Ecomod Heat Pump Control -
Installation and Servicing
Time programme 5 K13
The relay is controlled by the settings for timer programme 5.
Compressor stage 1 K1
The relay is used to control the first stage of the compressor.
This assignment can be used to notify the HP operation request to an external regulator
(outside the defrosting cycle).
8.5.2.2. Sensor input BX*
Line no.
Programming
Possible values
BX1
BX3
BX4
5930
5932
5933
Sensor input BX1, 3, 4 None | Pool sensor B13 | Flow sensor common
B10 | Special temp. sensor 1 | Special
temp. sensor 2 | Outdoor sensor B9 | Room
thermostat B5 | Room thermostat B52 | Room
thermostat B53 |
The output settings assign the corresponding functions based on the
selection.
None
No function on the sensor input.
External sensor B9
Function not available
.
B10 line output sensor
This sensor is required for the common flow line.
Pool sensor B13
Function not available
.
Special temp. sensor 1
This sensor can be used for the temperature difference regulator general function.
Special temp. sensor 2
This sensor can be used for the temperature difference regulator general function.
Room thermostat B5
Function not available
.
Room thermostat B52
Function not available
.
Room thermostat B53
Function not available
.