SERVICE MANUAL
R
−
410A Ductless Split System: DLF4(A/H), DLC4(A/H)
48
421 08 9204 00
TROUBLESHOOTING
The unit has onboard diagnostics. Error codes will appear on the LED display on the front panel of the indoor unit in place of the
temperature display. Error codes are also displayed on the outdoor unit microprocessor board with colored LED lights. The tables
explain the error codes for the specific models.
UNITS 9K & 12K, 115 Volts
Malfunction
Display on
Indoor Unit
State of the Lamps of Outdoor Unit PCB
Reasons
Error Code
Green
−
LED2
Red
−
LED3
Yellow_LED4
Stop for anti
−
freeze protection of
indoor
−
unit
E2
Flash 4 Times
Flash 3 Times Refrigerant leakage. Indoor unit air flow
blocked. Filter dirty.
Stop for discharge temp protection
E4
Flash 7 Times Low refrigerant. Capillary blocked. Ambient
temp is abnormal.
Stop for low voltage protection
E5
Flash 5 Times Low voltage. Ambient temp is abnormal.
Stop for communication malfunction
E6
No Flash
Communication line failure. Main PCB failure.
Outside interference. Wiring error.
Condensate pump failure.
Stop for compressor overload
protection
H3
Flash 8 Times Compressor overheat. Low refrigerant.
Capillary blocked.
Overload protection
H4
Flash 6 Times Ambient temp is abnormal. Heat exchanger
blocked.
Stop for IPM module protection
H5
Flash 4 Times IPM module over temperature. Low voltage.
Silica grease problem.
DC motor (indoor unit) does not
operate
H6
DC motor control terminal contact problem.
Fan does not rotate smoothly due to incorrect
installation. Motor or control panel is
damaged.
Indoor ambient temperature sensor
malfunction
F1
Bad terminal connection. Temp sensor
malfunction.
Indoor tube temperature sensor
malfunction
F2
Bad terminal connection. Temp sensor
malfunction.
Outdoor ambient temperature sensor
malfunction
F3
Flash 6 Times
Bad terminal connection. Temp sensor
malfunction.
Outdoor tube temperature sensor
malfunction
F4
Flash 5 Times
Bad terminal connection. Temp sensor
malfunction.
Outdoor discharge temperature
sensor malfunction
F5
Flash 7 Times
Bad terminal connection. Temp sensor
malfunction.
Automatic defrosting
H1
Flash 2 Times H1 signal normal operation, heat pump only.
Remark
1. Error codes only can be seen in the type which has the temperature display PCB. Some types do not have
this function and have only the LED’s on the outdoor PCB.
2. If there is normal communication between the Indoor and Outdoor unit the green LED will be on., and
flashing.