22 

 

 

 

 

 

 

 

 

 

 

 

 

Rev: 05-15/12 

  

 

‘Automatic adjustment’ (Autotuning) function

 

The control panel features a programme that automatically finds the optimum PID settings for the connected load. 
For this programme to work, it is important that the regulator is ready for operation, the load is connected and that a 
non-critical temperature set value has already been set. In the ‘Loc’ menu (page 20), the value 0 must be set.

 

 

When in autotuning mode, the regulator moves through one or more control cycles so that it can establish the 
parameters. This can result in considerable deviations from the set value. Bear this in mind when specifying 
the set value. In consideration of this, it should be as close as possible to the actual control value. 

 

 

During normal operation when a load is connected, press the button              

for about 4 seconds. 

In the SV display, the set value flashes in alternation with - AT -.

 

The procedure is complete once SV has 

automatically returned to normal display.

 

In order to cancel autotuning, press the button again for about 4 

seconds, until SV stops flashing. The 

previous settings are not changed. 

 

Alarm output configuration:

 

As well as an SSR output, the TR-81 also features an alarm output (terminals 8, 7, 6), which can be provided with its 
own set value (Menu B, parameter AL1T) as well as its own hysteresis (Menu B, parameter DFAL). When making 
any such settings, refer to the information provided in menu table B, under parameter point ALT1. 
If, when the regulator is switched on, an undesired alarm is emitted (when the set value at the time of switching on 
corresponds to the alarm value), this can be prevented by the HJB setting (if the alarm range is higher than the set 
value) or the LJB setting (if the alarm range is below the set value). Both these settings can be found in menu AL1T. 
These settings enable the alarm to be temporarily bypassed after the control voltage has been switched on. 
 

 

Maintenance and customer service:

 

In normal operation, the TR-81 regulator does not require maintenance. Excessive dust deposits should however be 
avoided. Use in wet rooms is only permitted with the approved housing with protective cover (part no Z-45-
KsKap45x45). Electronic components must be protected against condensation moisture. 
Dirt on the front and on the housing can be removed with a slightly moistened cloth when the regulator is switched 
off. 

 
Error code: 

 

HHHH

 

Measurement signal is above the expected range! 

 

 

If displayed after sensor installation: Wrong sensor type set in the ‘Sn’ parameter (Menu table B).  

 

 

Temperature measured is outside the upper and lower set value range (‘inPL’ and ‘inPH’, page 21). 

 

 

Load is switched off. 

LLLL

 

Measurement signal is below the expected range! 

 

 

If displayed after sensor installation: Wrong sensor type set in the ‘Sn’ parameter (Menu table B).  

 

 

Temperature measured is outside the upper and lower set value range (‘inPL’ and ‘inPH’, page 21). 

 

 

Load is switched off.

 

 

We reserve the right to amend the technical specifications. 

 

 

 

 

Summary of Contents for PPS 1210

Page 1: ...instruction high pressure calibrator PPS 1210 L ICS Schneider Messtechnik GmbH Briesestra e 59 D 16562 Hohen Neuendorf OT Bergfelde Tel 03303 504066 Fax 03303 504068 info ics schneider de www ics sch...

Page 2: ...1 Description of the device 4 2 General safety warnings 4 3 Operating the calibrator 5 4 Description of the functions 5 5 Menu navigation for calibrators 6 6 Commissioning 6 7 Maintenance disposal 7 8...

Page 3: ...ealing plug 8 Manual booster pump 9 Pressure connection for test object only PPS1110 10 Drain valve 11 Screw compressor Additional components of High Pressure Calibrator PPS 1210 12 Heatable pressure...

Page 4: ...IMPORTANT Nothing must adhere to the surface of the test object no oil grease water etc Impurities could pass trough the adapter to reach the high pressure calibrator and damage it Overpressure If th...

Page 5: ...each the desired pressure please consult the section on Maintenance to find out how to vent the system Zeroing the device Open the drain valve 10 to release any pressure that may have built up If the...

Page 6: ...6...

Page 7: ...ssure change Set leak measurement time The leak measurement time is preset to 10 minutes in the factory and it can only be changed with the Mano Con fig software Software for calibrators MANO Continuo...

Page 8: ...15 L 17 L 19 L 21 and L 23 are completed The candidate s 100 bar range is entered in the cell L 11 printing area The cells L 11 L 15 L 23 and P 31 are obligatory fields The result of the measurement...

Page 9: ...LP 22 BP or olive oil Pressure port 1 2 20UNF or M18x1 5 Media compatibility Pressure transducer with stainless steel diaphragm Dimensions L x W x H 470 x 170 x 280 mm Weight approx 7 2kg Degree of pr...

Page 10: ...Konformit tserkl rung Declaration of Conformity D claration de Conformit 10...

Page 11: ...al use thanks to the many important customisation options it offers These include useful additional functions such as sensor break detection with automatic power cutoff alarm output maximum or minimum...

Page 12: ...ity in Resolution 0 1 C Display resolution is customisable non aggressive environment Closed circuit current 3W Control Display elements Status message display 1 4 4 RTD The display then changes to op...

Page 13: ...OFF regulation is that the temperature fluctuates in the range around the set value due to the hysteresis that was specified and the sluggishness of individual process components heater follow up time...

Page 14: ...0 changes in menu A and autotuning are permitted LOC 0 Changes in Menu A are not permitted exception parameters LOC 508 Call up and changes to menu B are permitted After leaving Menu B Loc jumps back...

Page 15: ...temperature value is added to both ascending and descending temperature slopes This therefore doubles the total hysteresis switching gap Example of a heating control system on output relay terminal 1...

Page 16: ...nformation provided in menu table B under parameter point ALT1 If when the regulator is switched on an undesired alarm is emitted when the set value at the time of switching on corresponds to the alar...

Reviews: