![ICP DAS USA PMD series User Manual Download Page 125](http://html1.mh-extra.com/html/icp-das-usa/pmd-series/pmd-series_user-manual_3622279125.webp)
ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
110
the status of the DI channel with the same channel number
on the M-7000/DL module will be copied to the DO channel.
For example, when the “DI Status Mapping” is enabled on
DO0, when the DI0 status is ON, DO0 will set to be ON, and
when the DI0 status is OFF, DO0 will set to be OFF as well.
After all settings are completed, click “OK” button to save the
changes and return to Modbus RTU Module List.
Please Note:
1.
To set up the Power On value of the DO channels on
M-7000/DL modules, please use DCON Utility to set the
value.
2.
The DO channels on M-7000/DL modules do not offer Pulse
Output function.
The AI channel setting for M-7000/DL module
The M-7000/DL module AI channel setting interface is shown as
below (using M-7018 as an example)