GT-530 user manual v1.0
2.4.2 for the detail.
DI-NO : Normal Open mode. When the DI circuit is shorten, the event is
triggered. GT-530 would send the alarm SMS. Refer to section
2.4.3 for the detail.
(3)
Trigger Time(sec)
:
Set the hold time of the DI triggered signal (0~9999
seconds)
(4)
DO ON : This function enable DO output when DI event is triggered.
(5)
DO ch.: Set the DO channel.
(6)
Time(sec) : Set the output time of DO channel (0~999 seconds). If the
power is just provided by Li-battery, GT-530 would not be into sleep
mode until the output time is reaching.
(7)
Event message : Set the user-defined message content. These message
would be included in event SMS.
GT-530 User Manual, Version 1.0, August 2009