18
Mexico Super 100 FF & 125 FF -
Installation
26 TOP FLUE OUTLET ASSEMBLY - 100 FF ONLY - Exploded view
1.
The boiler turret assembly is factory built for rear flue
installation.
2.
Remove the turret access cover.
3.
Remove the sealing plate from the turret access cover and
refit in the rear outlet.
IMPORTANT
The maximum total equivalent horizontal flue length is 2m
for 100 FF model.
For the number of extension ducts required see Frame 36.
LEGEND
1.
Terminal.
2.
Weather seal.
3.
Flue assembly.
4.
Boiler sealing ring.
5.
Flue extension tube (short).
6.
Elbow.
7.
Flue connector.
8.
Turret access cover.
4.
Fit the outlet flue elbow pointing upwards, rotate in
the bayonet slot and secure with the M4 screw.
5.
Fit the short extension tube (with no ring) to the flue
elbow, rotate in the bayonet slot and secure with the
M4 screw.
6.
An optional flue duct extension kit is required for
lengths (distance from the outside wall to the
relevant side of the boiler casing) greater than
600mm (23
1/2
") Refer to Frame 7.
7.
When cutting the ducts always use the cardboard
support provided.
27 PREPARING THE WALL
1.
Mark onto the wall the position of the flue duct
hole.
IMPORTANT.
Ensure that, during the cutting
operation, masonry falling outside of the building
does not cause damage or personal injury.
2.
Cut the flue hole, preferably with a 125mm (5")
core boring tool, ensuring that the hole is
square to the wall. If the hole has been quite
accurately cut with a drill then making good the
wall faces is not essential as seals are provided
at both ends of the flue. However, both wall
faces immediately around the cut hole should
be flat; make good if necessary. For less
accurate holes make good to approximately
125mm (5") diameter at the 2 wall faces.
Note.
If the
terminal is to be
sited within 25-
40mm of a
corner or
vertical pipe
(refer to Table 3)
then the hole
MUST be
accurately cut
and the rubber
weather seal
trimmed around
the groove
provided.
The terminal
wall plate need
not be fitted.
INSTALLATION
T
OP FLUE OUTLET