21
Mexico Super 100 FF & 125 FF -
Installation
36 FLUE EXTENSION DUCTS - continued
FLUE KITS
Pack B:
supplied as standard.
Pack D:
optional extension kit for side flue, top or rear flue outlet. Refer to Frame 35.
1.
A maximum of 2 extension ducts (plus the standard flue duct) may be used together.
2.
Flue extensions of greater than 1m (39") should be supported with the bracket
provided.
35 FLUE EXTENSION DUCTS
Flue length mm
100 FF Pack Req.
125 FF Pack Req.
Product No.
Up to 600
B, 1 off
B, 1 off
152 227
600 to 1000
B, 1 off + D, 1 off
B, 1 off + D, 1 off
152132
600 to 1550
B, 1 off + D, 1 off
N/A
152 227+
152132, 1 off
1550 to 2000
B, 1 off + D, 2 off
N/A
152 227+
152132, 2 off
INSTALLATION
T
OP REAR & SIDE FLUE OUTLET
Top outlet flue length
= A + B + Elbow allowance
90
o
Elbow = 1m
45
o
Elbow = 0.7m
37 FITTING THE KIT
1.
Remove the cardboard support aid from the flue and
place safely to one side.
2.
Fit the inner flue extension duct onto the inner flue duct.
3.
Fit the outer flue extension duct onto the outer air duct.
4.
Drill 3 - 3.2mm (
1/8
") dia. holes through the outer air duct.
Do not drill the inner flue
duct.
5.
Insert the self tapping screws provided to fix the air duct in
position.
6.
Repeat steps 1-5 if a second flue extension is required.