Output Terminal Wiring
SmartAXIS
Input Terminal (I*)
COM
• 2-wire Sensor
Sensor Power Supply
/ External Power
Sensor Power Supply
/ External Power
SmartAXIS
• PNP Output
Input Terminal (I*)
Sensor Output
COM
-
-
+
+
Internal
Circuit
Internal
Circuit
Output
•
If output relays or transistors in the SmartAXIS or output modules should fail, outputs may remain on or off. For
output signals which may cause heavy accidents, provide a monitor circuit outside the SmartAXIS.
•
Connect a fuse to the output module, selecting a fuse appropriate for the load.
•
Use proper wires for output wiring.
UL1015 AWG22 or UL1007 AWG18
•
When equipment containing the SmartAXIS is intended for use in European countries, insert an IEC 60127-approved
fuse to each output of every module for protection against overload or short-circuit. This is required when equipment
containing the SmartAXIS is destined for Europe.
•
When driving an inductive load that emits noise like a magnet or a valve, to reduce noise and protect circuits, use a
diode for the output on DC power type models and a surge absorber for the output on AC power type models.
•
Turn off the power to the SmartAXIS when wiring input/output terminals.
•
Emergency stop and interlocking circuits must be configured outside the SmartAXIS.
•
Use the input/output terminals within the SmartAXIS ratings and specifications.
•
Tighten mounting screws with torque of 0.5N·m (5 gf·cm).
Caution
Summary of Contents for FT1A-B12RA
Page 1: ...FT9Y B1378 5 ...
Page 2: ......
Page 208: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Page 226: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Page 340: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...
Page 385: ...SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 A 19 APPENDIX Japanese Font JIS X0201 ...
Page 386: ...APPENDIX A 20 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 ...