3: I
NSTALLATION
AND
W
IRING
3-2
S
MART
AXIS P
RO
/L
ITE
U
SER
'
S
M
ANUAL
FT9Y-B1378
The SmartAXIS can be mounted face up when the ambient temperature is 35°C or lower, and can be mounted on its side when the
ambient operating temperature is 40°C or lower. Do not mount the SmartAXIS on its side when the ambient temperature will
exceed 40°C.
Do not install the SmartAXIS face down.
Mounting Space
To allow for heat dissipation and facilitate replacement, ensure that there are at least 20 to 40mm between the SmartAXIS and
surrounding equipment and ducts.
Mounting Two or More Units
Face Up Orientation (Use if 35°C or less)
Side Orientation (Use if 40°C or less)
Face Down
20mm minimum
20mm minimum
40mm minimum
40mm minimum
DIN Rail
20mm minimum
40mm minimum
DIN Rail