Installation & Servicing
INSTALLATION
SIDE FLUE OUTLET
6.
Elbow.
7.
Side outlet plate.
8.
Flue connector.
9.
Sealing plate.
10.
Turret access cover.
LEGEND
1.
Terminal.
2.
Weather seal.
3.
Flue assembly.
4.
Boiler sealing ring.
5.
Flue extension tube (medium with ring).
18 PREPARING THE WALL
Note.
If the
terminal is to be
sited within 25-
40mm of a
corner or
vertical pipe
(refer to Table
3) then the hole
MUST be
accurately cut
and the rubber
weather seal
trimmed around
the groove
provided.
The terminal
wall plate need
not be fitted.
17 SIDE FLUE ASSEMBLY - Exploded view
For wall thickness 114mm to 600mm
1.
The boiler turret assembly is factory built for rear
flue installation.
2.
Remove the turret access cover.
3.
Remove the sealing plate from the appropriate side
to be used and refit in the rear outlet.
4.
An optional flue duct extension kit is required for lengths
(distance from the outside wall to the relevant side of the
boiler casing) greater than 600mm (23
1/2
") Refer to
Frame 7.
5.
When cutting the ducts always use the cardboard
support provided.