Ecomod Heat Pump Control -
Installation and Servicing
8.8.3. Commissioning*
Line
no.
Programming
Possible values
7202
Heat pump commissioning
Off | Heating | Cooling
7207
Select heat pump power modulation
7214
Test funct. mode
Commissioning
the heat pump
The commissioning function allows the Ecomod heat pump to operate
in line with consumer requirements. Setting 7202 determines the
operating mode.
CAUTION: Only “heating” mode is allowed on Ecomod heat pumps.
The heat pump however only comes on if the power selection (7207)
has been made.
The commissioning function ends if a power break occurs (7202 =
Off).
The compressor does not come back on automatically if the heat
pump reaches a safety limit value during the active commissioning
process. In this case, the output selection is reset (7207 = 0%), but the
commissioning function itself (7202 = heating for example) remains
active.
The commissioning function automatically switches off after two hours
with no manual changes made to the 7202 parameter settings.
The 7207 parameters are reset to the default values after manually
aborting or disabling the commissioning function.
The parameters need to be re-entered to restart the commissioning
function.
Select heat pump
power modulation
This setting defines the power (0...100%) of a modulating heat pump
during the active commissioning sequence. The heat pump will operate
at a set power level during the active commissioning sequence.
* = restricted access leve
l