 00 Off 14 00 Motion detector B1 Motion detector B2 Actuate motor for opening Open Close Close output Limit switch Door open Control switch Door op...

Page 279: ...nently open or The motion detectors indicate that somebody is ap proaching the door and The door has not yet fully opened limit switch at I4 Actuating the motor for closing Output Q2 is set to close t...

Page 280: ...Flow sensor Flow sensor Exhaust fan The room is equipped with an exhaust fan and a fresh air fan Both fans are monitored by means of a flow sensor An excess atmospheric pressure may never develop in...

Page 281: ...message is output This message can be acknowledged by pressing the OFF button In addition to the flow sensors the fan monitoring system also requires an evaluating circuit with several switching de vi...

Page 282: ...lamp H2 signal lamp Block diagram of the IDEC SmartRelay solution The block diagram of the air conditioning system with IDEC SmartRelay x I1 Q3 I2 Q1 Q2 Q1 I3 x I2 x T 10 s x T 10 s x x x I3 I4 Q1 Q2...

Page 283: ...t is possible to switch off of the fans by means of a se quential circuit These functions can be implemented without additional switchgear Block diagram of the extended IDEC SmartRelay solution The fa...

Page 284: ...contacts of output Q4 are always closed when the system is in operation Relay Q4 does not drop off unless there is a power failure or a fault in the system This contact can be used for remote monitori...

Page 285: ...e The porter can monitor the operation of the gate at the same time The gate is normally fully opened or fully closed The gate motion can be interrupted at any time An indicator lamp is switched on fi...

Page 286: ...K2 L1 N K1 H1 K4 S5 p K6 K6 K1 S2 S2 K3 K2 K4 K5 S5 p S1 K3 K1 S4 S3 Open Close Indicator lamp Open Close Auxiliary circuit Wiring of a gate control system with FL1D H12RCC L1 N I4 I5 I6 I7 I8 Q1 Q2 Q...

Page 287: ...E pushbuttons initiate the gate motion provided it is not already moving in the other direction The gate is stopped by means of the STOP pushbutton or the rel evant limit switch A safety bar furthermo...

Page 288: ...the safety bar is actuated x x I6 x Q2 I3 I4 x I1 Q2 T 5 s Q1 T 5 s x Q2 I3 I6 I5 I2 Q1 Q3 TH TL 2 s Inv lo Safety bar STOP pushbutton Gate is open OPEN pushbutton CLOSE pushbutton STOP pushbutton Sa...

Page 289: ...tehouse It must also be possible for a member of staff to open and close the gate locally For each gate we are going to use one FL1D H12RCC and one communication module The modules and the master are...

Page 290: ...or GATE CLOSED status is indicated An indicator lamp is switched on five seconds before the gate starts moving and when the gate is in motion A safety pressure bar prevents harm to persons and ob ject...

Page 291: ...3 normally open contact CLOSE pushbutton S4 normally closed contact position sensor GATE IS OPEN S5 normally closed contact position sensor GATE IS CLOSED S6 normally closed contact Safety bar Master...

Page 292: ...ective limit switch Closing of the gate is also interrupted by the safety bar Gate is open Open gate Open gate Gate is open Open gate by hand Gate is open Close gate by hand Gate is closed Safety bar...

Page 293: ...way the room is used 8 6 1 Requirements for a lighting system The various luminous rows are switched on and off local ly If there is sufficient daylight the rows on the window side of the room are au...

Page 294: ...to al low operation of the lights after they are switched off Components required Pushbuttons S1 to S4 Daylight control switch B1 Timer E1 Interval time delay relays K1 and K2 Pulse switches K3 to K6...

Page 295: ...1 lx E5 S1 S2 S3 S4 I4 I5 I1 I2 I3 1 2 1 2 1 2 1 2 Luminous rows 1 Luminous rows 2 Luminous rows 3 Luminous rows 4 Components used S1 to S4 normally open contact momentary pushbutton B1 normally open...

Page 296: ...n install a smaller and space saving distribution cabinet Fewer devices are required The lighting system can be easily modified Additional switching times can be set as required se quential circuit fo...

Page 297: ...S1 S2 S3 S4 M1 K4 Rainwater supply line Drinking water supply line Pressure switch Control in the distribution box Pressure tank Pump Rainwater reservoir Drinking water supply Off Drinking water supp...

Page 298: ...ion K1 K2 K3 S1 K3 S4 K3 L1 N K4 S3 K4 p K2 S3 S2 Y1 Auxiliary circuit Pump Tracking time Dry run protection Drinking water supply line The pump and a solenoid valve are controlled by means of a press...

