ET-2200 Series Ethernet I/O Modules
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-93 -
5.
I/O Pair Connection Applications
The ET-2200 series modules can be used to create DI-to-DO pair connections via the Ethernet. Once
the configuration is complete, the modules can then poll the status of the local DI channels and then
use the Modbus/TCP protocol to continuously write to a remote DO device in the background. This
is useful when connecting Digital I/O devices that do not the mselves have Ethernet capability. The
following will describe how to correctly configure the I/O pair-connection function.
5.1
One Module Polling the Remote DI/DO
(1-to-1, Pull / Push Mode)
Step 1: Connect the device to a Network, a PC and a Power supply.
Confirm that the ET-2200 series modules are functioning correctly. Refer to
for more details. An example configuration shown below:
Note that ET-2260 module is used in this example.
Figure 5-1.1