This manual contains information for dimensioning & assembly
of a Plate Heat Exchanger Package for the Evomax 2 range of
commercial boilers.
1.1 INTRODUCTION
1.2 GENERAL DESCRIPTION
This package provides the means to install an Evomax 2 boiler
complete with a plate heat exchanger and associated ancillary
items to separate the boiler hydraulically (primary) from an
existing heating / hot water system (secondary).
See appliance manuals for the flue configurations for the range
of appliances using this kit.
150 kW boilers must be flued following the Clean Air Act.
All headers and pipework should be insulated following the
Non-Domestic Building Services Compliance Guide.
Insulation thickness must be calculated according to BS EN
ISO 12241 using standardised assumptions.
This package is intended for system separation only and must
not be used for instantaneous domestic hot water generation.