SERVICE MANUAL
R
−
410A Ductless Split System: DLF4(A/H), DLC4(A/H)
22
421 08 9204 00
CLEARANCES
Distance to Ceiling
6” (152 mm)
Distance to Wall
6” (152 mm)
Distance to Floor
66” (1676 mm)
Distance to Wall
6” (152 mm)
Clearance in front of unit
118” (2997 mm)
Distance to
Back Wall
12” (305 mm)
Air Discharge Side
79” (2007 mm)
Above Unit
20” (508 mm)
Air Inlet Side
12” (305 mm)
Distance to Wall
20” (508 mm)
Valve Cover
Indoor Unit
Outdoor Unit
The clearance dimensions are necessary for a correct installation,
and are the minimum permissible distances to adjacent structures.
NOTE: Refrigerant lines
may be routed in any of
the (4) directions, right,
right rear, left, or left rear.
See instructions for de
tails.
A07891
Figure 2
-
Unit clearance