CRX-POSTX-DIN 

DIN Rail PostX IP Reporting Module 

Installation Manual | June 2017   

11

 

 

4

 

DC Power 

Module power is supplied by the N+ and N- terminals. 

NA

N+

N-

NB

DC Power input 
from 12 VDC Input

 

Standard DC Power Connection 

Connection of the DC supply should be performed according to the diagram shown above. It is important that 
the N+ module power be 12VDC supplied from an independent battery backed power supply unit such as the 
PRT-PSU-DIN capable of supplying the required voltage. 

 

 

Warning: 

 

The 12V N+ and N- DC power input must be supplied from only ONE point. Connections from 
more than one 12V supply may cause failure or damage to the PostX module. 

 

 

The 330 Ohm EOL (End of Line) resistor provided in the accessory bag MUST be inserted 
between the NA and NB terminals of the ACC-485 module directly connected to the PostX 
module..  

 

330R

NA

N+

N-

NB

NA

N+

N-

NB

CRX-POSTX-DIN

ACC-485

 

End of Line Resistor 

 

Summary of Contents for CRX-POSTX-DIN

Page 1: ...CRX POSTX DIN DIN Rail PostX IP Reporting Module Installation Manual...

Page 2: ...reproduced photocopied or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Integrated Control Technology Limited Designed and...

Page 3: ..._____________________ 12 5 1 Panel Interface 12 5 2 Telephone Dialler Interface 12 5 3 Ethernet 10 100 Network Interface 13 5 4 GPRS Interface 14 5 5 WiFi Interface 14 6 Interface Configuration ______...

Page 4: ...__ 36 10 1 Setup 36 10 2 Access Levels 36 10 3 Default Users 36 11 IP Troubleshooting _______________________________________________________ 37 11 1 Default Static IP Address Mode 37 11 2 DHCP IP Add...

Page 5: ...______________ 51 20 UL and ULC Installation Requirements ______________________________________ 52 20 1 UL ULC Installation Cabinet Options 52 20 2 Central Station Signal Receiver Compatibility List...

Page 6: ...92 or 256 bit AES encryption Fully configurable through an Internet browser Backup reporting options 64 message queue Industry standard DIN Rail mounting Online and remote upgradeable firmware For mor...

Page 7: ...pendently allowing you to select from Ethernet PSTN WiFi or GPRS according to the module used Communication Interface Ethernet PSTN WiFi GPRS CRX POSTX DIN PostX DIN Rail IP Reporting Module CRX POST...

Page 8: ...dup Systems UL 827 Central Station Alarm Services CAN ULC S301 Central and Monitoring Station Burglar Alarm Systems CAN ULC S302 Installation and Classification of Burglar Alarm Systems for Financial...

Page 9: ...is recommended to install the PostX Module in a location that will facilitate easy access for wiring It is also recommended that the PostX Module is installed in electrical rooms communication equipme...

Page 10: ...to activate if a communication channel fails or in response to an SMS message They can be used to activate bell sirens lighting circuits door locks relay accessory products and other automation points...

Page 11: ...2VDC supplied from an independent battery backed power supply unit such as the PRT PSU DIN capable of supplying the required voltage Warning The 12V N and N DC power input must be supplied from only O...

Page 12: ...ne interface from existing panel Wiring Interface to Existing Alarm Panel Warning NEVER connect the phone line emulator terminals Rpi and Tpi to a normal phone line This will cause permanent damage to...

Page 13: ...ion Default Static IP Address Mode see page 37 for details When installing an Ethernet connection the PostX Module should be interfaced using a standard segment 100M in length and should be connected...

Page 14: ...ntenna must be installed outside the DIN Rail cabinet V 12VDCOUT RELAY2 V NO C NC NO C NC GPRS Antenna Cabinet RELAY1 GPRS Antenna connection 5 5 WiFi Interface i This information only applies to the...

Page 15: ...e PostX Module will be 192 168 1 2 The suggested methods for connecting your PC or laptop to the PostX Module include via either a switch hub or a direct connection as shown in the section Ethernet 10...

Page 16: ...the web interface is displayed correctly it may be necessary to enable compatibility mode in your web browser To turn on compatibility view go to the Tools menu and choose Compatibility View settings...

Page 17: ...tX IP Reporting Module Installation Manual June 2017 17 7 2 Routing Setup To configure the routing options select the Routing Setup link using the web interface The following shows an example configur...

Page 18: ...field supports a maximum of 256 characters for each channel The reporting sequence is on a module base meaning that an event will be reported once on only one channel the first that succeeds All nece...

Page 19: ...mbers and does not form a known word The encryption key is case sensitive ArmorIP E TCP This format is identical to ArmorIP E UDP except it uses TCP as the transport layer Contact ID UDP This format i...

