Appendix D: Modbus Application Notes
ET-7000 AIO User Manual, Apr. 2009, V1.04, EMH-011-104
----------
145
High/Low Alarm of the average value of all AI channels
The average value of all AI channels also can equip with the alarm function like the AI
High/Low Alarm. For the detailed description, please refer the
AI High/Low Alarm
.
Register
Description
10336
High alarm for the average value of all AI registers
0=normal
1=alarm
10337
Low alarm for the average value of all AI registers
0=normal
1=alarm
40198
High alarm value for Average value of all AI channels
0 ~ 65535 or –32768 ~ +32767
40199
Low alarm value for Average value of all AI channels
0 ~ 65535 or –32768 ~ +32767