ET-2200 Series Ethernet I/O Modules
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-66 -
The table describes the parameters contained in the "
I/O Pair-Connection Settings
" section.
Item
Description
Defaults
Mode
This parameter is used to define the Server mode for the ET-2200
series module.
Disable
: Server mode (Slave).
PULL
: Pull remote AI (DI) to local AO (DO) in the Client mode (Master).
PUSH
:
Push local AI (DI) to remote AO (DO) in the Client mode (Master).
Disable
Remote IP
The IP address of the remote device to access.
0
Remote Port
The TCP port number of the remote device to access.
Range: 0 to 65535.
502
Net ID
The Modbus Net ID of the remote device to access.
Range: 1 to 247.
1
Scan Time
For
“PULL”
mode, the module will update the I/O states based on the
time period of the Scan Time parameter.
For
“PUSH”
mode, the module will update remote AO (DO) state
when the local AI (DI) state is changed. The module will also force
update remote AO (DO) when the local AI (DI) is no change during the
time period of the Scan Time parameter.
Range: 1000 to 42949672965 ms.
1000 ms
AI (DI) Count
This parameter specifies how many I/O channels are mapped.
Range: 1 to 16; 0= Disable.
0
AI (DI) Addr
For “PULL” mode, this parameter specifies the base address of the
Remote AI (DI) device that will be mapped to the Local AO (DO)
register. The range depends on the type of remote device being used.
For “PUSH” mode, this parameter specifies the base address of the
Local AI (DI) register that will be mapped to the Remote AO (DO)
device. The range depends on the type of ET-2200 module being used.
0
AO (DO) Addr
For
“PULL”
mode, this parameter specifies the base address of the
Local AO
(DO) register
that will be mapped to the
Remote AI (DI) device
. The range
depends on the type of the ET-2200 module being used.
For
“PUSH”
mode, this parameter specifies the base address of the
Remote
AO (DO) device
that will be mapped to the
Local AI (DI) register
. The range
depends on the type of remote device being used.
0
TCP/UDP
This parameter is used to set the type of Modbus protocol to be used and can
be either TCP or UDP
for the “PUSH” mode only.
TCP
Update
Click
“Submit”
button to save the revised settings to the ET-2200 module.