background image

GT-530 user manual v1.0 

2.5

 

LED indicators 

 

There are three LED indicators to help users to judge the various conditions of 

GT-530. The description is as follows

 

A.

 

EXT(Red)

External Power LED to indicate whether the external power is 

input or not. The description is as follows: 

The external power is active 

The external power is not active 

on 

off 

B.

 

STA(Orange):System LED is to indicate if the GT-530 is normal or fail.   

Condition

External power 

Normal 

GSM Fail 

PIN code is wrong

On 

Blanking (1 sec) Always on or off Blinking per 50 ms

Off 

Off (sleep mode)

or 

Blanking (1 sec)

(wake up) 

Always on 

Blanking per 50 ms

C.

 

GSM (Green):The modem LED can indicate the status of GSM module. 

Modem normal 

Modem fail 

Blanking (3 sec) 

Off 
  or 

Blanking (not 3 sec) 

 

 

 

GT-530 User Manual, Version 1.0, August 2009 

10/48 

Summary of Contents for GT-530

Page 1: ...GT 530 user manual v1 0 GT 530 Intelligent SMS alarm controller User Manual v1 0 High Quality Industrial Data Acquisition and Control Products Publication Aug 2009 Ver 1 0...

Page 2: ...ny time without notice The information furnished by ICP DAS is believed to be accurate and reliable However no responsibility is assumed by ICP DAS for its use or for any infringements of patents or o...

Page 3: ...tility 13 3 1 Install NET Compact Framework 13 3 2 Install GT 530 Utility 15 4 GT 530 Utility operation 18 4 1 Main menu 19 4 2 Operation Language 21 4 3 Login 22 4 4 Main parameter 24 4 5 SMS Recorde...

Page 4: ...manual v1 0 5 6 PASS Password inquiry 46 6 Send Receive SMS by com port 47 6 1 Send data to COM port of GT 530 by SMS command 47 6 2 Send SMS from COM port 47 7 Troubleshooting 48 Publication Aug 2009...

Page 5: ...allowing you to use your mobile phone to monitor and control your business from any location Its alarm facilities provide a flexible way to distribute critical alarm information to any number of mobi...

Page 6: ...nter 2 DO 2 RS232 port z Digital input support NC normal close NO normal open Counter modes z Peroidic SMS report z Alarm SMS triggered by DI trigger or exceed Counter preset limits z Support simple c...

Page 7: ...GT 530 user manual v1 0 Application 2 Home security Application 3 Remote maintenance Application 4 SMS Tunnel Communication GT 530 User Manual Version 1 0 August 2009 3 48...

Page 8: ...wer or Li battery On Voltage 3 5 24VDC Off Voltage 1V Max Output D O 2 Channel Open collector output 500mA 24VDC 2 digital output channels Output type Open Collector NPN Load Voltage 24V Max Load Curr...

Page 9: ...h Li ion battery backup Option 1200 mAh Mechanical Casing Plastic Flammability UL 94V 0 materials Dimensions W x H x D 91 mm x 132 mm x 52 mm Installation DIN Rail Environment Operating Temperature 25...

Page 10: ...of the external power input DI DO Terminal No Pin Assignment 01 DI0 02 DI1 03 DI2 04 DI3 05 DI4 06 DI5 07 DI6 08 DI7 09 DI8 DI 10 DI9 11 DO0 12 DO1 DO 13 DO PWR DI DO 14 Ext GND COM Port Power Input...

Page 11: ...GT 530 user manual v1 0 2 3 Diemensions GT 530 User Manual Version 1 0 August 2009 7 48...

Page 12: ...e NC normal close The NC mode is used as normal close in relay application as follows The logical value of DI is 1 when the relay is ON in normal use When the relay is triggered as relay open the logi...

Page 13: ...plication as follows The logical value of DI is 0 when the relay is close in normal use When the relay is triggered as relay close the logical value of DI is 1 and the SMS would be sent If the counter...

