FLUE
OUTLET
Notes.
1.
It is recommended that a support bracket
is fitted for every 1 metre of extension pipe
used and a bracket should be used at every
joint, to ensure pipes are held at the correct
angle.
If a slip joint coupling is to be used then a
bracket should be used to secure the collar.
2.
When extension ‘D’ packs are used the flue
duct MUST be inclined at 1.5 degrees to
the horizontal to allow condensate to drain
back into the boiler and out through the
condensate drain.
3.
If the B pack, or telescopic B pack only are
used, they may be mounted horizontally.
The 1.5 degrees is taken care of by the
inclination of the flue within the air pipe.
4.
Only use water as a lubricant during
assembly.
11 DETERMINING ThE FLUE LENGTh aND FLUE PaCKs REqUIRED CONT’D
12 FLUE assEMBLy - Exploded View
An optional flue duct extension
kit is required for wall
thicknesses greater than :
side
378mm
Rear
420mm
telescopic b Pack shown
LEGEND
1.
Duct assembly.
2.
Flue turret.
3.
Turret clamp.
The flue terminal MUST
be fitted with the ‘TOP’
uppermost to allow the
correct fit and use of
the plume management
system.
TOP
3
2
1
Total Flue length dimension
Flue
(measuring from CL of turret to outside wall)
Rear flue
Side flue
Extra packs
Boiler
dim. x+155
dim. L+197
required
size
Up to 640 mm Up to 640 mm
none
24,30 & 35
Up to 1590 mm Up to 1590 mm
Pack D - 1 off
24,30 & 35
Up to 2540 mm Up to 2540 mm
Pack D - 2 off
24,30 & 35
Up to 3490 mm Up to 3490 mm
Pack D - 3 off
24, 30 & 35
Up to 4440 mm Up to 4440 mm
Pack D - 4 off
24, 30 & 35
Up to 5390 mm Up to 5390 mm
Pack D - 5 off
24, 30 & 35
Up to 6340 mm Up to 6340 mm
Pack D - 6 off
24, 30 & 35*
Up to 7290 mm Up to 7290 mm
Pack D - 7off
24 & 30
Up to 8240 mm Up to 8240 mm
Pack D - 8 off
24 & 30**
Up to 9000 mm Up to 9000 mm
Pack D - 9 off
24
*Logic Combi 35 is capable of 6m flue only
** Logic Combi 30 is capable of 8m flue only
Total Flue length dimension
Flue
(measuring from CL of turret to outside wall)
Rear flue
Side flue
Extra packs
Boiler
dim. x+155
dim. L+197
required
size
Up to 575 mm Up to 575 mm
none
24,30 & 35
Up to 1525 mm Up to 1525 mm
Pack D - 1 off
24,30 & 35
Up to 2475 mm Up to 2475 mm
Pack D - 2 off
24,30 & 35
Up to 3425 mm Up to 3425 mm
Pack D - 3 off
24, 30 & 35
Up to 4375 mm Up to 4375 mm
Pack D - 4 off
24, 30 & 35
Up to 5325 mm Up to 5325 mm
Pack D - 5 off
24, 30 & 35
Up to 6275 mm Up to 6275 mm
Pack D - 6 off
24, 30 & 35*
Up to 7225 mm Up to 7225 mm
Pack D - 7off
24 & 30
Up to 8175 mm Up to 8175 mm
Pack D - 8 off
24 & 30**
Up to 9000 mm Up to 9000 mm
Pack D - 9 off
24
*Logic Combi 35 is capable of 6m flue only
** Logic Combi 30 is capable of 8m flue only
TELEsCOPIC FLUE