Page 299: ...or relay to switch the pump For single phase AC pump systems you must provide a contactor relay if the power consumption of the AC motor exceeds the capacity of the output relay Q1 The power consumpti...

Page 300: ...ch can only be implemented in a conventional circuitry by add ing further switchgear e g Enabling the pump at specific times Indication of imminent or existing water shortage Reporting of system fault...

Page 301: ...t regular intervals or opens and closes the shut ters while you are on holiday Central heating IDEC SmartRelay runs the circulation pump only when water or heating is actually required Refrigerating s...

Page 302: ...lay Manual 292 Do you want more Info For more information about IDEC SmartRelay see our web page see the preface for the URL ngineering Inc 230 Ryan Way South San Francisco CA 94080 6370 General Inqui...

Page 303: ...l installation Vertical installation Low temperature to IEC 60068 2 1 High temperature to IEC 60068 2 2 0 55 C 0 55 C Storage shipping 40 C 70 C Relative humidity IEC 60068 2 30 From 10 to 95 no conde...

Page 304: ...o FL1D H12RCC FL1D B12RCC IEC 61000 4 5 Severity 3 1 kV power lines symmetrical 2 kV power lines asymmetrical Safety to IEC VDE Clearance and creepage distance rating IEC 60664 IEC 61131 2 EN 50178 cU...

Page 305: ...30 mA 10 20 mA 5 15 mA 5 10 mA Voltage failure buffering 100 V AC 240 V AC typ 10 ms typ 20ms typ 10 ms typ 20ms Power loss at 100 V AC 240 V AC 100 V DC 240 V DC 1 1 4 6W 2 4 6 W 0 5 2 9 W 1 2 3 6 W...

Page 306: ...tputs Electrical isolation Yes Yes Dielectric Strength between power input terminals and output terminals 2 500 V AC 1minute 500 V DC 1 minute 2 500 V AC 1minute 500 V DC 1 minute In groups of 1 1 Con...

Page 307: ...6 A characteristic B16 Minimum Switching Load 10 mA 12 V DC 10 mA 12 V DC Initial Contact Resistance 100 m maximum at 1A 24V DC 100 m maximum at 1A 24V DC Mechanical Life 10 000 000 operations minimum...

Page 308: ...Power loss at 24 V 0 7 1 3 W 0 8 1 1 W Backup of the real time clock at 25 C Accuracy of the real time clock Digital inputs Number 8 4 Electrical isolation No No Input voltage Signal 0 Signal 1 L 5 V...

Page 309: ...on No No In groups of Control of a digital input Yes Yes Output voltage Supply voltage Supply voltage Output current max 0 3 A max 0 3 A Continuous current Ith Incandescent lamp load 25000 switching c...

Page 310: ...on 1 to 4 specifications For identifying the version see page 4 4 When FL1D H12SND or FL1B M08B1S2 are switched on signal 1 is sent to the digital outputs for about 50 microseconds Take this into acco...

Page 311: ...20 75 mA 40 100 mA 20 75 mA Voltage failure buffering typ 5 ms typ 5 ms Power loss 24 V AC 24 V DC 0 9 2 7 W 0 4 1 8 W 0 9 2 7 W 0 4 1 8 W Backup of the real time clock at 25 C typ 80 h Accuracy of th...

Page 312: ...s of 1 1 Control of a digital input Yes Yes Output voltage Output current Continuous current Ith max 10 A per relay max 5 A per relay Surge current max 30A max 30A Incandescent lamp load 25000 switchi...

Page 313: ...0 m maximum at 1A 24V DC 100 m maximum at 1A 24V DC Mechanical Life 10 000 000 operations minimum no load 10 Hz 10 000 000 operations minimum no load 10 Hz Electrical Life 100 000 operations minimum r...

Page 314: ...ng 12 V DC 24 V DC typ 2 ms typ 5 ms typ 2 ms typ 5 ms Power loss 12 V DC 24 V DC 0 3 1 7 W 0 4 1 8 W 0 3 1 7 W 0 4 1 8 W Backup of the real time clock at 25 C typ 80 h Accuracy of the real time clock...

Page 315: ...m Error limit 1 5 of full scale Digital outputs Number 4 4 Output type Relay outputs Relay outputs Electrical isolation Yes Yes Dielectric Strength between power input terminals and output termials 2...

Page 316: ...Short circuit proof cos 0 5 to 0 7 Power protection B16 900A Power protection B16 900A Parallel output circuits for power increase Not permitted Not permitted Protection of output relay if desired ma...

Page 317: ...5 specifications For identifying the version see page 4 FL1D H12RCE FL1D B12RCE FL1B M08B2R2 Note When connecting a fluorescent lamp to the output take the inrush current into consideration When the i...

