34
Mexico Super 100 FF & 125 FF -
Installation
SERVICING
67 CONTROLS PANEL REPLACEMENT
1.
Remove the 2 screws and lift off the
lower front panel. Refer to Frame 57.
2.
Pull off the thermostat knob.
3.
Disconnect the in-line electrical
connector between the control box
and PCB box.
4.
Unscrew the 2 screws and pull down
the control panel so that the 2 tabs
clear the top panel.
5.
Remove the thermostat phial from
the pocket. Refer to Frame 57.
6.
Remove the bottom screw and
remove the cover from the control
box.
7.
Remove the top screw and ease the
control box off the control panel.
8.
Disconnect the mains electrical
supply from the terminal strip and
release from its clamp.
9.
Assemble new control box and
panel and fit to the casing in reverse
order.
10.
Insert control thermostat phial into
pocket and secure with the split pin.
11.
Refit the in-line electrical connector between the control
box and the PCB box.
12.
Remove control box cover and make electrical supply
connections to the terminal strip. Refer to Frame 46.
1.
Remove the 2 screws and lift off the lower front
panel. Refer to Frame 57.
2.
Slacken the screw at the thermostat pocket and
withdraw the phial from the pocket.
3.
Remove the thermostat retaining nut and withdraw
the thermostat from the control panel.
4.
Transfer the electrical leads from the old
thermostat to the replacement (polarity is not
important).
5.
Fit the new thermostat ensuring that the alignment
peg on the thermostat sits in the small hole
adjacent to the main fixing hole and reassemble in
reverse order.
6.
Replace the lower front panel and secure with the
2 fixing screws.
7.
Check the operation of the boiler.
68 OVERHEAT THERMOSTAT REPLACEMENT (if fitted)
13.
Replace the lower front panel and secure with
the 2 fixing screws.
14.
Check the operation of the boiler.
SER
VICING