10
Ideal Logic Combi -
Installation and Servicing
GENERaL
204626-9450d
395
2.5
2.5
from case
700
43
65
57
38
Gas Inlet
39
65
Side flue
dim. A
1 BOILER DIMENsIONs, sERVICEs & CLEaRaNCEs
all dimensions in mm
The boiler connections are made on the boiler connection tails.
Refer to Frame 31.
The following minimum clearances must be maintained for
operation and servicing.
Additional space will be required for installation, depending upon
site conditions.
side and Rear Flue
a.
Provided that the flue hole is cut accurately, e.g. with a core
drill, the flue can be installed from inside the building where
Front clearance
The minimum front clearance when built in to a cupboard is 5mm
from the cupboard door but 450mm overall clearance is still
required, with the cupboard door open, to allow for servicing.
*
Bottom clearance
Bottom clearance after installation can be reduced to 5mm.
This must be obtained with an easily removable panel, to enable
the consumer to view the system pressure gauge, and to provide
the 100mm clearance required for servicing.
wall thicknesses do not exceed 600mm (24”). Where the
space into which the boiler is going to be installed is less
than the length of flue required the flue must be fitted from
the outside.
Installation from inside ONLy
b.
If a core boring tool is to be used inside the building the
space in which the boiler is to be installed must be at least
wide enough to accommodate the tool.
REaR FLUE ONLy
MIN. Top clearance required = 165 mm
sIDE FLUE ONLy
Horizontal length of flue from
Top clearance required
CL of boiler to outside wall
(MIN.) Dim. A
24
30
35
0.5 m
0.5 m
0.5 m
165 mm
1.0 m
1.0 m
1.0 m
170 mm
1.5 m
1.5 m
1.5 m
185 mm
2.0 m
2.0 m
2.0 m
200 mm
2.5 m
2.5 m
2.5 m
210 mm
3.0 m
3.0 m
3.0 m
225 mm
3.5 m
3.5 m
3.5 m
250 mm
4.0 m
4.0 m
4.0 m
260 mm
4.5 m
4.5 m
4.5 m
265 mm
5.0 m
5.0 m
5.0 m
275 mm
5.5 m
5.5 m
5.5 m
290 mm
6.0 m
6.0 m
6.0 m
300 mm
6.5 m
6.5 m
N/A
320 mm
7.0 m
7.0 m
N/A
330 mm
7.5 m
7.5 m
N/A
345 mm
8.0 m
8.0 m
N/A
360 mm
8.5m
N/A
N/A
370 mm
9.0 m
N/A
N/A
385 mm
204626-8.indd 10
25/08/2011 13:15:24
Summary of Contents for LOGIC+ Combi 24