Page 318: ...s solenoid coils motors 0 1 0 2 0 3 0 4 0 5 2 4 6 8 10 Switching cycles million 12 24 V AC DC 100 120 V AC 230 240 V AC 120 V DC 240 V DC Switched current A Maximum 10 A Maximum 10 A Maximum 10 A Maxi...

Page 319: ...nal for connecting ground and shielding of the analog measuring line Analog inputs Number 2 Type Unipolar Input range 0 10 V DC input impedance 76 k or 0 20 mA input impedance 250 Resolution 10 bit no...

Page 320: ...ng line Analog outputs Number 2 Input range 0 10 V DC Load resistor 5 k Resolution 10 bit normalized to 0 1000 Cycle time for analog value output depending on installation typ 50 ms Electrical isolati...

Page 321: ...This test program is created in IDEC SmartRelay and returns a value during its execution in parameter assignment mode from which the current cycle time is derived Test program 1 Create the test progra...

Page 322: ...nverted marker block changes its output signal at each program execution Thus one logic level high or low width is exactly equivalent to the length of one cycle Hence a pe riod lasts 2 cycles The freq...

Page 323: ...ore The versions without display offer you the following benefits Even more cost effective without the operating element Requires less switch cabinet space than conventional hardware Substantial benef...

Page 324: ...by means of buttons This is why the FL1D B12 versions have other startup characteristics Startup characteristics If there is no circuit program in the IDEC SmartRelay or on the inserted memory cartri...

Page 325: ...nt data WindLGC see Chapter 7 provides an online test for reading the current data of all functions while the system is in RUN If your IDEC SmartRelay without display holds a protected memory cartridg...

Page 326: ...t menu Parameter setting Chapter 5 1 1 cont Default values setting Chapter 5 2 cont Display of the program name See Main menu Main menu ESC Stop See Programming menu See Transfer menu See Setup menu S...

Page 327: ...apter 6 3 Copying the program from the memory cartridge card to IDEC SmartRelay Chapter 6 4 Setting the program copy protection Chapter 6 1 Setup menu ESC Stop Setup Setting the time date Chapter 5 2...

Page 328: ...240V AC DC 8 4 Yes Yes FL1D B12RCC FL1D H12RCA 24V AC DC 8 4 Yes Yes FL1D B12RCA FL1D H12RCE 12 24V DC 8 I1 I8 2 I7 I8 4 Yes Yes FL1D B12RCE FL1D H12SND 24V DC 8 I1 I8 2 I7 I8 4 Tr Yes Expansion Modul...

Page 329: ...incl Hardware Software Manual FL9Y LP1CDW PC Cable Down load Up load Cable FL1A PC1 Memory cartridge Brown FL1C PM3 User s Manual FL1D User s Manual English FL9Y B966 Mounting Clip 5 pieces FL1B PSP1P...

Page 330: ...ion 115 NAND 116 NAND with Edge Detection 117 NOR 119 NOT 120 OR 118 XOR 120 blank outputs 55 110 Block deleting 91 block groups 92 inserting 85 number 57 assigning 58 BN 108 C Cap 20 Card See memory...

Page 331: ...Display 58 Display contrast 239 Disposal 12 DM See Digital module Dual function switch 154 E Earth connection 28 Edge detection 115 117 Edge triggered interval time delay relay 144 Editing 85 Example...

Page 332: ...relay edge triggered 144 Internet address ii Interpulse width 148 Interval time delay relay Pulse out put 142 Inverter 120 L Latching relay 195 LCD 4 5 LED 315 Levels 111 List BN 108 Co 108 109 GF 108...

Page 333: ...cs 314 Status indication 315 Operating hours counter 169 Reading the MN and OT values 172 Operating mode Changing the operating mode 63 Programming mode 66 OR 118 Outputs 110 blank 55 110 connecting 4...

Page 334: ...haracteristics 29 Sensor connections 34 Set Set 238 Setting Default values 237 Display contrast 239 Start screen 240 time 88 Time of day and date 237 Setting the date 237 Setting the time of date 237...

Page 335: ...lock 96 disabling 100 enabling 97 user define parameters 99 Switch Dual function switch 154 Seven day time switch 157 Stairwell Light Switch 151 Twelve month time switch 162 Switched current maximum 4...

Page 336: ...USB 255 V Verification 89 Voltage levels 111 Voltage supply connecting Circuit protection 28 W Weekday 158 WindLGC 253 Wintertime 96 Wire ferrules 26 without display 313 creating a circuit program 52...

Reviews: