8
Menu level
Parameterisation level
Selection of the input signal,
TYPE:
Default:
frequ
If the scaling of the device is done via
SEnS.F
(Sensor calibration), the frequency range needs to
be preset under
rAnGE
and is adjusted by application of the final value/initial value. If
FrEqU
(Factory calibration) is preferred, the final value needs to be entered under
End
and the final
frequency needs to be entered under
EndA
. Under
OFFS
the initial value needs to be entered and
under
OFFSA
the initial frequency. There is no application of the measuring signal.
Rotar
is the
rotation in r.p.m. up to 10 kHz input frequency.
Posit
is the position recognition per incremental
encoder. Confirm the selection with
[P]
and the display switches back to menu level.
Adjustment of pulses per rotation,
ppr
:
Default:
1
This parameter is only important if
type
=
rotar
or =
Posit
have been selected. Generally it
shows the number of pulses per rotation.
Setting the frequency range,
range
:
Default:
100e3
Choose between six different frequency ranges. Confirm the selection with
[P]
and the display
switches back to menu level.
5.1. Switching-on
Once the installation is complete, start the device by applying the voltage supply. Before, check
once again that all electrical connections are correct.
Starting sequence
For 1 second during the switching-on process, the segment test (
8 8 8 8 8
) is displayed, followed by
an indication of the software type and, after that, also for 1 second, the software version. After the
starting sequence, the device switches to operation/display mode.
5.2. Standard parameterisation:
(flat operation level)
To parameterize the display, press the
[P]-key
in operating mode for 1 second. The display then
changes to the menu level with the first menu item
TYPE
.
5. Setting up the device
5. Setting up the device
9.9999 Hz
99.999 Hz
999.99 Hz
9.9999 kHz
99.999 kHz
999.99 kHz