15
BOXER
combination boiler -
Installation and Servicing
INSTALLATION
FLUE OUTLET
15 PREPARING THE WALL
WARNING.
Ensure that, during the cutting operation,
masonry falling outside of the building does not
cause damage or personal injury.
1.
Cut the flue hole (preferably with a 5" core boring
tool), ensuring that the hole is square to the wall.
Both wall faces immediately around the cut hole
should be flat.
2.
Drill 2 holes (see frame 14) with a 12 mm (1/2")
masonry drill and insert the plastic plugs
complete with hook screws, provided, for the
upper boiler bracket.
or
Drill 4 holes (see frame 14) with a 12 mm (1/2")
masonry drill for the stand-off kit.
16 CUTTING THE FLUE - REAR
Wall thicknesses of 114 to 620 mm
Note.
a.
If using the extension ducts go to Frame 20.
b.
If the upward routing pipe stand-off kit is used it is
essential add 50 mm to 'X' the measured wall
thickness when marking the flue (this will allow for the
fitted stand-off kit).
1.
Measure and note wall thickness X - Refer to Frame 12
2.
Add 90 mm (3 9/16) to dimension X and, measuring
from the groove, cut the outer tube only.
3.
To ensure the tube is cut square, mark the flue all the
way round.
4.
Cut the inner tube to a length 20 mm (3/4") longer to
aid engagement.
17 CUTTING THE FLUE - SIDE
Wall thicknesses of 114 to 580 mm
Note.
If using the extension ducts go to Frame 20.
1.
Measure and note wall thickness X - Refer to Frame 12
2.
Add 130 mm (5 1/8") to dimension X and, measuring
from the groove, cut the outer tube only.
3.
To ensure the tube is cut square, mark the flue all the
way round.
4.
Cut the inner tube to a length 20 mm (3/4") longer to
aid engagement.
Note.
If the terminal is to be sited within 25-40 mm of a corner or vertical
pipe then the hole MUST be accurately cut.
Rear flue
only 5
diameter
hole
Side flue
only 5
diameter
hole
Note:
Check all of the hole
positions before drilling.
Section
through
wall
X
With
stand-off kit
Without
stand-off kit
0HD
VXUH
0HDVXUHIURP
*5229(
PP
0HD
VXUH
0HDVXUHIURP
*5229(
PP
With
stand-off kit