44
xtra
-
Installation & Servicing
SERVICING
57 REMOVAL OF SUMP COVER
1.
Refer to Frame 49.
2.
Remove the jacket front and inner front
panels. (Refer to Frame 52).
3.
Remove the 6 nuts and withdraw the sump
cover plate taking care to retain the gasket.
4.
Scrape out any deposits within the sump.
5.
Re-assemble in reverse order replacing the
sump cover plate gasket if it is showing
signs of wear.
REPEAT PROCEDURE FOR SLAVE MODULE.
6.
Refer to Frame 49 for final safety checks.
3
58 CLEANING CONDENSATE TRAP
1.
Refer to Frame 49.
2.
Remove the jacket front, inner front, controls fascia, top
and side panels. (Refer to Frame 52).
3.
Place a container beneath the condensate trap to
collect the condensate contained within.
4.
Remove bottom nut/plug from the condensate trap
whilst collecting the condensate which will drain out.
5.
Withdraw the cartridge and ball from within the
condensate trap. Thoroughly clean the cartridge and
ball by flushing with water.
6.
If deposits are visible in the condensate trap body, it
can be removed by unscrewing the inlet and outlet
nuts. Thoroughly flush the body with water.
7.
Re-assemble in reverse order, replacing the
condensate trap if there are signs of wear to any seals
or the ball.
REPEAT PROCEDURE FOR SLAVE MODULE.
8.
Refer to Frame 49 for final safety checks.
4
5
6
SER
VICING