6
mexico HE
-
Installation & Servicing
GENERAL
All dimensions
in mm (in.)
mxhe7564
450 (17
3
/
4
)
225 (8
7
/
8
)
530 (21)
690
(27
1
/
4
)
467
(18
3
/
8
)
232 (9
1
/
8
)
288 (11
5
/
16
)
348 (13
11
/
16
)
449
(17
1
/
16
)
850
(33
1
/
2
)
Gas
Gas
Flow
Return
Flow
Retur
n
1 BOILER sERVICE CONNECTIONs
1.
This appliance is NOT suitable for use
in a direct hot water system.
2.
If the boiler is to be used on a sealed
system an
Overheat Thermostat
is
fitted as standard.
2 FLOOR MOUNTINg AND BOILER CLEARANCEs
Flammable materials must not be placed in close proximity to the appliance.
Materials giving off flammable vapours must not be stored in the same room as
the appliance.
Floor mounting
1.
The floor must be flat, level and of suitable load
bearing capacity.
2.
The back of the boiler may be fitted up to the wall.
Boiler clearances
The minimum overall dimensions of the space in
which the boiler is to operate and to facilitate servicing
are as shown
Additional space may be required for installation,
depending upon site conditions.
In addition a MINIMUM clearance of 450 mm (17
3
/
4
”)
MUST be available at the front of the boiler, for
servicing.
Minimum front clearance when built behind a
concealing panel is 5mm (
1
/
4
”).
mxhe7565
All dimensions in mm (in.)
Top clearance
5
(
1
/
4
)
5
(
1
/
4
)
20
(
3
/
4
)
Boiler Flue
Overall space Dim.
Model Length Depth height Width
hE15
6m
530 870 460
hE18
6m 530 870 460
hE24
6m
530 870 460
hE30
3m
530 870 460
hE36
3m
530 870 460
INTRODUCTION
The mexico hE
range of boilers
are fully automatically controlled,
floor standing, low water content, balanced flue, fanned,
condensing gas boilers. They have full modulating central heating
outputs of :
hE15
8.8 kW (30,000 Btu/h) to 14.6 kW (50,000 Btu/h).
hE18
8.8 kW (30,000 Btu/h) to 18.2 kW (62,300 Btu/h).
hE24
8.8 kW (30,000 Btu/h) to 23.4 kW (80,000 Btu/h).
hE30
10.6 kW (36,200 Btu/h) to 30.1 kW (102,700 Btu/h).
hE36
10.6 kW (36,200 Btu/h) to 37.0 kW (126,200 Btu/h).
Due to the very high efficiency of the boiler a plume of water
vapour will form at the flue terminal during operation depending on
external conditions.
The boiler casing is of white painted mild steel with the user
controls capable of being mounted remotely from the boiler, if the
option is required.
The heat exchanger is of cast aluminium.
Artificially softened water must NOT be used.
A pre-piping frame is provided to allow system and gas
connection to be made prior to boiler installation.
Note.
These boilers cannot be used on systems which include gravity
circulation.
The boilers are suitable for connection to fully pumped, open
vented or sealed water systems. Adequate arrangements for
completely draining the system by provision of drain cocks MUST
be provided in the installation pipework.