5. Setting up the device
24
Menu level
Parameterisation level
Overflow behaviour,
O.FLoU:
Default:
edge
To recognise and evaluate faulty signals, e.g. by a controller, the overflow behaviour of the
analog output can be defined. As overflow can be seen either
EdGE
, that means the analog
output runs on the set limits e.g. 4 and 20 mA, or
to.OFF
(input value smaller than initial value,
analog output switches on e.g. 4 mA),
to.End
(higher than final value, analog output switchess
on e.g. 20 mA). If
to.MIn
or
to.MAX
is set, the analog output switches onto the smallest or highest
possible binary value. This means that values of e.g. 0 mA, 0 VDC or values higher than 20 mA
or 10 VDC can be reached. With
[P]
the selection is confirmed and the device changes into
menu level.
Back to menu group level,
rEt
:
With
[P]
the selection is confirmed and the device changes into menu group level
„–out–“
.
Menu group level
Analog output parameters 2
Menu level
Parameterisation level
Selection reference analog output,
Ou2.Pt:
Default:
actua
The analog output signal can refer to different functions, in detail this are the current
measurand, min-value, max-value, totaliser/sum-function, the sliding average value, the
constant value or the difference between the current measurand and the constant value. If
HoLd
is selected the signal of the analog output will be hold and processed just after deactivation of
HOLD
. With
[P]
the selection is confirmed and the device changes into menu level.
Selection analog output,
Ou2.rA:
Default:
4-20
There are 3 output signals availabe: 0-10 VDC, 0-20 mA and 4-20 mA. With this function the
demanded signal can be selected.
Menu level