410A Ductless Split System: DLF4(A/H), DLC4(A/H)
421 08 9204 00
71
(2) IPM protection, desynchronizing malfunction, phase current of compressor is overcurrent (outdoor unit malfunction)
Outdoor unit malfunction indicator status
Malfunction
D5
D6
D16
D30
IPM protection
Desynchronizing
malfunction
Compressor
overcurrent
Detection:
If control board AP1 and compressor COMP are well
connected? If they are loose? If the connection se-
quence is correct?
Is voltage input in the normal range (Test the voltage
between L, N of wiring board XT by DC voltage meter)?
If coil resistance of compressor is normal?
If the work load of unit is heavy? If the refrigerant char-
ging is appropriate?
Malfunction diagnosis process: