ET-2200 Series Ethernet I/O Modules
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-30 -
Output Wiring for ET-2260/2261/2261-16:
Output Wiring for ET-2268:
Note for the ET-2260/2261/2261-16/2268:
When inductive loads are connected to the
relays, a large counter electromotive force may
occur when the relay actuates because of the
energy stored in the load. These fly back voltages
can severely damage the relay contacts and
greatly shorten the relay life. Limit these fly back
voltages at your inductive load by installing a
flyback diode for DC loads or a metal oxide
varistor for AC loads.
Varistor Selection:
Operating Voltage
Varistor Voltage
Max. Peak Current
100 ~ 120 V
AC
240 ~ 270 V
AC
> 1000 A
200 ~ 240 V
AC
440 ~ 470 V
AC
> 1000 A