ET-2200 Series Ethernet I/O Modules
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-62 -
The table describes the parameters contained in the "
DIO Synchronization
" section.
Item
Description
Synchronous DIO (Local Mirror)
Note:
ET-2254 supports these functions when low 8-bit are DI0 to DI7 and high 8-bit are DO8 to DO15.
Level Sync (DO = DI)
This parameter is used to enable the synchronization operation in
Digital Input/Output function.
Rising Active (DO = ON)
This parameter is used to enable rising active in Digital Input
function. When the specified DI state changed from OFF to ON, the
corresponding DO will be set to ON.
Falling Active (DO = ON)
This parameter is used toenable falling active in Digital Input
function. When the specified DI state changed from ON to OFF, the
corresponding DO will be set to ON.
Additional Controls
Min-Switch Time of DO
(0 to 65535 Seconds)
This parameter is used to set the minimum switching time between
the ON and OFF state of the Digital Output. This protects some
machines from being damaged by too many ON/OFF switches in a
short time.
Auto-off Time of DO
(0 to 65535 Seconds)
This parameter is used to set the auto-off time of the Digital Output.
If the Digital Output is ON, the Digital Output will be auto-off based
on the configured time value.
Update Settings
Click this button to save the revised settings of DIO configuration to
the ET-2200 module.