PRODUCT SPECIFICATIONS (Cont.)
Model
−
Outdoor Unit
DLC4AV24K1A
DLC4HV24K1A
Compressor
Manufacturer
Mitsubishi
Mitsubishi
Model
SNB150FGAMC
SNB150FGAMC
Oil
FV50S
−
PVE
FV50S
−
PVE
Type
Rotary
Rotary
L.R.A.
A
18.5
18.5
R.L.A.
A
4.9
4.9
Power Input
W
1420
1420
Overload Protector
INT11L
−
6578
INT11L
−
6578
Throttling Method
Electronic Expansion Valve
Electronic Expansion Valve
Set Temperature Range
°
F
61
~
86
61
~
86
Cooling Operation Ambient Temperature Range
°
F
5
~
109.0
5
~
109.0
Heating Operation Ambient Temperature Range
°
F
N/A
19.4
−
75.0
Condenser
Form
Aluminum Fin
−
copper Tube
Aluminum Fin
−
copper Tube
Pipe Diameter
inch
f
0.27
f
0.27
Rows
−
Fin Gap
inch
2
−
0.05
2
−
0.05
Coil Length (LxDxW)
inch
38x1.5x29
38x1.5x29
Fan Motor
Speed
rpm
800
800
Output of Fan Motor
W
90
90
R.L.A.
A
1.1
1.1
Capacitor
m
F
4
4
Air Flow Volume of Outdoor Unit
CFM
2354
2354
Fan
Type
Axial Flow
Axial Flow
Diameter
inch
21.732
21.732
Defrosting Method
N/A
N/A
Climate Type
T1
T1
Isolation
I
I
Moisture Protection
IP24
IP24
Permissible Excessive Operating Pressure for the
Discharge Side
Mpa
4.3
4.3
Permissible Excessive Operating Pressure for the
Suction Side
Mpa
2.5
2.5
Sound Pressure Level (H/M/L)
DB (A)
56/
−
/
−
56/
−
/
−
Sound Power Level (H/M/L)
DB (A)
66/
−
/
−
66/
−
/
−
Dimensions (WxHxD)
inch
38.6x31.1x16.8
38.6x31.1x16.8
Dimensions of Carton Box (WxHxD)
inch
42.5x19x33
42.5x19x33
Dimensions of Package (WxHxD)
inch
42.6x19x33.7
42.6x19x33.7
Net Weight / Gross Weight
Lbs.
119 / 132
119 / 132
Refrigerant
Name of Refrigerant
R410A
R410A
Weight
Oz.
56.448
56.448
Connection Pipe
Length
inch
25
25
Gas Additional Charge
Oz/ft
0.2
0.2
Liquid Pipe Outer Diameter
inch
1/4
1/4
Gas Pipe Outer Diameter
inch
5/8
5/8
Max. Interunit height Difference
Ft.
33
33
Max. Interunit Piping Length
Ft.
82
82
* The above data is subject to change without notice. Please refer to the nameplate of the unit.