ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
319
Communication Protocol: has to be set as Modbus RTU.
Address: the address has to be set between 1~64, please note: the
configuration of M-7000 module address on PMC/PMD has to be set
exactly the same.
Baudrate: the Baudrate has to be set the same as the Baudrate of PMC/PMD
COM Port which the module will connect. All M-7000 modules’ Baudrate
have to be set the same as well
Data format: set to be “Engineering” format.
Please complete others setting of M-7000/DL module according to system’s
requirement. For more detailed information, please refer to DCON Utility manual as
below.
http://ftp.icpdas.com/pub/cd/8000cd/napdos/driver/dcon_utility/manual/
3.
For others ICP DAS I/O module, please refer to related user manual for the
configuration setting. In order to accurately connect with PMC/PMD, please
make sure of the COM port setting (Module address (1~255), Baudrate, Parity)
or Ethernet setting (IP address, Connection Port (1~65535), NetID (1~247)).
Please follow the links as below for the user manual of the related ICP DAS I/O
modules.
DL-100 module
Link
http://ftp.icpdas.com.tw/pub/cd/usbcd/napdos/dl_100/dl100tm4
File name dl_100tm485_v
XXX
DL-302 module
Link
http://ftp.icpdas.com.tw/pub/cd/usbcd/napdos/dl-300/document/
File name dl300_user_manial_english_v
XXX
IR module
Link
http://ftp.icpdas.com.tw/pub/cd/usbcd/napdos/ir/
File name ir-
XXX
/manual/ ir-
XXX
_usermanual_en_v
X
_
X