The EBDSPIR-AT-AD has capacity to store 20 Local
Scenes and 120 Area Scenes. By default all Scenes are
pre-programmed with the following channel levels, but
these can be changed as required:
NOTE:
Local Scene 20 and Area Scene 120 are
designated ‘off’ scenes within a system and should
normally be programmed with all channels off or at zero.
Scenes can be recalled by using an IR Handset or by a
switch/button plate via an AT-BB-IN Input Unit.
Local Scenes
1
2
3
4
5
6
...
19
20
Ch1 on
on
on
on
on
on
...
on
off
Ch2 100% 75% 50% 25% 100% 75% ... 50% 0%
Area Scenes
101 102 103 104 105 106 ...
119 220
Ch1 on
on
on
on
on
on
...
on
off
Ch2 100% 75% 50% 25% 100% 75% ... 50% 0%
Step 3: Re-program scenes
Each Scene has a Fade Rate, which is the time taken for
the existing output channel levels to fade to the levels
defined in the selected Scene. By default this is set to 3
seconds for all Scenes.
Each Scene also has a Maintained Illuminance Level
setting. By default this is set to 0 (i.e. disabled) for all
Scenes.
Scenes Used for Occupancy Detection
If movement is detected (in Presence mode), Local On
Scene 1 is selected. By default this switches Channel 1
On and sets Channel 2 to 100% with a 1 second Fade
Rate.
If no movement is detected for the Time Adjustment Period
(in Presence or Absence mode), Local Off Scene 20 is
selected. By default this switches Channel 1 Off and sets
Channel 2 to 0% with a 1 second Fade Rate.
NOTE:
These ‘On’ and ‘Off’ Scene selections cannot be
changed using the UHS4 handset. You can, however,
reprogram the levels for Scenes 1 and 20 if required.