Page 14: ...wer is active The external power is not active on off B STA Orange System LED is to indicate if the GT 530 is normal or fail Condition External power Normal GSM Fail PIN code is wrong On Blanking 1 se...

Page 15: ...tery to GT 530 F It is needed to wait for 30 50 seconds to search the GSM base and register to the ISP After finishing the process GT 530 would be in normal operation mode and the STA LED would blank...

Page 16: ...power supplying to GT 530 is from Li Battery If the voltage of Li Battery is lower than the preset limit GT 530 can send the SMS message to inform the users Note A new Li Battery can supply power to...

Page 17: ...Framework 2 0 or above in the PC the section 3 1 can be omitted 3 1 Installing NET Compact Framework A Plug shipment CD into the PC B Execute GT 530 Utility dotnetfx20 exe C The install figure is as...

Page 18: ...GT 530 user manual v1 0 3 The installation process would be going 4 After finishing the installation press Finish to exit the program GT 530 User Manual Version 1 0 August 2009 14 48...

Page 19: ...B Execute GT 530 Utility SMSUtilitySetup exe C The installation figure is as follows 1 Press Next to start the installation procedure 2 Select the installation path The default path is C Progrm Files...

Page 20: ...0 user manual v1 0 3 Input the name shown in All Programs Press Next to the next step 4 After finishing the installation procedure press OK to the next step GT 530 User Manual Version 1 0 August 2009...

Page 21: ...er manual v1 0 5 Press Finish to finish the installation procedure 6 Launch GT 530 Utility from the start menu Start All Programs GT 530 Utility GT 530 Utility GT 530 User Manual Version 1 0 August 20...

Page 22: ...g per 1 sec Normal mode Blanking per 50 ms The pin code is wrong The login windows would show the field to input pin or PUK code 2 Confirm the RS232 connection between GT 530 and PC is correct Users c...

Page 23: ...Tradition and Simplified Chinese interface Users can select which language interface they want from the Language item The language setting would be influencing on the encode of SMS 4 File There are i...

Page 24: ...the information of the last and next time of the return report 4 Counter Value Inquire and set the counter value 5 Change Password Change the login password 6 DO Control DI status Display the status o...

Page 25: ...ded on the selected language interface The format of SMS accords to the selected language If the 7 BITS format is set the maximum characters can be sent in SMS is 140 If UCS2 the maximum number is 70...

Page 26: ...GT 530 If the pin code in GT 530 is not correct the STA led would be blanking per 50 ms and GT 530 utility would ask for users to input Pin or PUK code 1 Asking for inputting PIN code If the PIN code...

Page 27: ...of times for inputting the wrong PUK code is more than allowed number the SIM card would be ineffective forever Therefore it is important to input the correct PUK code If the PIN or PUK code is correc...

Page 28: ...main menu 4 4 1 Phone Periodic report Alarm The following page is Phone Periodic Report Alarm Users can refer the explanation below 1 Machine ID The device ID would be shown in the report and alarm S...

Page 29: ...te SS second DI0 DI5 The counter values of DI0 DI5 If these DI channels are not set as counter mode the counter value would be zero Note If CRPT function is enabled and the return time is changed the...

Page 30: ...hine ID Report Date Report Time Event Message ALARM Indicate alarm report Machine ID Device ID Report Date Report date The format is YYYYMMDD YYYY year MM month DD day Report Time Report time The form...

Page 31: ...530 is abnormal This function can not be disabled It could make the wrong timing for report and the cause is the silver battery of GT 530 is abnormal After changing the silver battery the time of GT...

Page 32: ...ggered signal 0 9999 seconds 4 DO ON This function enable DO output when DI event is triggered 5 DO ch Set the DO channel 6 Time sec Set the output time of DO channel 0 999 seconds If the power is jus...

Page 33: ...ing back the setting of device parameters from par file and displaying in Device parameter window When press import button a file selection window would pop up for users to choice the par file B Expor...

