Ideal Logic Combi -
Installation and Servicing
85 aLTERNaTING ‘F’ aND ‘6’ - OUTsIDE sENsOR FaULT
Disconnect the wires to the outside sensor.
Check the resistance using a suitable multimeter
connected across the Outside Sensor’s terminal pins.
At 0
o
C
expect
31,000 - 35,000
Ohms
At 15
o
C expect
15,000 - 16,500
Ohms
At 30
o
C expect
7,700 - 8,500
Ohms
Is the Outside Sensor value correct?
YES
Is the wiring securely connected between the
incoming terminal block boiler connection of the
Outside Sensor and the PCB?
Replace PCB
Fit a new Outside Sensor
NO
Securely connect the wiring at the
Terminal Block and the PCB
Is the wiring securely connected at both the boiler and
Outside Sensor?
YES
NO
Securely connect the wiring at both the
boiler and Outside Sensor
NO
YES
86 aLTERNaTING ‘c’ aND ‘2’ - BCC FaULT (BOILER ChIP CaRD)
Is the correct BCC for the boiler securely inserted into the
slot at the front left of the PCB?
(identified by the label on the BCC)
YES
NO
Securely insert the correct BCC for the boiler
into the PCB and after switching power on and
‘c0’ being shown, reset boiler.
Note.
Ensure the correct orientation of BCC by
placing “TOP” side up.
Replace the BCC with a new BCC (that is correct for the
boiler). After switching power on and ‘c0’ being shown,
press reset. Is ‘c2’ still shown?
Replace PCB
YES
REsET PROCEDURE
- To reset boiler, turn mode knob to reset position and immediately turn knob back to required setting.