Using the menus: 

The temperature regulator is operated via two menus (A and B). Menu A contains the settings for the set 
value (see also page 19: ‘Changing the set value and alarm temperature’). These settings are easily 
accessible to any operator by simply pressing the button to call them up. Repeated pressing of the button

 

moves to the next menu item.

 

The parameters in menu B are settings for configuration of the regulator, along with other advanced 
parameters. As a rule, these are not operating functions. Access to menu B is therefore password protected, 
by calling up ‘Loc’ and entering the password 508 (see next page). 
The ‘Loc’ menu also provides you with the option to prevent the set value (menu A) being changed, should 
you wish that operators are not permitted to change it. To do so, set a value other than 0 (not 508). 
 

 

consec. 

No. 

parameter 

code 

p a r a m e t e r   n a m e  

a d j u s t me n t   r a n g e  

d e s c r i p t i o n

 

Menu A

 

1

 

SU 

s e t   v a l u e   s e t t i n g  

(SU) 

INPL to IN PH

 

switches output terminal

 

1, 2 (relay contact potential-free)

 

2

 

AL I 

alarm value setting

 

( AL1) 

INPL to IN PH

 

switches output terminal

 

8, 7, 6 (changeover contact potential-free)

 

3

 

 
 

Loc 

password-protected 

menu access

 

LOC 

0~9999

 

LOC=0, 

changes in menu A and autotuning are permitted;

 

LO

C

=0, 

Changes  in  Menu  A  are  not  permitted  (exception:  parameters

); 

LOC=508, 

Call-up and changes to menu B are  permitted. After leaving  Menu B, 

‘Loc’ jumps back to the value that was originally set.

 

 

 

Making changes in the ‘Advanced parameters’ menu

:

 

When the regulator is switched on:

 

 

Press the button

 

SET

 3x kurz hintereinander. 

‘Loc’ appears on the PV display, and the last figure on the SV display flashes (active).)

 

Use the arrow keys                             

to enter the password 508 and then confirm it with. 

SET 

.  

 

The PV display now shows the first parameter code Sn. In the SV display, the value that has been set flashes (active).

 

Change the value by pressing the buttons  

according to the table, then press 

 

SET

 again to call up the next parameter. 

 
Confirm you have finished making parameter settings by pressing and holding down the 

SET

 button for about 3 seconds. 

Customisation is now complete, and the regulator now once again shows the temperature in the PV display and the set 
value in the SV display.  
After about 30 seconds of inactivity, the parameter settings display returns to normal operating mode. 
 Customisation is now complete, and the regulator now once again shows the temperature in the PV display and the set 
value in the SV display.  
After about 30 seconds of inactivity, the parameter settings display returns to normal operating mode. 

 

 

  > 

 

>

 

 

>

 

Summary of Contents for PPS 1210

Page 1: ...instruction high pressure calibrator PPS 1210 L ICS Schneider Messtechnik GmbH Briesestra e 59 D 16562 Hohen Neuendorf OT Bergfelde Tel 03303 504066 Fax 03303 504068 info ics schneider de www ics sch...

Page 2: ...1 Description of the device 4 2 General safety warnings 4 3 Operating the calibrator 5 4 Description of the functions 5 5 Menu navigation for calibrators 6 6 Commissioning 6 7 Maintenance disposal 7 8...

Page 3: ...ealing plug 8 Manual booster pump 9 Pressure connection for test object only PPS1110 10 Drain valve 11 Screw compressor Additional components of High Pressure Calibrator PPS 1210 12 Heatable pressure...

Page 4: ...IMPORTANT Nothing must adhere to the surface of the test object no oil grease water etc Impurities could pass trough the adapter to reach the high pressure calibrator and damage it Overpressure If th...

Page 5: ...each the desired pressure please consult the section on Maintenance to find out how to vent the system Zeroing the device Open the drain valve 10 to release any pressure that may have built up If the...

Page 6: ...6...

Page 7: ...ssure change Set leak measurement time The leak measurement time is preset to 10 minutes in the factory and it can only be changed with the Mano Con fig software Software for calibrators MANO Continuo...

Page 8: ...15 L 17 L 19 L 21 and L 23 are completed The candidate s 100 bar range is entered in the cell L 11 printing area The cells L 11 L 15 L 23 and P 31 are obligatory fields The result of the measurement...

Page 9: ...LP 22 BP or olive oil Pressure port 1 2 20UNF or M18x1 5 Media compatibility Pressure transducer with stainless steel diaphragm Dimensions L x W x H 470 x 170 x 280 mm Weight approx 7 2kg Degree of pr...

Page 10: ...Konformit tserkl rung Declaration of Conformity D claration de Conformit 10...

Page 11: ...al use thanks to the many important customisation options it offers These include useful additional functions such as sensor break detection with automatic power cutoff alarm output maximum or minimum...

Page 12: ...ity in Resolution 0 1 C Display resolution is customisable non aggressive environment Closed circuit current 3W Control Display elements Status message display 1 4 4 RTD The display then changes to op...

Page 13: ...OFF regulation is that the temperature fluctuates in the range around the set value due to the hysteresis that was specified and the sluggishness of individual process components heater follow up time...

Page 14: ...0 changes in menu A and autotuning are permitted LOC 0 Changes in Menu A are not permitted exception parameters LOC 508 Call up and changes to menu B are permitted After leaving Menu B Loc jumps back...

Page 15: ...temperature value is added to both ascending and descending temperature slopes This therefore doubles the total hysteresis switching gap Example of a heating control system on output relay terminal 1...

Page 16: ...nformation provided in menu table B under parameter point ALT1 If when the regulator is switched on an undesired alarm is emitted when the set value at the time of switching on corresponds to the alar...