Chapter 3
Web Configuration Page
ET-7000 AIO User Manual, Apr. 2009, V1.03, EMH-011-103----------
72
Modbus Registers and Factory Defaults
Common Functions
Modbus Address
Points
Description
Range
Factory default
40557 1
Set host watch dog timer
(Second)
5~65535 (Enable)
(<5: Disable)
0 (Disable)
DO Module Functions
Modbus Address Points (Max.)
Description
Range
Factory default
00435~00514
80
Power on value for DO
0=off / 1=on
0
00515~00594
80
Safe value for DO
0=off / 1=on
0
AI Module Functions
Modbus Address Points (Max.)
Description
Range
Factory default
00595~00626
32
Enable/Disable AI channel
0=disabled
1=enabled
1
00628
1
Normal/Fast mode for AI
0=normal (16 bit)
1=fast (12 bit)
0
00629
1
50/60 Hz rejection for AI
0= 50 Hz
1=60 Hz
1
40296~40327
32
High alarm value for AI
-32768 ~ +32767
32767
40328~40359
32
Low alarm value for AI
-32768 ~ +32767
-32768
40700~40731
32
High alarm mode
0= moment
1= latched
0
40732~40763 32
Low
alarm
mode
0= moment
1= latched
0
40427~40458
32
Type code for AI
Refer to type code
table
Depends on
the type of
Module
Summary of Contents for ET-7000 series
Page 1: ...ET 7000 series Ethernet Remote I O Module User Manual...
Page 8: ......
Page 38: ...Chapter 1 Introduction ET 7000 AIO User Manual Apr 2009 V1 04 EMH 011 104 38 ET 7018Z...
Page 60: ...Chapter 3 Web Configuration Page ET 7000 AIO User Manual Apr 2009 V1 04 EMH 011 104 60...
Page 70: ...Chapter 3 Web Configuration Page ET 7000 AIO User Manual Apr 2009 V1 04 EMH 011 104 70...
Page 71: ...Chapter 3 Web Configuration Page ET 7000 AIO User Manual Apr 2009 V1 04 EMH 011 104 71...
Page 88: ...Chapter 3 Web Configuration Page ET 7000 AIO User Manual Apr 2009 V1 04 EMH 011 104 88...