C-10. CL-211 / CL-211-E Modbus Address Mappings (Base 1)
- 206 -
Address Description
Attribute
00321 ~
00327
Enable/disable alarm of channel 0 to 6, write 0 to disable alarm ;
write 1 to enable alarm.
channel 0: CO in 1ppm,
channel 1: PM2.5 in 1ug/m
3
channel 2: relative humidity in 0.01%,
channel 3: temperature in 0.01°C,
channel 4: temperature in 0.01°F,
channel 5: dew point temperature in 0.01°C,
channel 6: dew point temperature in 0.01°F
R/W
00337 ~
00343
Alarm type, momentary or latched, of channel 0 to 6, write 0 to
enable momentary alarm mode; write 1 to enable latched alarm
mode.
channel 0: CO in 1ppm,
channel 1: PM2.5 in 1ug/m
3
,
channel 2: relative humidity in 0.01%,
channel 3: temperature in 0.01°C,
channel 4: temperature in 0.01°F,
channel 5: dew point temperature in 0.01°C,
channel 6: dew point temperature in 0.01°F
R/W
00385 ~
00391
Write 1 to clear high latched analog input value of channel 0 to 6,
channel 0: CO in 1ppm,
channel 1: PM2.5 in 1ug/m
3
,
channel 2: relative humidity in 0.01%,
channel 3: temperature in 0.01°C,
channel 4: temperature in 0.01°F,
channel 5: dew point temperature in 0.01°C,
channel 6: dew point temperature in 0.01°F
W
00417 ~
00423
Write 1 to clear low latched analog input value of channel 0 to 6
channel 0: CO in 1ppm,
channel 1: PM2.5 in 1ug/m
3
,
channel 2: relative humidity in 0.01%,
channel 3: temperature in 0.01°C,
channel 4: temperature in 0.01°F,
channel 5: dew point temperature in 0.01°C,
channel 6: dew point temperature in 0.01°F
W
00449 ~
00455
Enable/disable beep on alarm for channel 0 to 6
R/W