12
Advanced programming
Parameter Name Default Value
Range / Options
Description
Programming
Devices
UHS4
UNLCDHS
For Device
Product ID
Automatically
assigned by the
device
1 to 999
A number used to uniquely identify each device within a range of
devices that are set to the same Local Code.
Building Code
1
1 to 999
A number shared by all devices that belong to the same building or
system.
Lock
0
Enable (1) or disable
(0)
Lock the An-10 network. Prevents more devices joining the network.
For
Channel 1
(Switched Output)
Local Code
1
1 to 999
A number corresponding to the Local Code of all devices to be
controlled by an associated input channel.
Sub Local Code(s)
Not set
1 to 99
0 to clear
A number corresponding to the Sub Local Code of all devices to be
controlled by an associated input channel. Up to 20 Sub Local
Codes can be set for Channel 1 and 2, e.g. 15 on Ch.1 and 5 on
Ch.2, etc.
Area Code(s)
999
1 to 999
0 to clear
A number corresponding to the Area Code of all devices to be
controlled by an associated input channel. Up to 32 Area Codes can
be set for Channel 1 and 2, e.g. up to 16 per channel, or 20 on Ch.1
and 12 on Ch.2, etc.
Circuit Number
1
1 to 999
Sets the circuit number for this channel.
Detection Mode
Presence
Presence or Absence
Presence mode allows the output to turn on when movement is
detected and off when movement ceases. Absence mode allows
the output to turn off when movement ceases, but must be manually
turned on first.
Output State
Set by Scene
0-100%
0=off
The current output state of the channel, for example as set by a
Scene Select command.
Light Level
(maintained illuminance)
Set by Scene
0 (disabled) or
1 to 999
The maintained illuminance target level of the channel, for example
as set by a Scene Select command. See page 8.
Raise from off
1
Enable (1) or disable
(0)
Enables raise from off feature.
Lower from off
1
Enable (1) or disable
(0)
Enables lower from off feature.
Emergency output 0
Enable (1) or disable
(0)
Enabling this sets the output to a ‘switched permanent live’ mode
for emergency ballasts.
Lux off period
0
0 to 999 in minutes
(0=15 seconds)
Number of minutes above the Lux Off level before a lux switching
decision is made.
Lux switching
enabled
1
Enable (1) or disable
(0)
Enables or disables the output channel to respond to lux switching
commands.
Detector enabled
1
Enable (1) or disable
(0)
Enables the output channel to be controlled by detector occupancy.
Detector inhibit
period
0
0 to 255
Detector inhibit period in 100s of milliseconds (255 = 25 seconds).
The tables on pages 12 to 15 give a summary of all programmable parameters for the EBDSPIR-AT-AD Sensor.