Page 20: ...ual poll message and therefore cannot be changed programmed All other IP formats can have customized poll messages Test Report A test report is a signal sent to the monitoring station validating the o...

Page 21: ...the PostX Module when using 22 AWG wire Each zone input may be individually configured for normally opened or normally closed configurations with or without EOL resistors for tamper and short conditio...

Page 22: ...Contact ID event code to indicate the type of event that is being reported The following table shows some example event codes that may be used It is recommended that you always consult your monitoring...

Page 23: ...For the settings shown above when the input opens the following email will be sent by the PostX Module Site Name ICT PostX Module Zone Message Zone 1 Opened Time Stamp Wed Feb 17 13 00 26 2013 SMS Mes...

Page 24: ...ther automation points through SMS messages i In order to enter any of the IP troubleshooting modes Relay 1 on the PostX Module will enable briefly on startup To prevent this from occurring ensure tha...

Page 25: ...ff for the period of time set before turning on again for the On Time Configuring both the On and Off Time creates a pulsed output The On Time can be configured with a value ranging from 0 255 seconds...

Page 26: ...t with validate by any no acknowledge and the command gate This pin code has been set to house SMS Message Action house garage on ack PGM 1 turned on and acknowledge SMS sent house garage off a PGM 1...

Page 27: ...ill be sent is selectable Ethernet is available on all variants of the PostX The others depend on the model WiFi will be available on the WF variants while the GPRS IP on the GP variant The IP address...

Page 28: ...elp ensure your PostX Module cannot be configured by invalid users change the default passwords for the web interface before commissioning the installation There are two options for configuring the IP...

Page 29: ...1 3 with a subnet mask of 255 255 255 0 for the WiFi interface If your computer network is on this subnet and no other computer on the network uses this IP address you will be able to connect to the...

Page 30: ...twork interface to use the following settings IP Address 192 168 1 4 192 168 1 254 Subnet Mask 255 255 255 0 Please select the IP address for your PC or laptop from the range given above ensuring it i...

Page 31: ...cters Contact your local network provider for assistance with the information required Should anything go wrong while using the GPRS interface an error code is displayed on the Events page 7 8 PSTN Co...

Page 32: ...32 CRX POSTX DIN DIN Rail PostX IP Reporting Module Installation Manual June 2017 8 Advanced Configuration...

Page 33: ...Connection Timeout The IP Connection Timeout is the number of seconds the PostX Module waits for a response for an IP message Log Poll Events Log the send poll and received ACK poll events Disabling t...

Page 34: ...rough This feature is only available from hardware revision 040 and later of the PostX Module PSTN Pass Through gives you the ability to temporarily connect the security control panel directly to the...

Page 35: ...Accessories Command Prompt and type in the following command using the IP address of the PostX Module tftp i 192 168 1 2 GET config bin This will create a file called config bin in the same directory...

Page 36: ...user again select the appropriate checkbox and click Edit This will bring you back to the edit user s settings page From there simply set the access level to none then click Save i To ensure the secu...

Page 37: ...168 1 2 and a subnet mask of 255 255 255 0 complete the following steps 1 Connect the terminals for Zone 1 and NO of Relay 1 together Repeat the procedure for the V and C terminals as shown in the di...

Page 38: ...he following instructions detail how to ping a device 1 Open a command prompt Click Start Run then type cmd into this window and click OK 2 Type ping 192 168 1 2 into the command prompt and press ENTE...

Page 39: ...into the command prompt and press ENTER 3 Wait for the command prompt to respond The command prompt ICTNET will come up when a connection has been established To terminate the telnet session type exi...

Page 40: ...PRS module gprs set apn gprs set apn internet com Sets the APN parameter of the GPRS module gprs set user gprs set user wapuser1 Sets the user name parameter of the GPRS module gprs set password gprs...

Page 41: ...configuration system system Displays the system details including serial number and software version time time Displays the current time stored in the PostX wifi default wifi default Resets the WIFI...

Page 42: ...ower indicator is lit whenever the correct module input voltage is applied across the N and N terminals State Description On green Correct module input voltage applied Off Incorrect module input volta...

Page 43: ...iber phone State Description On Subscriber phone is off hook Off Subscriber phone is not active 13 6 Ethernet Indicator The Ethernet indicator will show the status of the Ethernet connection State Des...

Page 44: ...is in a TAMPER state 13 9 WiFi Indicator i This information only applies to the PostX modules that support GPRS and or WIFI communication The WiFi indicator shows the status of the WiFi connection and...