Page 34: ...maximum number of CRPT report record is 64 2 Save Save these records to a file csv 3 Delete all Delete all CRPT report records from GT 530 Text field 1 No The number of RTCP records 2 Report time CRPT...

Page 35: ...Report record In this page users can inquire all event report of GT 530 The explanation is below Operation 1 Read Read all the CRPT report from GT 530 The maximum number of CRPT report records is 64 2...

Page 36: ...time would be updated 2 Set Set the GT 530 time according the Device Time field After setting the time successfully the information of GT 530 time and CRPT report time would be updated 3 Read Read ba...

Page 37: ...he maximum is 999999999 This field is enabled when DI is set as counter mode 4 Counter Alarm Enable the counter alarm 5 Alarm Value Counter alarm value current value alarm value This field can not be...

Page 38: ...s password is also applied in SMS command to GT 530 These SMS commands is described in chapter 5 Text field 1 Old password Input the current password 2 New password Input the new password maximum 12 c...

Page 39: ...the status of DIs Text field 1 DI0 DI9 DO0 DO1 Grey the voltage logic is high Red the voltage logic is low Operation 1 Read Read back the status of DI0 DI9 and DO0 DO1 from GT 530 2 DO0 DO1 ON Set th...

Page 40: ...eeds to open the external power when using utility to configure GT 530 2 Level Show the percentage of battery volume If the battery is not connected to GT 530 The value is about 60 3 Voltage The volta...

Page 41: ...11 Signal Quality This window can show GSM signal strength Text field The strength is divided into 5 sections shown in percentage Operation 1 Read Read the GSM signal strength GT 530 User Manual Vers...

Page 42: ...how the version of Utility and firmware Text field 1 Firmware version show the version information of GT 530 s firmware 2 Utility version show the version information of GT 530 s utility Operation Rea...

Page 43: ...T 530 as factory settings including password The steps are below 1 Connect COM3 TX and COM3 RX 2 Make sure the STA led is blanking per 1 sec 3 Select the Recover to Factory Settings 4 13 2 Reset GT 53...

Page 44: ...numbers set in GT 530 These phone numbers must be set to have Allowed authority If the phone number is not in the list GT 530 would not reply to any command Command Table SMS command Description DTIME...

Page 45: ...our MM minute SS second Example Set the time as 2009 04 10 10 03 00 TIME 000000 20090410 100300 Inquiry the time TIME 000000 3 Response MID TIME Result YYYYMMDD HHMMSS MID Machine ID TIME Command name...

Page 46: ...r PLUS mode 0 999 seconds Example Set DO1 output to on DOC1 000000 ON Set DO1 output to on during 20 seconds DOC1 000000 PLUS 20 3 Response MID DOCn Result CMD Second MID Machine ID DOC command name n...

Page 47: ...ER The format is wrong or authority is not allowed DI0 The DI0 counter value If the DI is not set as counter the value is 0 DI1 The DI1 counter value If the DI is not set as counter the value is 0 DI2...

Page 48: ...Result DI0 DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DI9 DO0 DO1 MID Machine ID DIV command name Result command result OK command successflly NO the password is wrong ER The format is wrong or authority is not...

Page 49: ...000000 3 Response MID BAT Result Pext Percent Voltage MID Machine ID BAT command name Result command result OK command successfully NO the password is wrong ER The format is wrong or authority is not...

Page 50: ...be set the authority of SMS Command 2 Request Inquiry PASS Example Inquire the password of GT 530 PASS 3 Response MID PASS Result Password Password MID Machine ID PASS command name Result command resu...

Page 51: ...ommand header is The first setting phone number just has the authority to use this function with the Allowed enabling The command support 7 Bits format Command Message Message The message is sent to c...

Page 52: ...Check wire connection Check the counter signal is at 5 40Hz Check the DI mode setting Must be counter mode 6 The content of received SMS is abnormal Please select the correct language to set the conte...