Ecomod Heat Pump Control -
Installation and Servicing
Charge regulation logic in time range:
DHW charging is carried out gradually over a defined time range.
During this time period, the DHW temperature setpoint changes continuously in order
to reach the desired final setpoint at the end of the DHW charging.
The setpoint transmitted to the Ecomod producer is adjusted respectively throughout
the charging period in order to meet the needs of the DHW setpoint.
In order to correctly define the starting point for this gradual setpoint, the Ecomod
generator is released at its minimum modulation, and the plate exchanger is released.
In this way, temperatures in the circuit are kept even for a predefined period of time.
The generator is then free to follow the appropriate modulation to meet the needs of the
set point at all times.
INFORMATION:
This operating mode is the only one authorised for the hot water
production.
DHW setpoint activation
DHW setpoint
Param. 1610
DHW sensor B3
B10 line output sensor
PAC setpoint
Param. 2926
Param. 5008
Param. 5020
Param. 5036
Time range (561-566)
Compressor
modulation
Min. modulation
DHW request