Page 45: ...rength State Description Wave constantly on Connection available Wave flashing Communication data transfer GPRS constantly on 1 bar red Connection not established GPRS constantly on All bars off Conne...

Page 46: ...entification sticker contains details that may be of use to you such as the MAC address of the PostX Module An example of the identification sticker is shown in the diagram below Din Rail PostX IP Mod...

Page 47: ...t test calls at pre determined times Such test calls will interrupt any other calls that may be set up on the line at the same time The timing set for such test calls should be discussed with the inst...

Page 48: ...below outlines the essential details needed to help ensure the correct installation of the PostX Module LED Indicators Signal Indicators 12VDC Pass Through Zones 1 to 4 12VDC Input External Modem Inte...

Page 49: ...Manual June 2017 49 17 Mechanical Layout The mechanical layout shown below outlines the essential details needed to help ensure the correct installation of the PostX Module 156 8mm 143 5mm 36 4mm 90m...

Page 50: ...12VDC 10 Operating Current 110mA Typical 220mA Peak Panel Off Hook Low Voltage Cutout 8 7VDC Low Voltage Restore 10 5VDC Communication RS 485 RS485 Menu Interface Ethernet 10 100 Auto Negotiation Ful...

Page 51: ...IP Reporting Module Installation Manual June 2017 51 19 New Zealand and Australia General Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies...

Page 52: ...CAN ULC S319 All cabinet internal covers and lid doors must be connected to the cabinets main ground point for electrical safety and static discharge protection 20 2 Central Station Signal Receiver C...

Page 53: ...nual 227 1500 000 Central Station Signal Receiver The common equipment of each signal receiving center control unit shall be limited to 1000 alarm systems Number of attempts In the event of unsuccessf...

Page 54: ...tions channel security encryption shall be enabled at all times The ArmorIP E UDP protocol must be used and the Encryption Type must be set to AES 256 The following options must be enabled for the the...

Page 55: ...is used to connect to line voltage strain relief must be provided for the cord inside the enclosure or at the knockout The Power Supply is not intended to be mounted on the exterior of vault safe or...

Page 56: ...the failure shall be made at the premises In the Protege System the reporting service selected as Contact ID must have the number of attempts programmed to 5 attempts The Dialing Attempts option must...

Page 57: ...cannot be programmed to activate the bell output EOL resistor must be installed at the Fire Alarm Control Panel Output RELAY 1 or 2 Dry Contacts Typical Zone Circuits Value 1 Value 2 Monitored Status...

Page 58: ...5 The AC FAIL output on the Power Supply MUST be programmed to follow the AC Trouble Input as follows AC FAIL OPEN on fail DIALER PSTN TELECOM EQUIPMENT Fire Zone Inputs and Outputs Fire Zone inputs m...

Page 59: ...e section Report IP in the Protege GX Operator Reference Manual 227 1500 000 When more than one means of signal transmission is used loss of communication with the receiving system shall be annunciate...

Page 60: ...Internet Monitoring Application User s Manual 227 5500 000 For UL and ULC installations the Central Station Receiving software must have the Contact ID details as specified programmed for the Compromi...

Page 61: ...nal visibility This shall be wired between 12V and a PGM output that is programmed to follow the AC trouble input as shown below BZ L1 D1 DO LED V V Z4 V Z3 Z2 V Z1 1K5 OHM READER 1 ZONE INPUT 1 4 12V...

Page 62: ...the party responsible for compliance could void the user s authority to operate this product This device complies with Part 15 of the FCC rules Operation is subject to the following two conditions Th...

Page 63: ...advance notice in order for you to make necessary modifications to maintain uninterrupted service Equipment Maintenance Facility If trouble is experienced with this equipment CRX POSTX DIN for repair...

Page 64: ...ay consist of any combination of devices subject only to the requirement that the sum of the RENs of all the devices does not exceed five L indice d quivalence de la sonnerie IES du pr sent mat riel e...

Page 65: ...se the following product codes when placing an order for the DIN Rail PostX IP Reporting Module CRX POSTX DIN CRX POSTX DIN WF with WIFI interface CRX POSTX DIN GP with GPRS interface CRX POSTX DIN WF...

Page 66: ...ct the products and because the products may be used in conjunction with products not manufactured by ICT ICT cannot guarantee the performance of the security system ICT s obligation and liability und...

Page 67: ...on below Integrated Control Technology P O Box 302 340 North Harbour Post Centre Auckland New Zealand 4 John Glenn Ave Rosedale North Shore City 0632 Auckland New Zealand Phone 64 9 476 7124 Toll Free...

Page 68: ...4 Designers manufacturers of integrated electronic access control security and automation products Designed manufactured by Integrated Control Technology Ltd Copyright Integrated Control Technology Li...

Reviews: